ACCESSORY DESCRIPTION AND USAGE (Listed Alphabetically) Continued
11. Low-Ambient Controller
Head pressure controller is a cycle control device activated by a temperature sensor mounted on a header tube of the outdoor coil. It is designed to cycle the outdoor fan motor in order to maintain condensing temperature within normal operating limits (approximately 100°F high and 60°F low). The control will maintain working head pressure at
SUGGESTED USE: Cooling operation at outdoor temperatures below 55°F (12.8°C).
12. Low-Pressure Switch
Auto reset SPST switch activated by refrigerant pressure on low side of refrigerant circuit. Cycles compressor off if refrigerant pressure drops to about 27 psig. Prevents indoor coil
SUGGESTED USE: Where indoor coil is exposed to ‘‘dirty’’ air. All commercial installations.
13. MotorMaster® Control
A fan speed control device activated by a temperature sensor. Designed to control condenser fan motor speed in response to the saturated, condensing temperature during operation in cooling mode only. For outdoor temperatures down to
SUGGESTED USE: Cooling operation at outdoor temperatures below 55°F. All commercial installations.
14. Outdoor Air Temperature Sensor
A device that allows the temperature at a remote location (outdoors) to be displayed at the thermostat.
SUGGESTED USE: All corporate programmable thermostats.
15. Support Feet
Four
SUGGESTED USE: Coastal installations.
Windy areas or where debris is normally circulating. Rooftop installations.
16. Thermostatic Expansion Valve (TXV)
A modulating flow control valve which meters refrigerant liquid flow rate into the evaporator in response to the superheat of the refrigerant gas leaving the evaporator. Kit includes valve, adapter tubes, and external equalizer tube. Both hard shutoff and RPB type valves are available.
SUGGESTED USE: For improved system performance in cooling mode for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory. Required for use on all zoning systems.
17. Time-Delay Relay
An SPST delay relay which briefly continues operation of the indoor blower motor to provide additional cooling after the compressor cycles off. SUGGESTED USE: For improved efficiency ratings for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory.
Required for use on all zoning systems.
18. Winter Start Control
An SPST delay relay which bypasses the