Exide S47-0079 AC fuse blows, DC fuse blows, Excessive water loss in battery, General Maintenance

Page 15

4.3. AC fuse blows.

POSSIBLE CAUSE

A.Incorrect fuse rating.

B.Incorrect AC voltage.

C.Fuse Block holding clips loose.

D.Shorted transformer winding.

4.4. DC fuse blows.

POSSIBLE CAUSE

A.Reversed battery connector.

B.Incorrect fuse rating.

C.Shorted diode.

4.5. Excessive water loss in battery.

POSSIBLE CAUSE

A.Charging rate is too high. See Section 1.8.

B.Charger amp-hour rating exceeds the battery amp-hour rating.

C.Battery has defective cells.

4.6. Low specific gravity at the end of the charge cycle.

POSSIBLE CAUSE

A.Battery was over-discharged.

B.Charger amp-hour rating is less than the battery AH rating.

C.Defective open diode.

D.Charging rate is too low. See Section 1.8.

E.Battery has defective cells.

F.Battery has been over-watered.

4.7. Charger does not turn off when the control terminates the charge cycle.

POSSIBLE CAUSE

A.Defective control.

B.AC contactor has welded contacts.

4.8. General Maintenance

The charger requires a minimum of maintenance. Connections and terminals should be kept clean and tight. The charger should be periodically cleaned with an air hose to prevent any excessive dirt build up on components. Care should be taken not to bump or move any adjustments during cleaning. Make sure that both the AC lines and the battery are disconnected before cleaning. The frequency of this type of maintenance depends on the environment in which this unit is installed. If any cabinet sheet metal panels are removed for cleaning, be certain they are properly reinstalled upon completion.

15

Image 15
Contents GNB Section Description IndexImportant Save These Instructions Location InstallationLine Voltage Adjustments ReceivingPower Transformer Setting Connecting AC Service to the Charger AC Service RequirementsBattery Connector and Charging Cable Charging Rate AdjustmentGrounding the Charger Operation 1 046-0371 Control Feature SummaryOperation Normal Daily ChargeDelayed Start Equalize ChargeAuto- Refresh Charge Charge Time Viewing Charge InformationDisplay Description Charge IndicationsJumper Settings 10 F3 Low Battery OverrideParameter Message Range ProgrammingPossible Cause Optional FeaturesDC fuse blows Excessive water loss in batteryGeneral Maintenance AC fuse blowsReplaceable Parts Ordering InformationRecommended Spares Part Number Description Condensers Spare Parts ListThree Phase Charger Schematic # Single Phase Charger Schematic # 02-490