Bryant 558F installation instructions CO2 Sensor Standard Settings

Page 30

CO2 Sensor Configuration

The CO2 sensor has preset standard voltage settings that can be selected anytime after the sensor is powered up. See Table 5.

Use setting 1 or 2 for Bryant equipment. See Table 5.

1.Press Clear and Mode buttons. Hold at least 5 sec- onds until the sensor enters the Edit mode.

2.Press Mode twice. The STDSET Menu will appear.

3.Use the Up/Down button to select the preset number. See Table 5.

4.Press Enter to lock in the selection.

5.Press Mode to exit and resume normal operation.

The custom settings of the CO2 sensor can be changed any- time after the sensor is energized. Follow the steps below to change the non-standard settings:

1.Press Clear and Mode buttons. Hold at least 5 sec- onds until the sensor enters the Edit mode.

2.Press Mode twice. The STDSET Menu will appear.

3.Use the Up/Down button to toggle to the NONSTD menu and press Enter.

4.Use the Up/Down button to toggle through each of the nine variables, starting with Altitude, until the desired setting is reached.

5.Press Mode to move through the variables.

6.Press Enter to lock in the selection, then press Mode to continue to the next variable.

Dehumidification of Fresh Air with DCV Control

Information from ASHRAE indicates that the largest humid- ity load on any zone is the fresh air introduced. For some applications, a device such as an energy recovery unit is added to reduce the moisture content of the fresh air being brought into the building when the enthalpy is high. In most cases, the normal heating and cooling processes are more than adequate to remove the humidity loads for most com- mercial applications.

If normal rooftop heating and cooling operation is not ade- quate for the outdoor humidity level, an energy recovery unit and/or a dehumidification option should be considered.

Table 5 — CO2 Sensor Standard Settings

 

 

 

VENTILATION

ANALOG

CO2

OPTIONAL

RELAY

SETTING

EQUIPMENT

OUTPUT

RATE

CONTROL RANGE

RELAY SETPOINT

HYSTERESIS

OUTPUT

 

 

 

(cfm/Person)

(ppm)

(ppm)

(ppm)

 

 

 

 

1

 

Proportional

Any

0-10V

0-2000

1000

50

 

4-20 mA

 

 

 

 

 

 

 

2

Interface w/Standard

Proportional

Any

2-10V

0-2000

1000

50

Building Control System

7-20 mA

 

 

 

 

 

 

3

 

Exponential

Any

0-10V

0-2000

1100

50

 

4-20 mA

 

 

 

 

 

 

 

4

 

Proportional

15

0-10V

0-1100

1100

50

 

4-20 mA

 

 

 

 

 

 

 

5

 

Proportional

20

0-10V

0- 900

900

50

 

4-20 mA

 

Economizer

 

 

 

 

 

6

Exponential

15

0-10V

0-1100

1100

50

 

 

4-20 mA

 

 

 

 

 

 

 

7

 

Exponential

20

0-10V

0- 900

900

50

 

4-20 mA

 

 

 

 

 

 

 

8

Health & Safety

Proportional

0-10V

0-9999

5000

500

4-20 mA

 

 

 

 

 

 

 

9

Parking/Air Intakes/

Proportional

0-10V

0-2000

700

50

Loading Docks

4-20 mA

 

 

 

 

 

 

