Bryant 581A operation manual Troubleshooting, Cooling Service Analysis, Problem Cause Remedy

Page 35

TROUBLESHOOTING

Refer to Tables 18 and 19 for troubleshooting details.

Table 18 — Cooling Service Analysis

PROBLEM

CAUSE

REMEDY

Compressor and condenser fan will

Power failure.

Call power company.

not start.

Fuse blown or circuit breaker tripped.

Replace fuse or reset circuit breaker.

 

Defective thermostat, contactor, transformer,

Replace component.

 

or control relay.

 

 

Insufficient line voltage.

Determine cause and correct.

 

Incorrect or faulty wiring.

Check wiring diagram and rewire correctly.

 

Thermostat setting too high.

Lower thermostat setting below room

 

 

temperature.

Compressor will not start but

Faulty wiring or loose connections in

Check wiring and repair or replace.

condenser fan runs.

compressor circuit.

 

 

Compressor motor burned out, seized, or

Determine cause. Replace compressor.

 

internal overload open.

 

 

Defective overload.

Determine cause and replace.

 

Compressor locked out.

Determine cause for safety trip and reset

 

 

lockout.

 

One leg of 3-phase power dead.

Replace fuse or reset circuit breaker.

 

 

Determine cause.

Compressor cycles (other than

Refrigerant overcharge or undercharge.

Recover refrigerant, evacuate system, and recharge to

normally satisfying thermostat).

 

nameplate.

 

Defective compressor.

Replace and determine cause.

 

Insufficient line voltage.

Determine cause and correct.

 

Blocked condenser.

Determine cause and correct.

 

Defective overload.

Determine cause and replace.

 

Defective thermostat.

Replace thermostat.

 

Faulty condenser-fan motor.

Replace.

 

Restriction in refrigerant system.

Locate restriction and remove.

Compressor operates continuously.

Dirty air filter.

Replace filter.

 

Unit undersized for load.

Decrease load or increase unit size.

 

Thermostat set too low.

Reset thermostat.

 

Low refrigerant charge.

Locate leak, repair, and recharge.

 

Air in system.

Recover refrigerant, evacuate system, and recharge.

 

Condenser coil dirty or restricted.

Clean coil or remove restriction.

Excessive head pressure.

Dirty air filter.

Replace filter.

 

Dirty condenser coil.

Clean coil.

 

Refrigerant overcharged.

Recover excess refrigerant.

 

Faulty TXV.

1. Check TXV bulb mounting and secure tightly to

 

 

suction line.

 

 

2. Replace TXV if stuck open or closed.

 

Air in system.

Recover refrigerant, evacuate system, and recharge.

 

Condenser air restricted or air short-cycling.

Determine cause and correct.

Head pressure too low.

Low refrigerant charge.

Check for leaks, repair, and recharge.

 

Restriction in liquid tube.

Remove restriction.

Excessive suction pressure.

High heat load.

Check for source and eliminate.

 

Faulty TXV.

1. Check TXV bulb mounting and secure tightly to

 

 

suction line.

 

 

2. Replace TXV if stuck open or closed.

 

Refrigerant overcharged.

Recover excess refrigerant.

Suction pressure too low.

Dirty air filter.

Replace filter.

 

Low refrigerant charge.

Check for leaks, repair, and recharge.

 

Metering device or low side restricted.

Remove source of restriction.

 

Faulty TXV.

1. Check TXV bulb mounting and secure tightly to

 

 

suction line.

 

 

2. Replace TXV if stuck open or closed.

 

Insufficient evaporator airflow.

Increase air quantity. Check filter and replace if necessary.

 

Temperature too low in conditioned area.

Reset thermostat.

 

Field-installed filter drier restricted.

Replace.

Compressor no. 2 will not run.

Unit in economizer mode.

Proper operation; no remedy necessary.

