Bryant 594D warranty Specifications, Unit Size - Series, 018-E, 024-E, 030-E, 036-E, Electrical

Page 4

SPECIFICATIONS

UNIT SIZE - SERIES

018-E

 

024-E

 

030-E

 

036-E

OPERATING WT (Lb)

138

 

143

 

146

 

200

ELECTRICAL

 

 

 

 

 

 

 

Unit Volts—Hertz—Phase

208/230—60—1

 

208/230—60—1

 

208/230—60—1

 

208/230—60—1

Operating Voltage Range*

187—253

 

187—253

 

187—253

 

187—253

Compressor— Rated Load Amps

8.9

 

11.4

 

13.7

 

16.0

 

Locked Rotor Amps

41.0

 

56.0

 

72.5

 

88.0

Condenser Fan Motor—Full Load Amps

0.5

 

0.5

 

0.8

 

1.1

Min Unit Ampacity for Wire Sizing

11.6

 

14.8

 

17.9

 

21.1

Min Wire Size (60°C Copper) AWG†

14

 

14

 

14

 

12

Min Wire Size (75°C Copper) AWG†

14

 

14

 

14

 

12

Max Wire Length (60°C) (Ft)‡

61

 

53

 

56

 

66

Max Wire Length (75°C) (Ft)‡

58

 

50

 

53

 

63

Max Branch Circuit Fuse Size**

20

 

20

 

25

 

30

COMPRESSOR AND REFRIGERANT

 

 

 

 

 

 

 

Compressor—Manufacturer & Type

 

 

Copeland Scroll

 

 

Temperature & Current Protection

 

 

Internal Line Break

 

 

Refrigerant—R-22 Amount (Lb)

4.00

 

4.25

 

4.50

 

5.53

CONDENSER COIL AND FAN

 

 

 

 

 

 

 

Coil Face Area (Sq Ft)

7.27

 

 

8.8

 

12.0

Fins per In.—Rows—Circuits

 

20—1—1

 

 

25—1—2

Fan Motor—HP, Type, & RPM

1/12 PSC & 1100

 

1/10 PSC & 1100

 

1/5 PSC & 825

Volts—Hertz—Phase

 

 

208/230—60—1

 

 

Condenser Airflow (CFM)

 

1700

 

2000

 

3000

OPTIONAL EQUIPMENT

 

 

 

 

 

 

 

Support Feet Kit

 

 

KSASF0101AAA

 

 

Coastal Filter

 

 

KAACF0601SML

 

 

 

KAACF0201MED

Time-Delay Relay

 

 

KAATD0101TDR

 

 

Cycle Protector

 

 

KSACY0101AAA

 

 

Crankcase Heater

 

 

KAACH1201AAA

 

 

Start Assist—Capacitor/Relay Type

 

 

KSAHS1501AAA

 

 

Start Assist—PTC Type

 

 

KAACS0201PTC

 

 

TXV Kit (RPB)

KAATX0201RPB

 

KAATX0301RPB

 

KAATX0401RPB

 

KAATX0501RPB

TXV Kits (Hard Shutoff)

 

 

KSATX0601HSO

 

 

Low-Pressure Switch

 

 

KAALP0101LPS

 

 

High-Pressure Switch

 

 

KSAHI0101HPS

 

 

Filter Drier

 

 

P502-8083S (RCD)

 

 

Evaporator Freeze Thermostat††

 

 

KAAFT0101AAA

 

 

Liquid-Line Solenoid Valve

 

 

KAALS0101LLS

 

 

Winter Start Control††

 

 

KAAWS0101AAA

 

 

Low-Ambient Kit

 

 

KSALA0201R22

 

 

Low-Ambient Controller

 

 

P251-0083 (RCD)

 

 

MotorMaster® Control‡‡

 

 

32LT660004 (RCD)

 

 

Ball Bearing Fan Motor

 

 

HC34GE232 (RCD)

 

 

 

HC38GE231 (RCD)

Thermostat, Auto Changeover,

 

 

 

 

 

 

 

Non-Programmable, °F/°C,

 

 

 

 

 

 

 

1-Stage Heat, 1-Stage Cool

 

 

TSTATBBNAC01-B

 

 

Thermostat, Auto Changeover,

 

 

 

 

 

 

 

7-Day Programmable, °F/°C,

 

 

 

 

 

 

 

1-Stage Heat, 1-Stage Cool

 

 

TSTATBBPAC01-B

 

 

Builder’s Thermostat, Manual

 

 

 

 

 

 

 

Changeover, Non-Programmable,

 

 

 

 

 

 

 

°F/°C, 1-Stage Heat, 1-Stage Cool

 

 

TSTATBBBAC01-B

 

 

Thermidistat™ Control—Programmable/

 

 

 

 

 

 

 

Non-Programmable Thermostat with

 

 

 

 

 

 

 

Humidity Control

 

 

TSTATBBPRH01-B

 

 

Outdoor Air Temperature Sensor

 

 

TSTATXXSEN01-B

 

 

Backplate for Non-Programmable

 

 

 

 

 

 

 

Thermostat

 

 

TSTATXXNBP01

 

 

Backplate for Builder’s Thermostat

 

 

TSTATXXBBP01

 

 

Backplate for Programmable Thermostat

 

 

TSTATXXPBP01

 

 

Thermostat Conversion Kit (4 to 5 wire)

 

 

 

 

 

 

 

— 10 Pack

 

 

TSTATXXCNV10

 

 

See notes on page 5.

—4—

Image 4
Contents AVAILABLE OPTIONS Model 594D 60 HzELECTRIC AIR CONDITIONERDIMENSIONS IN RECOMMENDED TUBE DIAMETERS SOUND POWER dBACHECK-FLO-RATER SPECIFICATIONS UNIT SIZE - SERIES018-E 024-ESPECIFICATIONS Continued UNIT SIZE - SERIES042-E 048-E/FACCESSORY USAGE GUIDELINE 12. Low-PressureSwitch 11. Low-AmbientController13. MotorMaster Control 14. Outdoor Air Temperature SensorCOMBINATION RATINGS COMBINATION RATINGS Continued COMBINATION RATINGS Continued COMBINATION RATINGS Continued DETAILED COOLING CAPACITIES DETAILED COOLING CAPACITIES* Continued DETAILED COOLING CAPACITIES* Continued DETAILED COOLING CAPACITIES* Continued DETAILED COOLING CAPACITIES* Continued DETAILED COOLING CAPACITIES* Continued DETAILED COOLING CAPACITIES* Continued CONDENSER ONLY RATINGS 594D018-E594D024-E 594D030-ECONDENSER ONLY RATINGS* Continued 594D042-E594D048-E,F 594D060-ESYSTEM DESIGN SUMMARY MATCHED SYSTEM Page GUIDE SPECIFICATIONS Warranty for inclusion by specifying engineerOperating Characteristics Special Features