Bryant 533A warranty System Design Summary

Page 22

SYSTEM DESIGN SUMMARY

1.Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01-in. wc.

2.Minimum outdoor operating air temperature without low-ambient operation accessory is 55°F (12.8°C).

3.Maximum outdoor operating air temperature is 125°F (51.7°C).

4.For reliable operation, unit should be level in all horizontal planes.

5.Maximum elevation of indoor coil above or below base of outdoor unit is: Indoor coil above = 30 ft, indoor coil below = 30 ft.

6.For interconnecting refrigerant tube lengths greater than 50 ft, consult the Residential Split-System Application Guideline and Service Manual for Air Conditioners and Heat Pumps using Puron® Refrigerant available from equipment distributor.

7.If any refrigerant tubing is buried, provide a 6 in. vertical rise to the valve connections at the unit. Refrigerant tubing lengths up to 36 in. may be buried without further consideration. For buried lines longer than 3 ft, consult your local distributor.

8.Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector provided.

9.Do not apply capillary tube indoor coils to these units.

10.Factory-supplied filter drier must be installed.

11.Do not deviate from factory specified TXV’s and Liquid Line Solenoids.

—22—

Image 22
Contents 533A 60 Hz Unit Dimensions Minimum Mounting DimensionsDimensions SizeCHECK-FLO-RATER Piston Recommended Tube DiametersCharging Subcooling TXV-TYPE Expansion Device Specifications ElectricalSpecifications KSAHS1601AAA/NAApplications Accessory Accessory Usage GuidelineRequired for LOW-AMBIENT LONG-LINE SEA Coast Unit Size Sound Blanket SizeCombination Ratings Coils + 355MAV060080 Variable Speed Furnace Combination RatingsCoils + 333B,JAV048080 Variable Speed Furnace Coils + 355MAV060100 Variable Speed FurnaceCoils + 333B,JAV060100 Variable Speed Furnace Coils + 333B,JAV060120 Variable Speed FurnaceFX4ANF048 11.45 Tested combination 533AN024-A Outdoor Section With CK5AA030 Indoor Section Evap Condenser Entering AIR Temperatures FDetailed Cooling Capacities CFM EWB533AN030-A Outdoor Section With CK5AA036 Indoor Section Detailed Cooling CapacitiesCoils + 333B,JAV036060 Variable Speed Furnace 533AN036-A Outdoor Section With CK5AA042 Indoor Section Coils + 333B,JAV048080 Variable Speed Furnace533AN042-A Outdoor Section With CK5AA048 Indoor Section Coils + 333B,JAV060100 Variable Speed Furnace533AN048-A Outdoor Section With CK5AA060 Indoor Section 533AN060-A Outdoor Section With CK5AA060 Indoor Section Coils + 333B,JAV060120 Variable Speed Furnace533AN024-A SST Condenser Entering AIR Temperatures FCondenser only Ratings 533AN030-A533AN048-A Condenser only Ratings533AN042-A 533AN060-ASystem Design Summary Page General Guide SpecificationsProducts