XIII. GAS HEAT

Verify gas pressures before turning on heat as follows:

1.Turn off manual gas stop.

2.Connect pressure gage to supply gas pressure tap (see Fig. 13).

3.Connect pressure gage to manifold pressure tap on gas valve.

4.Turn on manual gas stop and set thermostat to

HEAT position. After the unit has run for several minutes, verify that incoming pressure is 5.5 in. wg or greater, and that the manifold pressure is

3.3 in. wg. If manifold pressure must be adjusted, refer to Gas Valve Adjustment section on page 29.

5.After unit has been in operation for 5 minutes, check temperature rise across the heat exchangers. See unit informative plate for correct rise limits of the heat supplied. Air quantities may need to be adjusted to bring the actual rise to within the allowable limits.

XIV. BASE UNIT OPERATION

A. Cooling, Units Without Economizer

When thermostat calls for cooling, terminals G and Y1 are energized. The indoor (evaporator) fan contactor (IFC) and- compressor contactor no. 1 (C1) are energized and evapora- tor-fan motor (IFM), compressor no. 1 and condenser fan start. The condenser-fan motors run continuously while unit is cooling. If the thermostat calls for a second stage of cooling by energizing Y2, compressor contactor no. 2 (C2) is ener- gized and compressor no. 2 starts.

B. Heating, Units Without Economizer

NOTE: The 581A155-240 units have 2 stages of heat.

When the thermostat calls for heating, power is sent to W on the IGC (integrated gas unit controller) board. An LED (light-emitting diode) on the IGC board will be on during normal operation. A check is made to ensure that the rollout switch and limit switch are closed and the induced-draft motor is running. The induced-draft motor is then energized, and when speed is proven with the hall effect sensor on the motor, the ignition activation period begins. The burners will ignite within 5 seconds.

If the burners do not light, there is a 22-second delay before another 5-second attempt. If the burners still do not light, this sequence is repeated for 15 minutes. After the 15 min- utes have elapsed, if the burners still have not lighted, heat- ing is locked out. To reset the control, break 24-v power to the thermostat.

When ignition occurs the IGC board will continue to monitor the condition of the rollout and limit switches, the hall effect sensor, as well as the flame sensor. If the unit is controlled through a room thermostat set for fan auto.,45 seconds after ignition occurs, the indoor-fan motor will be energized (and the outdoor-air dampers will open to their minimum posi- tion). If for some reason the overtemperature limit opens prior to the start of the indoor fan blower, on the next attempt, the 45-second delay will be shortened to 5 seconds less than the time from initiation of heat to when the limit tripped. Gas will not be interrupted to the burners and heat- ing will continue. Once modified, the fan on delay will not change back to 45 seconds unless power is reset to the control.

When additional heat is required, W2 closes and initiates power to the second stage of the main gas valve. When the thermostat is satisfied, W1 and W2 open and the gas valve closes, interrupting the flow of gas to the main burners. If the call for W1 lasted less than 1 minute, the heating cycle will not terminate until 1 minute after W1 became active. If the unit is controlled through a room thermostat set for fan auto., the indoor-fan motor will continue to operate for an additional 45 seconds then stop (and the outdoor-air damp- ers will close). If the overtemperature limit opens after the indoor motor is stopped within 10 minutes of W1 becoming inactive, on the next cycle the time will be extended by 15 seconds. The maximum delay is 3 minutes. Once modi- fied, the fan off delay will not change back to 45 seconds unless power is reset to the control.

A LED indicator is provided on the IGC to monitor opera- tion. The IGC is located by removing the side panel and viewing the IGC through the view port located in the control box access panel. See Fig. 28. During normal operation, the LED is continuously on. See Table 15 for error codes.

Table 15 — IGC LED Indications

 

 

ERROR CODE

 

LED INDICATION

 

 

Normal Operation

 

On

 

 

HardwareFailure

 

Off

 

 

Fan On/Off Delay

 

1 Flash

 

 

Modified

 

 

 

 

 

 

 

Limit Switch Fault

 

2 Flashes

 

 

Flame Sense Fault

 

3 Flashes

 

 

Five Consecutive Limit

 

4 Flashes

 

 

Switch Faults

 

 

 

 

 

 

 

Ignition Lockout Fault

 

5 Flashes

 

 

Inducer Switch Fault

 

6 Flashes

 

 

Rollout Switch Fault

 

7 Flashes

 

 

Internal Control Fault

 

8 Flashes

 

 

LEGEND

 

IGC

Integrated Gas Unit Controller

 

LED

Light-Emitting Diode

 

NOTES:

1.There is a 3-second pause between error code displays.

2.If more than one error code exists, all applicable error codes will be displayed in numerical sequence.

3.Error codes on the IGC will be lost if power to the unit is interrupted.

C. Cooling, Units With Economizer

Upon a call for cooling, when outdoor ambient is above the changeover control setting, the economizer damper moves to VENT position. The compressors and evaporator and con- denser fans energize and operate as per Cooling, Units With- out Economizer section on this page.

