Bryant XI. Install ALL Accessories, Motormaster I Control Installation 581A155 and 180 Only

Page 13

 

CONTROL

CONTROL

POINT

CURVE

(Approx Deg)

 

AT 50% RH

A

73

B

68

C

63

D

58

RH — Relative Humidity

Fig. 24 — Psychrometric Chart for Solid-State

Enthalpy Control

B. Differential Enthalpy Control

NOTE: The accessory outdoor-air enthalpy sensor must be installed BEFORE the economizer hoods are installed on the unit or hoods will have to be removed.

1.Remove and discard the factory-installed jumper assembly containing the 800-ohm resistor on the

economizer control module (between terminals SR and +). See Fig. 18.

2.Disconnect black wire from economizer control mod-

ule terminal SO and blue wire from the OAT (outdoor- air thermostat).

3.Remove OAT and black wire assembly containing the 620-ohm resistor from the outside of the economizer (see Fig. 17).

4.Mount the outdoor-air enthalpy sensor (first sensor) to the economizer on the outside of the unit (in the same location from which the OAT was removed) using the 2 screws provided. See Fig. 17.

5.Reconnect the blue wire removed in Step 2 to the enthalpy sensor terminal +.

6.Cut the violet wire provided to desired length and terminate with quick-connect terminal provided. Route the violet wire from the enthalpy sensor termi- nal S, through the snap bushing, and to the econo- mizer control module terminal SO.

7.Mount the second enthalpy sensor in the return-air duct (return-air sensor).

8.Route the blue wire (provided) from terminal + on the return-air enthalpy sensor to the economizer control module terminal +.

9.Route the violet wire (provided) from terminal S on the return-air enthalpy sensor to the economizer con- trol module terminal SR.

10.Turn changeover set point dial clockwise past the “D” setting, or the control will not operate on a differen- tial. See Fig. 18.

11. Reinstall economizer hood if removed.

IMPORTANT: Be sure all seal strips and RTV sealant are intact. A watertight seal to inside of unit must be maintained.

XI. STEP 11 — INSTALL ALL ACCESSORIES

After all the factory-installed options have been adjusted, install all field-installed accessories. Refer to the accessory installation instructions included with each accessory.

A.Motormaster® I Control Installation (581A155 and 180 Only)

Install Field-Fabricated Wind Baffles

Wind baffles must be field-fabricated for all units to ensure proper cooling cycle operation at low ambient temperatures. See Fig. 25 for baffle details. Use 20-gage, galvanized sheet metal, or similar corrosion-resistant metal for baffles. Use field-supplied screws to attach baffles to unit. Screws should be 1/4-in. diameter and 5/8-in. long. Drill required screw holes for mounting baffles.

CAUTION: To avoid damage to the refrigerant coils and electrical components, use recommended screw sizes only. Use care when drilling holes.

Install Motormaster I Controls

Only one Motormaster I control is required per unit. The Motormaster I control must be used in conjunction with the Accessory 0° F Low Ambient Kit (purchased separately). The Motormaster I device controls outdoor fan no. 1 while out- door fans no. 2 and 3 are sequenced off by the Accessory 0° F Low Ambient Kit.

Accessory 0° F Low Ambient Kit — Install the Accessory 0° F Low Ambient Kit per instruction supplied with accessory.

NOTE: Dimensions in ( ) are in mm.