LEGEND

 

 

TXV — Thermostatic Expansion Valve

 

 

—35—

Image 35
Contents Installation Provide Unit Support ContentsSafety Considerations Roof Curb Details Roof Mount Alternate Unit SupportII. RIG and Place Unit PositioningBase Unit Dimensions 581A155 Base Unit Dimensions 581A240 Unit 581A Physical Data581A180, 240 Unit Shown Install Flue Hood and Wind BaffleIII. Field Fabricate Ductwork IV. Make Unit Duct ConnectionsVIII. Make Electrical Connections VII. Install GAS PipingField Power Supply VI. Trap Condensate DrainOptional Economizer Field Control WiringMake OUTDOOR-AIR Inlet Adjustments Manual Outdoor-Air DamperFLA LRA MCA Mocp Electrical Data25% Outdoor-Air Section Details Install OUTDOOR-AIR HoodSeal Strip Location Enthalpy Control InstallationMotormaster I Control Installation 581A155 and 180 Only XI. Install ALL AccessoriesUnit Preparation II. Service ValvesIV. Refrigerant Service Ports START-UPVIII. Evaporator FAN VI. Internal WiringXII. Accessory Economizer Adjustment VII. Crankcase HeatersBhp Brake Horsepower Fan Performance 581A180270 Low Heat Units Fan Performance 581A240270 Low Heat Units 753 915 844 1077 949 1287 1047 753 942 844 1101 949 Fan Performance 581A180360 High Heat Units Fan Performance 581A240360 High Heat Units Air Quantity Limits Evaporator Fan Motor SpecificationsAccessory/FIOP Economizer Static Pressure in. wg Fan RPM at Motor Pulley SettingXIV. Base Unit Operation XIII. GAS HeatService Cleaning II. Lubrication IV. Evaporator FAN Service and Replacement581A240 Units Fig Belt Tension AdjustmentVI. CONDENSER-FAN Adjustment 581A155 and 180 Units FigIX. Refrigerant Charge VII. Economizer AdjustmentVIII. Power Failure XIII. Protective Devices GAS Valve AdjustmentXI. Main Burners XII. Filter DrierXV. Control Circuit XVI. Replacement PartsXVII. Diagnostic Leds XIV. Relief DevicesSpark Gap Adjustment Typical Wiring Schematic and Typical Component Arrangement Typical Wiring Schematic 581A180, 208/230 V Unit Shown Typical Component Arrangement 581A180 Shown Problem Cause Remedy TroubleshootingCooling Service Analysis Burners will not ignite Heating Service AnalysisIGC Control Heating and Cooling Call for Free Catalog Packaged Service TrainingPage General TemperaturesElectrical Pressures
Related manuals
Manual 56 pages 3.06 Kb

581A specifications

The Bryant 581A is a pivotal model in the realm of heating, ventilation, and air conditioning (HVAC) systems, known for its robust performance and energy efficiency. As part of the Bryant product lineup, the 581A offers a blend of innovative technologies combined with reliable engineering, making it a suitable choice for both residential and light commercial applications.

One of the standout features of the Bryant 581A is its outstanding energy efficiency. With a Seasonal Energy Efficiency Ratio (SEER) rating of up to 16, this model meets Energy Star qualifications, ensuring that homeowners can enjoy lower utility bills while helping to reduce their environmental footprint. The efficiency is further enhanced by the unit’s environmentally friendly refrigerant, which not only improves performance but also aligns with modern sustainability standards.

Another key characteristic of the Bryant 581A is its durable construction. Designed to withstand various weather conditions, the unit features a robust cabinet that protects internal components. This durability not only prolongs the lifespan of the system but also minimizes the need for frequent maintenance or repairs. The coil design is optimized for heat transfer efficiency, enhancing the unit's overall performance in both cooling and heating modes.

In terms of technology, the Bryant 581A incorporates advanced control systems that enable precise temperature regulation. The multi-stage cooling capabilities ensure that the system can adapt to varying temperature demands, providing comfort in all seasons. Additionally, the model is compatible with smart thermostats, allowing homeowners to control their HVAC system remotely via smartphone or other connected devices.

Noise reduction is another aspect where the Bryant 581A excels. Equipped with a variable-speed compressor and sound-dampening features, this model operates quietly, minimizing disruption in residential or office environments. This focus on acoustic comfort makes it an ideal choice for those who value a peaceful living or working space.

Overall, the Bryant 581A represents an excellent balance of efficiency, durability, and modern technology. With features aimed at enhancing user comfort and reducing operational costs, it stands out as a reliable solution in the competitive HVAC market. Whether for new installations or replacements, the Bryant 581A is a testament to the brand’s commitment to quality and innovation in home climate control.