Bryant 558F EconoMi$er IV Preparation, Differential Enthalpy, Single Enthalpy, Supply-Air Input

Page 62

A. EconoMi$er IV Preparation

This procedure is used to prepare the EconoMi$er IV for troubleshooting. No troubleshooting or testing is done by performing the following procedure.

NOTE: This procedure requires a 9-v battery, 1.2 kilo-ohm resistor, and a 5.6 kilo-ohm resistor which are not supplied with the EconoMi$er IV.

IMPORTANT: Be sure to record the positions of all potenti- ometers before starting troubleshooting.

1.Disconnect power at TR and TR1. All LEDs should be off. Exhaust fan contacts should be open.

2.Disconnect device at P and P1.

3.Jumper P to P1.

4.Disconnect wires at T and T1. Place 5.6 kilo-ohm re- sistor across T and T1.

5.Jumper TR to 1.

6.Jumper TR to N.

7.If connected, remove sensor from terminals SO and +. Connect 1.2 kilo-ohm 4074EJM checkout resistor across terminals SO and +.

8.Put 620-ohm resistor across terminals SR and +.

9.Set minimum position, DCV set point, and exhaust potentiometers fully CCW (counterclockwise).

10.Set DCV maximum position potentiometer fully CW (clockwise).

11.Set enthalpy potentiometer to D.

12.Apply power (24 vac) to terminals TR and TR1.

B. Differential Enthalpy

To check differential enthalpy:

1.Make sure EconoMi$er IV preparation procedure has been performed.

2.Place 620-ohm resistor across SO and +.

3.Place 1.2 kilo-ohm resistor across SR and +. The Free Cool LED should be lit.

4.Remove 620-ohm resistor across SO and +. The Free Cool LED should turn off.

5.Return EconoMi$er IV settings and wiring to normal after completing troubleshooting.

C.Single Enthalpy

To check single enthalpy:

1.Make sure EconoMi$er IV preparation procedure has been performed.

2.Set the enthalpy potentiometer to A (fully CCW). The Free Cool LED should be lit.

3.Set the enthalpy potentiometer to D (fully CW). The Free Cool LED should turn off.

4.Return EconoMi$er IV settings and wiring to normal after completing troubleshooting.

D.DCV (Demand Controlled Ventilation) and Power Exhaust

To check DCV and Power Exhaust:

1.Make sure EconoMi$er IV preparation procedure has been performed.

2.Ensure terminals AQ and AQ1 are open. The LED for both DCV and Exhaust should be off. The actuator should be fully closed.

3.Connect a 9-v battery to AQ (positive node) and AQ1 (negative node). The LED for both DCV and Exhaust should turn on. The actuator should drive to between 90 and 95% open.

4.Turn the Exhaust potentiometer CW until the Ex- haust LED turns off. The LED should turn off when the potentiometer is approximately 90%. The actua- tor should remain in position.

5.Turn the DCV set point potentiometer CW until the DCV LED turns off. The DCV LED should turn off when the potentiometer is approximately 9 v. The ac- tuator should drive fully closed.

6.Turn the DCV and Exhaust potentiometers CCW un- til the Exhaust LED turns on. The exhaust contacts will close 30 to 120 seconds after the Exhaust LED turns on.

7.Return EconoMi$er IV settings and wiring to normal after completing troubleshooting.

E.DCV Minimum and Maximum Position

To check the DCV minimum and maximum position:

1.Make sure EconoMi$er IV preparation procedure has been performed.

2.Connect a 9-v battery to AQ (positive node) and AQ1 (negative node). The DCV LED should turn on. The actuator should drive to between 90 and 95% open.

3.Turn the DCV Maximum Position potentiometer to midpoint. The actuator should drive to between 20 and 80% open.

4.Turn the DCV Maximum Position potentiometer to fully CCW. The actuator should drive fully closed.

5.Turn the Minimum Position potentiometer to mid- point. The actuator should drive to between 20 and 80% open.

6.Turn the Minimum Position Potentiometer fully CW. The actuator should drive fully open.

7.Remove the jumper from TR and N. The actuator should drive fully closed.

8.Return EconoMi$er IV settings and wiring to normal after completing troubleshooting.

F.Supply-Air Input

To check supply-air input:

1.Make sure EconoMi$er IV preparation procedure has been performed.

2.Set the Enthalpy potentiometer to A. The Free Cool LED turns on. The actuator should drive to between 20 and 80% open.