LEGEND

ppm — Parts Per Million

30

Image 30
Contents Contents Safety ConsiderationsII. Field Fabricate Ductwork III. Install External Trap for Condensate Drain IV. RIG and Place UnitPositioning Roof Curb Details ‘‘A’’ ‘‘C’’558F Base Unit Dimensions 558F090,102,120,150 Base Unit Dimensions 558F091,103,121,151 Physical Data 558F090,102,120,150 Units 558F Unit SizePhysical Data 558F091,103,121,151 Units Ashrae 90.1-1999 Compliant UnitsField Power Supply Field Control WiringMake Electrical Connections Voltage Compressor OFM Electric Power Disconnect Nominal Type FLA Size 150 Voltage Compressor 103 151 Type FLA 17.0 17.1 31.4 136 34.0 34.1 52.7 51.0 51.2 60.8 150 44.9 234/234 017 10.4 21.7 25.0 006 49.1 277/277 017 10.4 21.7 25.0 006 61.0 364/364 017 10.4 21.7 25.0 012 Conduit Installation Convenience OutletDamper Panel with Manual Outdoor-Air Damper Installed EconoMi$er IV Component Locations Barometric Flow Capacity EconoMi$er IV Control Modes EconoMi$er IV Sensor UsageOutside Air Temperature Changeover Set Points Enthalpy Changeover Set Points Page CO2 Sensor Standard Settings VII. Adjust EVAPORATOR-FAN Speed Typical Belt-Drive Motor Mounting for Sizes 090,091,102,103Fan Rpm at Motor Pulley Settings Accessory/FIOP Static Pressure* in. wgEvaporator-Fan Motor Efficiency Evaporator Fan Motor Data General FAN Performance Notes511 492 External Static Pressure in. wgRpm Bhp Watts 519 518534 571 611 768 678 982 511 492 591 680 660 885519 518 597 709 666 916 550 629 624 832534 571 611 768 678 982 739 1210 795 1453 511 492 591 680 660 885 722 1106 779 1342519 518 597 709 666 916 727 1140 784 1378 550 629 624 832 690 1051 750 1285 805 1533663 504 468 584 653 654 855646 679646 1071 711 1313 770 1568 824 1835 504 468 584 653 654 855 716 1074 774 1307630 985 696 1220 756 1469 811 1731 663 1162 726 1411 784 1672 837 1944557 658 627 810 532 559 604 702 668 846545 607 615 755 678 903 570 712 638 869557 658 627 810 689 963 745 1117 797 1271 532 559 604 702 668 846 726 990 779 1136545 607 615 755 678 903 735 1052 788 1202 570 712 638 869 699 1026 755 1184 806 13431153 3999 1134 37011144 3847 1162 4154739 1385 792 1572 840 1758 726 1299 779 1481 828 1662683 753 1474 804 1666 852 1857780 1665 739 1385 792 1572753 1474 804 1666 794 1767483 461 571 665 465 402 555 596471 421 560 618 495 503 581 715483 461 571 665 644 881 465 402 555 596 629 802471 421 560 618 634 828 495 503 581 715 654 937483 461 571 665 644 881 708 1109 766 1348 465 402 555 596 629 802 694 1021 753 1252471 421 560 618 634 828 699 1050 757 1283 495 503 581 715 654 937 717 1171 775 1416675 1454 459 384 550 575 625 778662 1361 943 2241675 1454 745 1771 806 2093 862 2422 913 2758 459 384 550 575 625 778 690 994 748 1221662 1361 732 1670 794 1985 851 2307 903 2635 689 1553 757 1877 818 2207 873 2543 924 2886505 597 581 723 647 855 484 506 562 625 630 752494 550 571 672 638 802 516 647 590 776 655 911505 597 581 723 647 855 706 996 761 1146 484 506 562 625 630 752 691 888 747 1035494 550 571 672 638 802 699 941 754 1089 516 647 590 776 655 911 714 1055 768 1207627 1316 690 1481 747 1648 800 1821 604 1155 669 1312 728 1473 782 1639616 1233 680 1395 738 1559 791 1728 639 1402 701 1570 757 1741 809 1917697 1243 750 1423 801 1608 850 1799 628 997 685 1167 739 1343 791 1525 841 1712641 709 1322 761 1506 812 1695734 1492 784 1683 628 997 685 1167 739 1343 791 1525697 1243 750 1423 801 1608 747 1582 796 1777PRE-START-UP Internal WiringVI. Refrigerant Service Ports START-UP Unit PreparationSafety Relief VIII. CoolingXII. Operating Sequence Condenser Coil Service CleaningEvaporator Coil Condensate DrainIII. Evaporator FAN Belt Inspection VI. Economizer AdjustmentII. Lubrication Manual OUTDOOR-AIR DamperIX. LOSS-OF-CHARGE Switch To Use Cooling Charging ChartsVIII. HIGH-PRESSURE Switch XI. Replacement PartsCooling Charging Chart 558F120 Cooling Charging Chart 558F091 Troubleshooting Unit Troubleshooting II. ECONOMI$ER IV TroubleshootingEconoMi$er IV Preparation DCV Demand Controlled Ventilation and Power ExhaustEconoMi$er IV Troubleshooting Completion Differential EnthalpyTypical Unit Wiring Schematic Cooling Service Analysis EconoMi$er IV Input/Output Logic Demand Control EnthalpyTerminal† Index Service Training Call for Free CatalogCopyright 2005 Bryant Heating & Cooling Systems Catalog no Page Preliminary Information START-UP ChecklistTemperatures III. START-UP Electrical
Related manuals
Manual 170 pages 34.1 Kb

558F specifications

The Bryant 558F is a highly efficient and versatile gas furnace designed to provide reliable heating for residential spaces. Known for its exceptional performance and advanced technology, the 558F caters to homeowners looking for comfort, efficiency, and sustainability in their heating solutions.

One of the primary features of the Bryant 558F is its two-stage heating capability. This system allows the furnace to operate at different levels of output, optimizing energy consumption based on the heating demands of the home. By operating at a lower stage most of the time, the 558F can maintain consistent indoor temperatures while using less energy, leading to reduced utility bills.

The furnace is also equipped with aVariable Speed ECM blower motor. This feature provides enhanced air distribution and comfort by allowing for more precise control over airflow. The variable speed operation ensures that the furnace can adjust to the heating needs of the space without the constant on-off cycling, promoting quieter operation and better efficiency.

In terms of efficiency ratings, the Bryant 558F boasts an impressive Annual Fuel Utilization Efficiency (AFUE) rating of up to 96%. This high rating indicates that the furnace converts a significant portion of its fuel into usable heat, making it an environmentally friendly choice. With lower greenhouse gas emissions, homeowners not only benefit from cost savings but also contribute to reducing their carbon footprint.

Additionally, the furnace incorporates advanced combustion technology, including a durable heat exchanger designed for longevity and efficiency. This component is vital for maximizing heat transfer while minimizing heat loss, contributing to the overall performance of the unit.

The Bryant 558F is compatible with the manufacturer's Infinity System control, providing homeowners with a user-friendly interface to manage their heating system effectively. This compatibility allows for the integration of smart home technology, enabling remote access and programmable settings for added convenience.

Installation and maintenance of the Bryant 558F are straightforward, thanks to its compact design and thoughtful layout. Homeowners can find peace of mind knowing that service and upkeep are manageable, prolonging the life of the furnace.

In summary, the Bryant 558F gas furnace combines efficiency, advanced technology, and reliability to provide exceptional indoor comfort. With its two-stage heating, variable speed blower motor, and high AFUE rating, the 558F stands out as an optimal heating solution for modern homes seeking both performance and sustainability.