GUIDE SPECIFICATIONS

GENERAL

System Description

Outdoor-mounted, air-cooled, split-system air conditioner unit suitable for ground or rooftop installation. Unit consists of a her- metic compressor, an air-cooled coil, propeller-type condenser fan, and a control box. Unit will discharge supply air upward as shown on contract drawings. Unit will be used in a refrigeration circuit to match up to a packaged fan coil or coil unit.

Quality Assurance

Unit will be rated in accordance with the latest edition of ARI Standard 210.

Unit will be certified for capacity and efficiency, and listed in the lastest ARI directory.

Unit construction will comply with latest edition of ANSI/ ASHRAE and with NEC.

Unit will be constructed in accordance with UL standards and will carry the UL label of approval. Unit will have c-UL approval.

Unit cabinet will be capable of withstanding Federal Test Method Standard No. 141 (Method 6061) 500-hr salt spray test.

Air-cooled condenser coils will be leak tested at 250 psig and pressure tested at 450 psig.

Unit constructed in ISO9001 approved facility.

Delivery, Storage, and Handling

Unit will be shipped as single package only and is stored and handled per unit manufacturer’s recommendations.

Warranty (for inclusion by specifying engineer)

U.S. and Canada only.

PRODUCTS

Equipment

Factory assembled, single piece, air-cooled air conditioner unit. Contained within the unit enclosure is all factory wiring, piping, controls, compressor, refrigerant charge Puron® (R-410A), and special features required prior to field start-up.

Refrigerant

Refrigerant will be Puron HFC Refrigerant with zero ozone depletion potential. Puron is approved under the EPA’s Significant New Alternatives Program (SNAP).

Unit Cabinet

Unit cabinet will be constructed of galvanized steel, bonderized, and coated with a powder coat paint.

Fans

Condenser fan will be direct-drive propeller type, discharging air upward.

Air-Cooled, Split-System Air Conditioner 533A 2 to 5 Tons Nominal

Fans

Condenser fan will be direct-drive propeller type, discharging air upward.

Condenser fan motors will be totally enclosed, 1-phase type with class B insulation and permanently lubricated bearings.

Shafts will be corrosion resistant.

Fan blades will be statically and dynamically balanced.

Condenser fan openings will be equipped with PVC-coated steel wire safety guards.

Compressor

Compressor will be hermetically sealed.

Compressor will be mounted on rubber vibration isolators.

Condenser Coil

Condenser coil will be air cooled.

Coil will be constructed of aluminum fins mechanically bonded to copper tubes which are then cleaned, dehydrated, and sealed.

Refrigeration Components

Refrigeration circuit components will include liquid-line shutoff valve with sweat connections, vapor-line shutoff valve with sweat connections, system charge of Puron® (R-410A) refrigerant, and compressor oil.

Operating Characteristics

The capacity of the unit will meet or exceed _____ Btuh at a

suction temperature of _____ °F. The power consumption at full

load will not exceed _____ kw.

Combination of the unit and the evaporator or fan coil unit will have a total net cooling capacity of _____ Btuh or greater at

conditions of _____ CFM entering air temperature at the

evapo-rator at _____ °F wet bulb and _____ °F dry bulb, and

air enter-ing the unit at _____ °F.

The system will have an SEER of _____ Btuh/watt or greater at

DOE conditions.

Electrical Requirements

Nominal unit electrical characteristics will be _____ v, single

phase, 60 hertz. The unit will be capable of satisfactory opera- tion within voltage limits of _____ v to _____ v.

Unit electrical power will be single point connection. Control circuit will be 24v.

Special Features

Refer to section of this literature identifying accessories and descriptions for specific features and available enhancements.

SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE

UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS

Cancels: NEW

© 2000 Bryant Heating & Cooling Systems, 7310 W. Morris St. Indpls, IN 46231

—24—

PRINTED IN U.S.A. Catalog No. 5253-300 2-00

Image 24
Contents 533A 60 Hz Dimensions DimensionsUnit Dimensions Minimum Mounting SizeRecommended Tube Diameters CHECK-FLO-RATER PistonCharging Subcooling TXV-TYPE Expansion Device Specifications ElectricalSpecifications KSAHS1601AAA/NAAccessory Usage Guideline Applications AccessoryRequired for LOW-AMBIENT LONG-LINE SEA Coast Unit Size Sound Blanket SizeCombination Ratings Combination Ratings Coils + 333B,JAV048080 Variable Speed FurnaceCoils + 355MAV060080 Variable Speed Furnace Coils + 355MAV060100 Variable Speed FurnaceCoils + 333B,JAV060100 Variable Speed Furnace Coils + 333B,JAV060120 Variable Speed FurnaceFX4ANF048 11.45 Tested combination Evap Condenser Entering AIR Temperatures F Detailed Cooling Capacities533AN024-A Outdoor Section With CK5AA030 Indoor Section CFM EWBDetailed Cooling Capacities 533AN030-A Outdoor Section With CK5AA036 Indoor SectionCoils + 333B,JAV036060 Variable Speed Furnace 533AN036-A Outdoor Section With CK5AA042 Indoor Section Coils + 333B,JAV048080 Variable Speed Furnace533AN042-A Outdoor Section With CK5AA048 Indoor Section Coils + 333B,JAV060100 Variable Speed Furnace533AN048-A Outdoor Section With CK5AA060 Indoor Section 533AN060-A Outdoor Section With CK5AA060 Indoor Section Coils + 333B,JAV060120 Variable Speed FurnaceSST Condenser Entering AIR Temperatures F Condenser only Ratings533AN024-A 533AN030-ACondenser only Ratings 533AN042-A533AN048-A 533AN060-ASystem Design Summary Page Guide Specifications GeneralProducts