3.Remove the 5.6 kilo-ohm resistor and jumper T to T1. The actuator should drive fully open.

4.Remove the jumper across T and T1. The actuator should drive fully closed.

5.Return EconoMi$er IV settings and wiring to normal after completing troubleshooting.

G.EconoMi$er IV Troubleshooting Completion

This procedure is used to return the EconoMi$er IV to opera- tion. No troubleshooting or testing is done by performing the following procedure.

1.Disconnect power at TR and TR1.

2.Set enthalpy potentiometer to previous setting.

3.Set DCV maximum position potentiometer to previ- ous setting.

4.Set minimum position, DCV set point, and exhaust potentiometers to previous settings.

5.Remove 620-ohm resistor from terminals SR and +.

6.Remove 1.2 kilo-ohm checkout resistor from termi- nals SO and +. If used, reconnect sensor from termi- nals SO and +.

7.Remove jumper from TR to N.

8.Remove jumper from TR to 1.

9.Remove 5.6 kilo-ohm resistor from T and T1. Recon- nect wires at T and T1.

10.Remove jumper from P to P1. Reconnect device at P and P1.

11.Apply power (24 vac) to terminals TR and TR1.

62

Image 62
Contents II. Field Fabricate Ductwork ContentsSafety Considerations Positioning III. Install External Trap for Condensate DrainIV. RIG and Place Unit Roof Curb Details 558F ‘‘A’’‘‘C’’ Base Unit Dimensions 558F090,102,120,150 Base Unit Dimensions 558F091,103,121,151 Physical Data 558F090,102,120,150 Units 558F Unit SizePhysical Data 558F091,103,121,151 Units Ashrae 90.1-1999 Compliant UnitsMake Electrical Connections Field Power SupplyField Control Wiring Voltage Compressor OFM Electric Power Disconnect Nominal Type FLA Size 150 Voltage Compressor 103 151 Type FLA 17.0 17.1 31.4 136 34.0 34.1 52.7 51.0 51.2 60.8 150 44.9 234/234 017 10.4 21.7 25.0 006 49.1 277/277 017 10.4 21.7 25.0 006 61.0 364/364 017 10.4 21.7 25.0 012 Conduit Installation Convenience OutletDamper Panel with Manual Outdoor-Air Damper Installed EconoMi$er IV Component Locations Barometric Flow Capacity EconoMi$er IV Control Modes EconoMi$er IV Sensor UsageOutside Air Temperature Changeover Set Points Enthalpy Changeover Set Points Page CO2 Sensor Standard Settings VII. Adjust EVAPORATOR-FAN Speed Typical Belt-Drive Motor Mounting for Sizes 090,091,102,103Evaporator-Fan Motor Efficiency Fan Rpm at Motor Pulley SettingsAccessory/FIOP Static Pressure* in. wg Evaporator Fan Motor Data General FAN Performance Notes511 492 External Static Pressure in. wgRpm Bhp Watts 519 518534 571 611 768 678 982 511 492 591 680 660 885519 518 597 709 666 916 550 629 624 832534 571 611 768 678 982 739 1210 795 1453 511 492 591 680 660 885 722 1106 779 1342519 518 597 709 666 916 727 1140 784 1378 550 629 624 832 690 1051 750 1285 805 1533663 504 468 584 653 654 855646 679646 1071 711 1313 770 1568 824 1835 504 468 584 653 654 855 716 1074 774 1307630 985 696 1220 756 1469 811 1731 663 1162 726 1411 784 1672 837 1944557 658 627 810 532 559 604 702 668 846545 607 615 755 678 903 570 712 638 869557 658 627 810 689 963 745 1117 797 1271 532 559 604 702 668 846 726 990 779 1136545 607 615 755 678 903 735 1052 788 1202 570 712 638 869 699 1026 755 1184 806 13431153 3999 1134 37011144 3847 1162 4154739 1385 792 1572 840 1758 726 1299 779 1481 828 1662683 753 1474 804 1666 852 1857780 1665 739 1385 792 1572753 1474 804 1666 794 1767483 461 571 665 465 402 555 596471 421 560 618 495 503 581 715483 461 571 665 644 881 465 402 555 596 629 802471 421 560 618 634 828 495 503 581 715 654 937483 461 571 665 644 881 708 1109 766 1348 465 402 555 596 629 802 694 1021 753 1252471 421 560 618 634 828 699 1050 757 1283 495 503 581 715 654 937 717 1171 775 1416675 1454 459 384 550 575 625 778662 1361 943 2241675 1454 745 1771 806 2093 862 2422 913 2758 459 384 550 575 625 778 690 994 748 1221662 1361 732 1670 794 1985 851 2307 903 2635 689 1553 757 1877 818 2207 873 2543 924 2886505 597 581 723 647 855 484 506 562 625 630 752494 550 571 672 638 802 516 647 590 776 655 911505 597 581 723 647 855 706 996 761 1146 484 506 562 625 630 752 691 888 747 1035494 550 571 672 638 802 699 941 754 1089 516 647 590 776 655 911 714 1055 768 1207627 1316 690 1481 747 1648 800 1821 604 1155 669 1312 728 1473 782 1639616 1233 680 1395 738 1559 791 1728 639 1402 701 1570 757 1741 809 1917697 1243 750 1423 801 1608 850 1799 628 997 685 1167 739 1343 791 1525 841 1712641 709 1322 761 1506 812 1695734 1492 784 1683 628 997 685 1167 739 1343 791 1525697 1243 750 1423 801 1608 747 1582 796 1777PRE-START-UP Internal WiringVI. Refrigerant Service Ports START-UP Unit PreparationXII. Operating Sequence Safety ReliefVIII. Cooling Condenser Coil Service CleaningEvaporator Coil Condensate DrainIII. Evaporator FAN Belt Inspection VI. Economizer AdjustmentII. Lubrication Manual OUTDOOR-AIR DamperIX. LOSS-OF-CHARGE Switch To Use Cooling Charging ChartsVIII. HIGH-PRESSURE Switch XI. Replacement PartsCooling Charging Chart 558F120 Cooling Charging Chart 558F091 Troubleshooting Unit Troubleshooting II. ECONOMI$ER IV TroubleshootingEconoMi$er IV Preparation DCV Demand Controlled Ventilation and Power ExhaustEconoMi$er IV Troubleshooting Completion Differential EnthalpyTypical Unit Wiring Schematic Cooling Service Analysis Terminal† EconoMi$er IV Input/Output LogicDemand Control Enthalpy Index Service Training Call for Free CatalogCopyright 2005 Bryant Heating & Cooling Systems Catalog no Page Preliminary Information START-UP ChecklistTemperatures III. START-UP Electrical
Related manuals
Manual 170 pages 34.1 Kb

