Bryant 558F III. Install External Trap for Condensate Drain, IV. RIG and Place Unit, Positioning

Page 2

Fig. 1 — Horizontal Conversion Panels

Ducts passing through an unconditioned space must be insu- lated and covered with a vapor barrier.

If plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with applicable fire codes.

If electrical connections are to be routed through the bottom of the unit, attach accessory thru-the-bottom service connections to the basepan in accordance with installation instructions.

A minimum clearance is not required around ductwork. Cab- inet return-air static pressure (a negative condition) should not exceed 0.30 in. wg with economizer or 0.45 in. wg without economizer.

III.STEP 3 — INSTALL EXTERNAL TRAP FOR CONDENSATE DRAIN

The unit’s 3/4-in. condensate drain connections are located on the bottom and side of the unit. Unit discharge connections do not determine the use of drain connections; either drain connection can be used with vertical or horizontal applications.

When using the standard side drain connection, ensure the plug in the alternate bottom connection (in center of pan) is tight before installing the unit.

To use the bottom drain connection for a roof curb installa- tion, relocate the factory-installed plug from the bottom con- nection to the side connection. See Fig. 4. The piping for the condensate drain and external trap can be completed after the unit is in place.

All units must have an external trap for condensate drain- age. Install a trap at least 4 in. deep and protect against freeze-up. If a drain line is installed downstream from the external trap, pitch the line away from the unit at 1 in. per 10 ft of run. Do not use a pipe size smaller than the unit connection (3/4-in.). See Fig. 5.

The center drain plug looks like a star connection, however it can be removed with a 1/2 in. socket drive extension.

IV. STEP 4 — RIG AND PLACE UNIT

Inspect unit for transportation damage. File any claim with transportation agency. Keep unit upright and do not drop. Spreader bars are not required if top crating is left on unit. Rollers may be used to move unit across a roof. Level by using unit frame as a reference. See Tables 1A and 1B and Fig. 6 for additional information. Operating weight is shown in Tables 1A and 1B and Fig. 6.

Lifting holes are provided in base rails as shown in Fig. 6 and 7A and 7B. Refer to rigging instructions on unit.

CAUTION: All panels must be in place when rig- ging and lifting. Unit is not designed for handling by a fork truck. Damage to unit may result.

A. Positioning

Maintain clearance around and above unit to provide proper airflow and service access. See Fig. 7A and 7B.

Position unit on roof curb so that the following clearances are maintained: 1/4-in. clearance between roof curb and base rails on duct end, front and back of unit; 35/16-in. clearance between roof curb and condenser fan end of unit (see Fig. 2, sections A-A and C-C).

Do not install unit in an indoor location. Do not locate unit air inlet near exhaust vents or other sources of contaminated air.

Although unit is weatherproof, guard against water from higher level runoff and overhangs.

After unit is in position, remove shipping materials and rig- ging skid.

