Bryant Guide Specifications, General, Products, Air-Cooled, Split-SystemAir Conditioner 594D

Page 24
GUIDE SPECIFICATIONS

GUIDE SPECIFICATIONS

GENERAL

System Description

Outdoor-mounted, air-cooled, split-system air conditioner unit suitable for ground or rooftop installation. Unit consists of a her- metic compressor, an air-cooled coil, propeller-type condenser fan, and a control box. Unit will discharge supply air upward as shown on contract drawings. Unit will be used in a refrigeration circuit to match up to a packaged fan coil or coil unit.

Quality Assurance

Unit will be rated in accordance with the latest edition of ARI Standard 210.

Unit will be certified for capacity, efficiency, and listed in the latest ARI directory.

Unit construction will comply with latest edition of ANSI/ ASHRAE and with NEC.

Unit will be constructed in accordance with UL standards and will carry the UL label of approval. Unit will have c-UL approval.

Unit cabinet will be capable of withstanding Federal Test Method Standard No. 141 (Method 6061) 500-hr salt spray test.

Air-cooled condenser coils will be leak tested at 150 psig and pressure tested at 300 psig.

Unit constructed in ISO 9001 approved facility.

Delivery, Storage, and Handling

Unit will be shipped as single package only and is stored and handled per unit manufacturer’s recommendations.

Warranty (for inclusion by specifying engineer)

U.S. and Canada only.

PRODUCTS

Equipment

Factory assembled, single piece, air-cooled air conditioner unit. Contained within the unit enclosure will be all factory wiring, piping, controls, compressor, refrigerant charge (R22), and special features required prior to field start-up.

Unit Cabinet

Unit cabinet will be constructed of galvanized steel, bonderized, and coated with a powder coat paint.

Fans

Condenser fan will be direct-drive propeller type, discharging air upward.

Air-Cooled, Split-System Air Conditioner 594D

1-1/2 to 5 Tons Nominal

Condenser fan motors will be totally enclosed, 1-phase type with class B insulation and permanently lubricated bearings.

Shafts will be corrosion resistant.

Fan blades will be statically and dynamically balanced.

Condenser fan openings will be equipped with steel wire safety guards.

Compressor

Compressor will be hermetically sealed.

Compressor will be mounted on rubber vibration isolators.

Condenser Coil

Condenser coil will be air cooled.

Coil will be constructed of aluminum fins mechanically bonded to copper tubes which are then cleaned, dehydrated, and sealed.

Refrigeration Components

Refrigeration circuit components will include liquid-line shutoff valve with sweat connections, suction line shutoff valves with sweat connections, system charge of R22 (R-410A) refrigerant, and compressor oil.

Operating Characteristics

The capacity of the unit will meet or exceed _____ Btuh at a

suction temperature of _____ °F. The power consumption at full

load will not exceed _____ kw.

Combination of the unit and the evaporator or fan coil unit will have a total net cooling capacity of _____ Btuh or greater at

conditions of _____ CFM entering air temperature at the

evaporator at _____ °F wet bulb and _____ °F dry bulb, and air

entering the unit at _____ °F.

The system will have an SEER of _____ Btuh/watt or greater at

DOE conditions.

Electrical Requirements

Nominal unit electrical characteristics will be _____ v, single

phase, 60 hertz. The unit will be capable of satisfactory opera- tion within voltage limits of _____ v to _____ v.

Unit electrical power will be single point connection. Control circuit will be 24v.

Special Features

Refer to section of this literature identifying accessories and descriptions for specific features and available enhancements.

SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE

UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS

Cancels: PDS 594D.18.6

© 1999 Bryant Heating & Cooling Systems, 7310 W. Morris St. Indpls, IN 46231

—24—

PRINTED IN U.S.A.

Catalog No. 5259-405 11-99

Image 24
Contents AVAILABLE OPTIONS Model 594D 60 HzELECTRIC AIR CONDITIONERDIMENSIONS IN SOUND POWER dBA RECOMMENDED TUBE DIAMETERSCHECK-FLO-RATER SPECIFICATIONS UNIT SIZE - SERIES018-E 024-ESPECIFICATIONS Continued UNIT SIZE - SERIES042-E 048-E/FACCESSORY USAGE GUIDELINE 12. Low-PressureSwitch 11. Low-AmbientController13. MotorMaster Control 14. Outdoor Air Temperature SensorCOMBINATION RATINGS COMBINATION RATINGS Continued COMBINATION RATINGS Continued COMBINATION RATINGS Continued DETAILED COOLING CAPACITIES DETAILED COOLING CAPACITIES* Continued DETAILED COOLING CAPACITIES* Continued DETAILED COOLING CAPACITIES* Continued DETAILED COOLING CAPACITIES* Continued DETAILED COOLING CAPACITIES* Continued DETAILED COOLING CAPACITIES* Continued CONDENSER ONLY RATINGS 594D018-E594D024-E 594D030-ECONDENSER ONLY RATINGS* Continued 594D042-E594D048-E,F 594D060-ESYSTEM DESIGN SUMMARY MATCHED SYSTEM Page GUIDE SPECIFICATIONS Warranty for inclusion by specifying engineerOperating Characteristics Special Features