558F specifications

The Bryant 558F is a highly efficient and versatile gas furnace designed to provide reliable heating for residential spaces. Known for its exceptional performance and advanced technology, the 558F caters to homeowners looking for comfort, efficiency, and sustainability in their heating solutions.

One of the primary features of the Bryant 558F is its two-stage heating capability. This system allows the furnace to operate at different levels of output, optimizing energy consumption based on the heating demands of the home. By operating at a lower stage most of the time, the 558F can maintain consistent indoor temperatures while using less energy, leading to reduced utility bills.

The furnace is also equipped with aVariable Speed ECM blower motor. This feature provides enhanced air distribution and comfort by allowing for more precise control over airflow. The variable speed operation ensures that the furnace can adjust to the heating needs of the space without the constant on-off cycling, promoting quieter operation and better efficiency.

In terms of efficiency ratings, the Bryant 558F boasts an impressive Annual Fuel Utilization Efficiency (AFUE) rating of up to 96%. This high rating indicates that the furnace converts a significant portion of its fuel into usable heat, making it an environmentally friendly choice. With lower greenhouse gas emissions, homeowners not only benefit from cost savings but also contribute to reducing their carbon footprint.

Additionally, the furnace incorporates advanced combustion technology, including a durable heat exchanger designed for longevity and efficiency. This component is vital for maximizing heat transfer while minimizing heat loss, contributing to the overall performance of the unit.

The Bryant 558F is compatible with the manufacturer's Infinity System control, providing homeowners with a user-friendly interface to manage their heating system effectively. This compatibility allows for the integration of smart home technology, enabling remote access and programmable settings for added convenience.

Installation and maintenance of the Bryant 558F are straightforward, thanks to its compact design and thoughtful layout. Homeowners can find peace of mind knowing that service and upkeep are manageable, prolonging the life of the furnace.

In summary, the Bryant 558F gas furnace combines efficiency, advanced technology, and reliability to provide exceptional indoor comfort. With its two-stage heating, variable speed blower motor, and high AFUE rating, the 558F stands out as an optimal heating solution for modern homes seeking both performance and sustainability.