2

Image 2
Contents II. Field Fabricate Ductwork ContentsSafety Considerations Positioning III. Install External Trap for Condensate DrainIV. RIG and Place Unit Roof Curb Details 558F ‘‘A’’‘‘C’’ Base Unit Dimensions 558F090,102,120,150 Base Unit Dimensions 558F091,103,121,151 Physical Data 558F090,102,120,150 Units 558F Unit SizePhysical Data 558F091,103,121,151 Units Ashrae 90.1-1999 Compliant UnitsMake Electrical Connections Field Power SupplyField Control Wiring Voltage Compressor OFM Electric Power Disconnect Nominal Type FLA Size 150 Voltage Compressor 103 151 Type FLA 17.0 17.1 31.4 136 34.0 34.1 52.7 51.0 51.2 60.8 150 44.9 234/234 017 10.4 21.7 25.0 006 49.1 277/277 017 10.4 21.7 25.0 006 61.0 364/364 017 10.4 21.7 25.0 012 Conduit Installation Convenience OutletDamper Panel with Manual Outdoor-Air Damper Installed EconoMi$er IV Component Locations Barometric Flow Capacity EconoMi$er IV Control Modes EconoMi$er IV Sensor UsageOutside Air Temperature Changeover Set Points Enthalpy Changeover Set Points Page CO2 Sensor Standard Settings VII. Adjust EVAPORATOR-FAN Speed Typical Belt-Drive Motor Mounting for Sizes 090,091,102,103Evaporator-Fan Motor Efficiency Fan Rpm at Motor Pulley SettingsAccessory/FIOP Static Pressure* in. wg Evaporator Fan Motor Data General FAN Performance Notes511 492 External Static Pressure in. wgRpm Bhp Watts 519 518534 571 611 768 678 982 511 492 591 680 660 885519 518 597 709 666 916 550 629 624 832534 571 611 768 678 982 739 1210 795 1453 511 492 591 680 660 885 722 1106 779 1342519 518 597 709 666 916 727 1140 784 1378 550 629 624 832 690 1051 750 1285 805 1533663 504 468 584 653 654 855646 679646 1071 711 1313 770 1568 824 1835 504 468 584 653 654 855 716 1074 774 1307630 985 696 1220 756 1469 811 1731 663 1162 726 1411 784 1672 837 1944557 658 627 810 532 559 604 702 668 846545 607 615 755 678 903 570 712 638 869557 658 627 810 689 963 745 1117 797 1271 532 559 604 702 668 846 726 990 779 1136545 607 615 755 678 903 735 1052 788 1202 570 712 638 869 699 1026 755 1184 806 13431153 3999 1134 37011144 3847 1162 4154739 1385 792 1572 840 1758 726 1299 779 1481 828 1662683 753 1474 804 1666 852 1857780 1665 739 1385 792 1572753 1474 804 1666 794 1767483 461 571 665 465 402 555 596471 421 560 618 495 503 581 715483 461 571 665 644 881 465 402 555 596 629 802471 421 560 618 634 828 495 503 581 715 654 937483 461 571 665 644 881 708 1109 766 1348 465 402 555 596 629 802 694 1021 753 1252471 421 560 618 634 828 699 1050 757 1283 495 503 581 715 654 937 717 1171 775 1416675 1454 459 384 550 575 625 778662 1361 943 2241675 1454 745 1771 806 2093 862 2422 913 2758 459 384 550 575 625 778 690 994 748 1221662 1361 732 1670 794 1985 851 2307 903 2635 689 1553 757 1877 818 2207 873 2543 924 2886505 597 581 723 647 855 484 506 562 625 630 752494 550 571 672 638 802 516 647 590 776 655 911505 597 581 723 647 855 706 996 761 1146 484 506 562 625 630 752 691 888 747 1035494 550 571 672 638 802 699 941 754 1089 516 647 590 776 655 911 714 1055 768 1207627 1316 690 1481 747 1648 800 1821 604 1155 669 1312 728 1473 782 1639616 1233 680 1395 738 1559 791 1728 639 1402 701 1570 757 1741 809 1917697 1243 750 1423 801 1608 850 1799 628 997 685 1167 739 1343 791 1525 841 1712641 709 1322 761 1506 812 1695734 1492 784 1683 628 997 685 1167 739 1343 791 1525697 1243 750 1423 801 1608 747 1582 796 1777PRE-START-UP Internal WiringVI. Refrigerant Service Ports START-UP Unit PreparationXII. Operating Sequence Safety ReliefVIII. Cooling Condenser Coil Service CleaningEvaporator Coil Condensate DrainIII. Evaporator FAN Belt Inspection VI. Economizer AdjustmentII. Lubrication Manual OUTDOOR-AIR DamperIX. LOSS-OF-CHARGE Switch To Use Cooling Charging ChartsVIII. HIGH-PRESSURE Switch XI. Replacement PartsCooling Charging Chart 558F120 Cooling Charging Chart 558F091 Troubleshooting Unit Troubleshooting II. ECONOMI$ER IV TroubleshootingEconoMi$er IV Preparation DCV Demand Controlled Ventilation and Power ExhaustEconoMi$er IV Troubleshooting Completion Differential EnthalpyTypical Unit Wiring Schematic Cooling Service Analysis Terminal† EconoMi$er IV Input/Output LogicDemand Control Enthalpy Index Service Training Call for Free CatalogCopyright 2005 Bryant Heating & Cooling Systems Catalog no Page Preliminary Information START-UP ChecklistTemperatures III. START-UP Electrical
Related manuals
Manual 170 pages 34.1 Kb

558F specifications

The Bryant 558F is a highly efficient and versatile gas furnace designed to provide reliable heating for residential spaces. Known for its exceptional performance and advanced technology, the 558F caters to homeowners looking for comfort, efficiency, and sustainability in their heating solutions.

One of the primary features of the Bryant 558F is its two-stage heating capability. This system allows the furnace to operate at different levels of output, optimizing energy consumption based on the heating demands of the home. By operating at a lower stage most of the time, the 558F can maintain consistent indoor temperatures while using less energy, leading to reduced utility bills.

The furnace is also equipped with aVariable Speed ECM blower motor. This feature provides enhanced air distribution and comfort by allowing for more precise control over airflow. The variable speed operation ensures that the furnace can adjust to the heating needs of the space without the constant on-off cycling, promoting quieter operation and better efficiency.

In terms of efficiency ratings, the Bryant 558F boasts an impressive Annual Fuel Utilization Efficiency (AFUE) rating of up to 96%. This high rating indicates that the furnace converts a significant portion of its fuel into usable heat, making it an environmentally friendly choice. With lower greenhouse gas emissions, homeowners not only benefit from cost savings but also contribute to reducing their carbon footprint.

Additionally, the furnace incorporates advanced combustion technology, including a durable heat exchanger designed for longevity and efficiency. This component is vital for maximizing heat transfer while minimizing heat loss, contributing to the overall performance of the unit.

The Bryant 558F is compatible with the manufacturer's Infinity System control, providing homeowners with a user-friendly interface to manage their heating system effectively. This compatibility allows for the integration of smart home technology, enabling remote access and programmable settings for added convenience.

Installation and maintenance of the Bryant 558F are straightforward, thanks to its compact design and thoughtful layout. Homeowners can find peace of mind knowing that service and upkeep are manageable, prolonging the life of the furnace.

In summary, the Bryant 558F gas furnace combines efficiency, advanced technology, and reliability to provide exceptional indoor comfort. With its two-stage heating, variable speed blower motor, and high AFUE rating, the 558F stands out as an optimal heating solution for modern homes seeking both performance and sustainability.