Fig. 25 — Wind Baffle Details

—13—

Image 13
Contents Safety Considerations ContentsInstallation Provide Unit Support Roof Curb Details II. RIG and Place Unit Alternate Unit SupportPositioning Roof MountBase Unit Dimensions 581A155 Base Unit Dimensions 581A240 Unit 581A Physical DataIII. Field Fabricate Ductwork Install Flue Hood and Wind BaffleIV. Make Unit Duct Connections 581A180, 240 Unit ShownField Power Supply VII. Install GAS PipingVI. Trap Condensate Drain VIII. Make Electrical ConnectionsMake OUTDOOR-AIR Inlet Adjustments Field Control WiringManual Outdoor-Air Damper Optional EconomizerFLA LRA MCA Mocp Electrical Data25% Outdoor-Air Section Details Install OUTDOOR-AIR HoodSeal Strip Location Enthalpy Control InstallationMotormaster I Control Installation 581A155 and 180 Only XI. Install ALL AccessoriesIV. Refrigerant Service Ports II. Service ValvesSTART-UP Unit PreparationXII. Accessory Economizer Adjustment VI. Internal WiringVII. Crankcase Heaters VIII. Evaporator FANBhp Brake Horsepower Fan Performance 581A180270 Low Heat Units Fan Performance 581A240270 Low Heat Units 753 915 844 1077 949 1287 1047 753 942 844 1101 949 Fan Performance 581A180360 High Heat Units Fan Performance 581A240360 High Heat Units Accessory/FIOP Economizer Static Pressure in. wg Evaporator Fan Motor SpecificationsFan RPM at Motor Pulley Setting Air Quantity LimitsXIV. Base Unit Operation XIII. GAS HeatService Cleaning II. Lubrication IV. Evaporator FAN Service and ReplacementVI. CONDENSER-FAN Adjustment Belt Tension Adjustment581A155 and 180 Units Fig 581A240 Units FigVIII. Power Failure VII. Economizer AdjustmentIX. Refrigerant Charge XI. Main Burners GAS Valve AdjustmentXII. Filter Drier XIII. Protective DevicesXVII. Diagnostic Leds XVI. Replacement PartsXIV. Relief Devices XV. Control CircuitSpark Gap Adjustment Typical Wiring Schematic and Typical Component Arrangement Typical Wiring Schematic 581A180, 208/230 V Unit Shown Typical Component Arrangement 581A180 Shown Cooling Service Analysis TroubleshootingProblem Cause Remedy Burners will not ignite Heating Service AnalysisIGC Control Heating and Cooling Call for Free Catalog Packaged Service TrainingPage Electrical TemperaturesPressures General
Related manuals
Manual 56 pages 3.06 Kb

581A specifications

The Bryant 581A is a pivotal model in the realm of heating, ventilation, and air conditioning (HVAC) systems, known for its robust performance and energy efficiency. As part of the Bryant product lineup, the 581A offers a blend of innovative technologies combined with reliable engineering, making it a suitable choice for both residential and light commercial applications.

One of the standout features of the Bryant 581A is its outstanding energy efficiency. With a Seasonal Energy Efficiency Ratio (SEER) rating of up to 16, this model meets Energy Star qualifications, ensuring that homeowners can enjoy lower utility bills while helping to reduce their environmental footprint. The efficiency is further enhanced by the unit’s environmentally friendly refrigerant, which not only improves performance but also aligns with modern sustainability standards.

Another key characteristic of the Bryant 581A is its durable construction. Designed to withstand various weather conditions, the unit features a robust cabinet that protects internal components. This durability not only prolongs the lifespan of the system but also minimizes the need for frequent maintenance or repairs. The coil design is optimized for heat transfer efficiency, enhancing the unit's overall performance in both cooling and heating modes.

In terms of technology, the Bryant 581A incorporates advanced control systems that enable precise temperature regulation. The multi-stage cooling capabilities ensure that the system can adapt to varying temperature demands, providing comfort in all seasons. Additionally, the model is compatible with smart thermostats, allowing homeowners to control their HVAC system remotely via smartphone or other connected devices.

Noise reduction is another aspect where the Bryant 581A excels. Equipped with a variable-speed compressor and sound-dampening features, this model operates quietly, minimizing disruption in residential or office environments. This focus on acoustic comfort makes it an ideal choice for those who value a peaceful living or working space.

Overall, the Bryant 581A represents an excellent balance of efficiency, durability, and modern technology. With features aimed at enhancing user comfort and reducing operational costs, it stands out as a reliable solution in the competitive HVAC market. Whether for new installations or replacements, the Bryant 581A is a testament to the brand’s commitment to quality and innovation in home climate control.