Bryant 558F installation instructions EconoMi$er IV Control Modes, EconoMi$er IV Sensor Usage

Page 26

SUPPLY AIR

TEMPERATURE

SENSOR

MOUNTING

LOCATION

SUPPLY AIR

TEMPERATURE

SENSOR

Fig. 27 — Supply Air Sensor Location

Table 3 — Supply Air Sensor

Temperature/Resistance Values

TEMPERATURE (F)

RESISTANCE (ohms)

–58

200,250

–40

100,680

–22

53,010

–4

29,091

14

16,590

32

9,795

50

5,970

68

3,747

77

3,000

86

2,416

104

1,597

122

1,080

140

746

158

525

176

376

185

321

194

274

212

203

230

153

248

116

257

102

266

89

284

70

302

55

The temperature sensor looks like an eyelet terminal with wires running to it. The sensor is located in the “crimp end” and is sealed from moisture.

Outdoor Air Lockout Sensor

The EconoMi$er IV is equipped with an ambient tempera- ture lockout switch located in the outdoor air stream which is used to lockout the compressors below a 42 F ambient tem- perature. See Fig. 17.

E. EconoMi$er IV Control Modes

Determine the EconoMi$er IV control mode before set up of the control. Some modes of operation may require different sensors. Refer to Table 4. The EconoMi$er IV is supplied from the factory with a supply air temperature sensor and an outdoor air temperature sensor. This allows for operation of the EconoMi$er IV with outdoor air dry bulb changeover control. Additional accessories can be added to allow for different

types of changeover control and operation of the EconoMi$er IV and unit.

Outdoor Dry Bulb Changeover

The standard controller is shipped from the factory config- ured for outdoor dry bulb changeover control. The outdoor air and supply air temperature sensors are included as standard. For this control mode, the outdoor temperature is compared to an adjustable set point selected on the control. If the outdoor-air temperature is above the set point, the EconoMi$er IV will adjust the outdoor-air dampers to minimum position. If the outdoor-air temperature is below the set point, the position of the outdoor-air dampers will be controlled to provide free cooling using outdoor air. When in this mode, the LED next to the free cooling set point potenti- ometer will be on. The changeover temperature set point is controlled by the free cooling set point potentiometer located on the control. See Fig. 28. The scale on the potentiometer is A, B, C, and D. See Fig. 29 for the corresponding temperature changeover values.

Table 4 — EconoMi$er IV Sensor Usage

 

ECONOMI$ER IV WITH OUTDOOR AIR

APPLICATION

 

DRY BULB SENSOR

 

 

Accessories Required

Outdoor Air

None. The outdoor air dry bulb sensor

Dry Bulb

 

is factory installed.

Differential

 

CRTEMPSN002A00*

Dry Bulb

 

 

 

 

 

 

 

Single Enthalpy

 

 

HH57AC078

Differential

 

 

HH57AC078

 

 

 

 

and

Enthalpy

 

 

 

 

 

CRENTDIF004A00*

 

 

CO2 for DCV

 

 

 

 

 

 

Control using a

 

 

33ZCSENCO2

Wall-Mounted

 

 

 

 

 

 

 

 

CO2 Sensor

 

 

 

 

 

 

CO2 for DCV

33ZCSENCO2†

 

 

 

 

Control using a

 

OR

 

CRCBDIOX005A00††

and

 

 

 

Duct-Mounted

 

 

 

33ZCASPCO2**

 

 

 

 

CO2 Sensor

 

 

 

 

 

 

 

 

 

 

*CRENTDIF004A00 and CRTEMPSN002A00 accessories are used on many different base units. As such, these kits may contain parts that will not be needed for installation.

†33ZCSENCO2 is an accessory CO2 sensor.

**33ZCASPCO2 is an accessory aspirator box required for duct-mounted applications.

††CRCBDIOX005A00 is an accessory that contains both 33ZCSENCO2 and 33ZCASPCO2 accessories.