Upon a first call for cooling, when outdoor ambient is below the changeover control setting, the evaporator fan starts and the economizer is fully open. The compressors remain off.

—24—

Image 24
Contents Contents Safety ConsiderationsInstallation Provide Unit Support Roof Curb Details Alternate Unit Support II. RIG and Place UnitPositioning Roof MountBase Unit Dimensions 581A155 Base Unit Dimensions 581A240 Physical Data Unit 581AInstall Flue Hood and Wind Baffle III. Field Fabricate DuctworkIV. Make Unit Duct Connections 581A180, 240 Unit ShownVII. Install GAS Piping Field Power SupplyVI. Trap Condensate Drain VIII. Make Electrical ConnectionsField Control Wiring Make OUTDOOR-AIR Inlet AdjustmentsManual Outdoor-Air Damper Optional EconomizerElectrical Data FLA LRA MCA MocpInstall OUTDOOR-AIR Hood 25% Outdoor-Air Section DetailsEnthalpy Control Installation Seal Strip LocationXI. Install ALL Accessories Motormaster I Control Installation 581A155 and 180 OnlyII. Service Valves IV. Refrigerant Service PortsSTART-UP Unit PreparationVI. Internal Wiring XII. Accessory Economizer AdjustmentVII. Crankcase Heaters VIII. Evaporator FANBhp Brake Horsepower Fan Performance 581A180270 Low Heat Units Fan Performance 581A240270 Low Heat Units 753 915 844 1077 949 1287 1047 753 942 844 1101 949 Fan Performance 581A180360 High Heat Units Fan Performance 581A240360 High Heat Units Evaporator Fan Motor Specifications Accessory/FIOP Economizer Static Pressure in. wgFan RPM at Motor Pulley Setting Air Quantity LimitsXIII. GAS Heat XIV. Base Unit OperationService Cleaning IV. Evaporator FAN Service and Replacement II. LubricationBelt Tension Adjustment VI. CONDENSER-FAN Adjustment581A155 and 180 Units Fig 581A240 Units FigVII. Economizer Adjustment VIII. Power FailureIX. Refrigerant Charge GAS Valve Adjustment XI. Main BurnersXII. Filter Drier XIII. Protective DevicesXVI. Replacement Parts XVII. Diagnostic LedsXIV. Relief Devices XV. Control CircuitSpark Gap Adjustment Typical Wiring Schematic and Typical Component Arrangement Typical Wiring Schematic 581A180, 208/230 V Unit Shown Typical Component Arrangement 581A180 Shown Troubleshooting Cooling Service AnalysisProblem Cause Remedy Heating Service Analysis Burners will not igniteIGC Control Heating and Cooling Packaged Service Training Call for Free CatalogPage Temperatures ElectricalPressures General
Related manuals
Manual 56 pages 3.06 Kb

581A specifications

The Bryant 581A is a pivotal model in the realm of heating, ventilation, and air conditioning (HVAC) systems, known for its robust performance and energy efficiency. As part of the Bryant product lineup, the 581A offers a blend of innovative technologies combined with reliable engineering, making it a suitable choice for both residential and light commercial applications.

One of the standout features of the Bryant 581A is its outstanding energy efficiency. With a Seasonal Energy Efficiency Ratio (SEER) rating of up to 16, this model meets Energy Star qualifications, ensuring that homeowners can enjoy lower utility bills while helping to reduce their environmental footprint. The efficiency is further enhanced by the unit’s environmentally friendly refrigerant, which not only improves performance but also aligns with modern sustainability standards.

Another key characteristic of the Bryant 581A is its durable construction. Designed to withstand various weather conditions, the unit features a robust cabinet that protects internal components. This durability not only prolongs the lifespan of the system but also minimizes the need for frequent maintenance or repairs. The coil design is optimized for heat transfer efficiency, enhancing the unit's overall performance in both cooling and heating modes.

In terms of technology, the Bryant 581A incorporates advanced control systems that enable precise temperature regulation. The multi-stage cooling capabilities ensure that the system can adapt to varying temperature demands, providing comfort in all seasons. Additionally, the model is compatible with smart thermostats, allowing homeowners to control their HVAC system remotely via smartphone or other connected devices.

Noise reduction is another aspect where the Bryant 581A excels. Equipped with a variable-speed compressor and sound-dampening features, this model operates quietly, minimizing disruption in residential or office environments. This focus on acoustic comfort makes it an ideal choice for those who value a peaceful living or working space.

Overall, the Bryant 581A represents an excellent balance of efficiency, durability, and modern technology. With features aimed at enhancing user comfort and reducing operational costs, it stands out as a reliable solution in the competitive HVAC market. Whether for new installations or replacements, the Bryant 581A is a testament to the brand’s commitment to quality and innovation in home climate control.