Bryant 594D SPECIFICATIONS Continued, Unit Size - Series, 042-E, 048-E/F, 060-E, Electrical

Page 5

SPECIFICATIONS Continued

UNIT SIZE - SERIES

042-E

 

048-E/F

 

060-E

OPERATING WT (Lb)

213

 

247

 

287

ELECTRICAL

 

 

 

 

 

Unit Volts—Hertz—Phase

208/230—60—1

 

208/230—60—1

 

208/230—60—1

Operating Voltage Range*

187—253

 

187—253

 

187—253

Compressor— Rated Load Amps

20.0

 

23.7/21.3

 

28.8

 

 

 

 

 

 

 

Locked Rotor Amps

104.0

 

129.0/137.0

 

169.0

Condenser Fan Motor—Full Load Amps

1.1

 

1.4

 

1.4

Min Unit Ampacity for Wire Sizing

26.1

 

31.0/28.0

 

37.4

Min Wire Size (60°C Copper) AWG†

10

 

8/10

 

8

Min Wire Size (75°C Copper) AWG†

10

 

10

 

8

Max Wire Length (60°C) (Ft)‡

96

 

71

 

104

Max Wire Length (75°C) (Ft)‡

91

 

68

 

99

Max Branch Circuit Fuse Size**

40

 

50/40

 

60

COMPRESSOR AND REFRIGERANT

 

 

 

 

 

Compressor—Manufacturer & Type

 

 

Copeland Scroll

 

Temperature & Current Protection

 

 

Internal Line Break

 

Refrigerant—R-22 Amount (Lb)

6.68

 

6.34

 

9.25

CONDENSER COIL AND FAN

 

 

 

 

 

Coil Face Area (Sq Ft)

15.2

 

 

18.3

Fins per In.—Rows—Circuits

25—1—3

 

 

25—1—4

Fan Motor—HP, Type, & RPM

1/5 PSC & 825

 

1/4 PSC & 1100

 

Volts—Hertz—Phase

 

 

208/230—60—1

 

Condenser Airflow (CFM)

3000

 

3300

 

OPTIONAL EQUIPMENT

 

 

 

 

 

Support Feet Kit

 

 

KSASF0101AAA

 

Coastal Filter

 

 

KAACF0201MED

 

Time-Delay Relay

 

 

KAATD0101TDR

 

Cycle Protector

KSACY0101AAA

 

Standard

 

Crankcase Heater

 

 

KAACH1201AAA

 

Start Assist—Capacitor/Relay Type

KSAHS1501AAA

 

 

KSAHS1601AAA

Start Assist—PTC Type

 

 

KAACS0201PTC

 

TXV Kit (RPB)

KAATX0501RPB

 

KAATX0601RPB

 

KAATX0701RPB

TXV Kits (Hard Shutoff)

KSATX0601HSO

 

KSATX0701HSO

 

Low-Pressure Switch

 

 

KAALP0101LPS

 

High-Pressure Switch

 

 

KSAHI0101HPS

 

Filter Drier

 

 

P502-8163S (RCD)

 

Evaporator Freeze Thermostat††

 

 

KAAFT0101AAA

 

Liquid-Line Solenoid Valve

 

 

KAALS0101LLS

 

Winter Start Control††

 

 

KAAWS0101AAA

 

Low-Ambient Kit

 

 

KSALA0201R22

 

Low-Ambient Controller

 

 

P251-0083 (RCD)

 

MotorMaster® Control‡‡

 

 

32LT660004 (RCD)

 

Ball Bearing Fan Motor

HC38GE231 (RCD)

 

HC40GE232 (RCD)

 

Thermostat, Auto Changeover,

 

 

 

 

 

Non-Programmable, °F/°C,

 

 

 

 

 

1-Stage Heat, 1-Stage Cool

 

 

TSTATBBNAC01-B

 

Thermostat, Auto Changeover,

 

 

 

 

 

7-Day Programmable, °F/°C,

 

 

 

 

 

1-Stage Heat, 1-Stage Cool

 

 

TSTATBBPAC01-B

 

Builder’s Thermostat, Manual

 

 

 

 

 

Changeover, Non-Programmable,

 

 

 

 

 

°F/°C, 1-Stage Heat, 1-Stage Cool

 

 

TSTATBBBAC01-B

 

Thermidistat™ Control—Programmable/

 

 

 

 

 

Non-Programmable Thermostat with

 

 

 

 

 

Humidity Control

 

 

TSTATBBPRH01-B

 

Outdoor Air Temperature Sensor

 

 

TSTATXXSEN01-B

 

Backplate for Non-Programmable

 

 

 

 

 

Thermostat

 

 

TSTATXXNBP01

 

Backplate for Builder’s Thermostat

 

 

TSTATXXBBP01

 

Backplate for Programmable Thermostat

 

 

TSTATXXPBP01

 

Thermostat Conversion Kit (4 to 5 wire)

 

 

 

 

 

— 10 Pack

 

 

TSTATXXCNV10

 

* Permissible limits of the voltage range at which the unit will operate satisfactorily. Operation outside these limits may result in unit failure. Copper wire must be used from service disconnect to unit.

† If wire is applied at ambient greater than 30°C (86°F), consult Table 310-16 of the NEC (ANSI/NFPA 70).

The ampacity of nonmetallic-sheathed cable (NM), trade name ROMEX, shall be that of 60°C (140°F) conductors, per the NEC (ANSI/NFPA 70) Article 336-26.

Length shown is as measured 1 way along wire path between unit and service panel for a voltage drop not to exceed 2 percent. All motors/compressors contain internal overload protection.

** Time-delay fuse.

†† Use with Low-Ambient Controller.

‡‡ Fan motor with ball bearings required.

—5—

Image 5
Contents Model 594D 60 Hz AVAILABLE OPTIONSELECTRIC AIR CONDITIONERDIMENSIONS IN CHECK-FLO-RATER SOUND POWER dBARECOMMENDED TUBE DIAMETERS UNIT SIZE - SERIES SPECIFICATIONS018-E 024-EUNIT SIZE - SERIES SPECIFICATIONS Continued042-E 048-E/FACCESSORY USAGE GUIDELINE 11. Low-AmbientController 12. Low-PressureSwitch13. MotorMaster Control 14. Outdoor Air Temperature SensorCOMBINATION RATINGS COMBINATION RATINGS Continued COMBINATION RATINGS Continued COMBINATION RATINGS Continued DETAILED COOLING CAPACITIES DETAILED COOLING CAPACITIES* Continued DETAILED COOLING CAPACITIES* Continued DETAILED COOLING CAPACITIES* Continued DETAILED COOLING CAPACITIES* Continued DETAILED COOLING CAPACITIES* Continued DETAILED COOLING CAPACITIES* Continued 594D018-E CONDENSER ONLY RATINGS594D024-E 594D030-E594D042-E CONDENSER ONLY RATINGS* Continued594D048-E,F 594D060-ESYSTEM DESIGN SUMMARY MATCHED SYSTEM Page Warranty for inclusion by specifying engineer GUIDE SPECIFICATIONSOperating Characteristics Special Features