Fig. 28 — EconoMi$er IV Controller Potentiometer

and LED Locations

26

Image 26
Contents II. Field Fabricate Ductwork ContentsSafety Considerations Positioning III. Install External Trap for Condensate DrainIV. RIG and Place Unit Roof Curb Details 558F ‘‘A’’‘‘C’’ Base Unit Dimensions 558F090,102,120,150 Base Unit Dimensions 558F091,103,121,151 Physical Data 558F090,102,120,150 Units 558F Unit SizePhysical Data 558F091,103,121,151 Units Ashrae 90.1-1999 Compliant UnitsMake Electrical Connections Field Power SupplyField Control Wiring Voltage Compressor OFM Electric Power Disconnect Nominal Type FLA Size 150 Voltage Compressor 103 151 Type FLA 17.0 17.1 31.4 136 34.0 34.1 52.7 51.0 51.2 60.8 150 44.9 234/234 017 10.4 21.7 25.0 006 49.1 277/277 017 10.4 21.7 25.0 006 61.0 364/364 017 10.4 21.7 25.0 012 Conduit Installation Convenience OutletDamper Panel with Manual Outdoor-Air Damper Installed EconoMi$er IV Component Locations Barometric Flow Capacity EconoMi$er IV Control Modes EconoMi$er IV Sensor UsageOutside Air Temperature Changeover Set Points Enthalpy Changeover Set Points Page CO2 Sensor Standard Settings VII. Adjust EVAPORATOR-FAN Speed Typical Belt-Drive Motor Mounting for Sizes 090,091,102,103Evaporator-Fan Motor Efficiency Fan Rpm at Motor Pulley SettingsAccessory/FIOP Static Pressure* in. wg Evaporator Fan Motor Data General FAN Performance Notes511 492 External Static Pressure in. wgRpm Bhp Watts 519 518534 571 611 768 678 982 511 492 591 680 660 885519 518 597 709 666 916 550 629 624 832534 571 611 768 678 982 739 1210 795 1453 511 492 591 680 660 885 722 1106 779 1342519 518 597 709 666 916 727 1140 784 1378 550 629 624 832 690 1051 750 1285 805 1533663 504 468 584 653 654 855646 679646 1071 711 1313 770 1568 824 1835 504 468 584 653 654 855 716 1074 774 1307630 985 696 1220 756 1469 811 1731 663 1162 726 1411 784 1672 837 1944557 658 627 810 532 559 604 702 668 846545 607 615 755 678 903 570 712 638 869557 658 627 810 689 963 745 1117 797 1271 532 559 604 702 668 846 726 990 779 1136545 607 615 755 678 903 735 1052 788 1202 570 712 638 869 699 1026 755 1184 806 13431153 3999 1134 37011144 3847 1162 4154739 1385 792 1572 840 1758 726 1299 779 1481 828 1662683 753 1474 804 1666 852 1857780 1665 739 1385 792 1572753 1474 804 1666 794 1767483 461 571 665 465 402 555 596471 421 560 618 495 503 581 715483 461 571 665 644 881 465 402 555 596 629 802471 421 560 618 634 828 495 503 581 715 654 937483 461 571 665 644 881 708 1109 766 1348 465 402 555 596 629 802 694 1021 753 1252471 421 560 618 634 828 699 1050 757 1283 495 503 581 715 654 937 717 1171 775 1416675 1454 459 384 550 575 625 778662 1361 943 2241675 1454 745 1771 806 2093 862 2422 913 2758 459 384 550 575 625 778 690 994 748 1221662 1361 732 1670 794 1985 851 2307 903 2635 689 1553 757 1877 818 2207 873 2543 924 2886505 597 581 723 647 855 484 506 562 625 630 752494 550 571 672 638 802 516 647 590 776 655 911505 597 581 723 647 855 706 996 761 1146 484 506 562 625 630 752 691 888 747 1035494 550 571 672 638 802 699 941 754 1089 516 647 590 776 655 911 714 1055 768 1207627 1316 690 1481 747 1648 800 1821 604 1155 669 1312 728 1473 782 1639616 1233 680 1395 738 1559 791 1728 639 1402 701 1570 757 1741 809 1917697 1243 750 1423 801 1608 850 1799 628 997 685 1167 739 1343 791 1525 841 1712641 709 1322 761 1506 812 1695734 1492 784 1683 628 997 685 1167 739 1343 791 1525697 1243 750 1423 801 1608 747 1582 796 1777PRE-START-UP Internal WiringVI. Refrigerant Service Ports START-UP Unit PreparationXII. Operating Sequence Safety ReliefVIII. Cooling Condenser Coil Service CleaningEvaporator Coil Condensate DrainIII. Evaporator FAN Belt Inspection VI. Economizer AdjustmentII. Lubrication Manual OUTDOOR-AIR DamperIX. LOSS-OF-CHARGE Switch To Use Cooling Charging ChartsVIII. HIGH-PRESSURE Switch XI. Replacement PartsCooling Charging Chart 558F120 Cooling Charging Chart 558F091 Troubleshooting Unit Troubleshooting II. ECONOMI$ER IV TroubleshootingEconoMi$er IV Preparation DCV Demand Controlled Ventilation and Power ExhaustEconoMi$er IV Troubleshooting Completion Differential EnthalpyTypical Unit Wiring Schematic Cooling Service Analysis Terminal† EconoMi$er IV Input/Output LogicDemand Control Enthalpy Index Service Training Call for Free CatalogCopyright 2005 Bryant Heating & Cooling Systems Catalog no Page Preliminary Information START-UP ChecklistTemperatures III. START-UP Electrical
Related manuals
Manual 170 pages 34.1 Kb

