SYSTEM DESIGN SUMMARY

1.Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01 in. wc.

2.Minimum outdoor operating air temperature without low-ambient operation accessory is 55°F (12.8°C).

3.Maximum outdoor operating air temperature is 125°F (51.7°C).

4.For reliable operation, unit should be level in all horizontal planes.

5.Maximum elevation of indoor coil above or below base of outdoor unit is: Indoor coil above = 50 ft. Indoor coil below = 150 ft.

6.For interconnecting refrigerant tube lengths greater than 50 ft, consult Residential Split System Long-Line Application Guidelines available from equipment distributor.

7.Crankcase heater required when interconnecting refrigerant tube length exceeds 50 ft.

8.Not more than 3 ft of refrigerant tube should be buried in the ground. If necessary to bury tubes under a sidewalk, provide a minimum 6-in. vertical rise to the valve connections at the unit. For buried lines longer than 3 ft, consult your local distributor.

9.Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector provided.

10.Mix-matches of indoor coil capacity more than 1 size larger than outdoor unit capacity may result in inadequate indoor comfort.

11.Do not apply capillary tube indoor coils to these units.

—21—

Image 21
Contents Model 594D 60 Hz AVAILABLE OPTIONSELECTRIC AIR CONDITIONERDIMENSIONS IN SOUND POWER dBA RECOMMENDED TUBE DIAMETERSCHECK-FLO-RATER UNIT SIZE - SERIES SPECIFICATIONS018-E 024-EUNIT SIZE - SERIES SPECIFICATIONS Continued042-E 048-E/FACCESSORY USAGE GUIDELINE 11. Low-AmbientController 12. Low-PressureSwitch13. MotorMaster Control 14. Outdoor Air Temperature SensorCOMBINATION RATINGS COMBINATION RATINGS Continued COMBINATION RATINGS Continued COMBINATION RATINGS Continued DETAILED COOLING CAPACITIES DETAILED COOLING CAPACITIES* Continued DETAILED COOLING CAPACITIES* Continued DETAILED COOLING CAPACITIES* Continued DETAILED COOLING CAPACITIES* Continued DETAILED COOLING CAPACITIES* Continued DETAILED COOLING CAPACITIES* Continued 594D018-E CONDENSER ONLY RATINGS594D024-E 594D030-E594D042-E CONDENSER ONLY RATINGS* Continued594D048-E,F 594D060-ESYSTEM DESIGN SUMMARY MATCHED SYSTEM Page Warranty for inclusion by specifying engineer GUIDE SPECIFICATIONSOperating Characteristics Special Features