SYSTEM DESIGN SUMMARY
1.Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01 in. wc.
2.Minimum outdoor operating air temperature without
3.Maximum outdoor operating air temperature is 125°F (51.7°C).
4.For reliable operation, unit should be level in all horizontal planes.
5.Maximum elevation of indoor coil above or below base of outdoor unit is: Indoor coil above = 50 ft. Indoor coil below = 150 ft.
6.For interconnecting refrigerant tube lengths greater than 50 ft, consult Residential Split System
7.Crankcase heater required when interconnecting refrigerant tube length exceeds 50 ft.
8.Not more than 3 ft of refrigerant tube should be buried in the ground. If necessary to bury tubes under a sidewalk, provide a minimum
9.Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector provided.
10.
11.Do not apply capillary tube indoor coils to these units.