558F specifications

The Bryant 558F is a highly efficient and versatile gas furnace designed to provide reliable heating for residential spaces. Known for its exceptional performance and advanced technology, the 558F caters to homeowners looking for comfort, efficiency, and sustainability in their heating solutions.

One of the primary features of the Bryant 558F is its two-stage heating capability. This system allows the furnace to operate at different levels of output, optimizing energy consumption based on the heating demands of the home. By operating at a lower stage most of the time, the 558F can maintain consistent indoor temperatures while using less energy, leading to reduced utility bills.

The furnace is also equipped with aVariable Speed ECM blower motor. This feature provides enhanced air distribution and comfort by allowing for more precise control over airflow. The variable speed operation ensures that the furnace can adjust to the heating needs of the space without the constant on-off cycling, promoting quieter operation and better efficiency.

In terms of efficiency ratings, the Bryant 558F boasts an impressive Annual Fuel Utilization Efficiency (AFUE) rating of up to 96%. This high rating indicates that the furnace converts a significant portion of its fuel into usable heat, making it an environmentally friendly choice. With lower greenhouse gas emissions, homeowners not only benefit from cost savings but also contribute to reducing their carbon footprint.

Additionally, the furnace incorporates advanced combustion technology, including a durable heat exchanger designed for longevity and efficiency. This component is vital for maximizing heat transfer while minimizing heat loss, contributing to the overall performance of the unit.

The Bryant 558F is compatible with the manufacturer's Infinity System control, providing homeowners with a user-friendly interface to manage their heating system effectively. This compatibility allows for the integration of smart home technology, enabling remote access and programmable settings for added convenience.

Installation and maintenance of the Bryant 558F are straightforward, thanks to its compact design and thoughtful layout. Homeowners can find peace of mind knowing that service and upkeep are manageable, prolonging the life of the furnace.

In summary, the Bryant 558F gas furnace combines efficiency, advanced technology, and reliability to provide exceptional indoor comfort. With its two-stage heating, variable speed blower motor, and high AFUE rating, the 558F stands out as an optimal heating solution for modern homes seeking both performance and sustainability.