Bryant 533A warranty Accessory Usage Guideline, Required for LOW-AMBIENT LONG-LINE SEA Coast

Page 6

*Permissible limits of the voltage range at which the unit will operate satisfactorily. Operation outside these limits may result in unit failure.

† If wire is applied at ambient greater than 30°C (86°F), consult Table 310-16 of the NEC (ANSI/NFPA 70).

The ampacity of nonmetallic-sheathed cable (NM), trade name ROMEX, shall be that of 60°C (140°F) conductors, per the NEC (ANSI/NFPA 70) Article 336-26. If other than uncoated (non-plated), 60 or 75°C (140 or 167°F) insulation, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA 70).

‡ Length shown is as measured 1 way along wire path between unit and service panel for a voltage drop not to exceed 2%.

**Fan motor with ball bearings required.

††See low-ambient controller Installation Instructions for application.

N/A — Not Applicable.

NOTE: Copper wire must be used from service disconnect to unit. All motors/compressors contain internal overload protection.

ACCESSORY USAGE GUIDELINE

 

REQUIRED FOR

REQUIRED FOR

REQUIRED FOR

 

LOW-AMBIENT

LONG-LINE

SEA COAST

 

APPLICATIONS

APPLICATIONS*

APPLICATIONS

ACCESSORY

(Below 55°F)

(Over 50 Ft)

(Within 2 Miles)

 

 

 

 

Crankcase Heater

Yes

Yes

No

 

 

 

 

Evaporator Freeze Thermostat

Yes

No

No

 

 

 

 

Winter Start Control

Yes†

No

No

 

 

 

 

Accumulator

No

No

No

 

 

 

 

Compressor Start Assist

Yes

Yes

No

Capacitor and Relay

 

 

 

 

 

 

 

Low-Ambient Controller,

 

 

 

MotorMaster® Control,

Yes

No

No

or

 

 

 

Low-Ambient Pressure Switch

 

 

 

 

 

 

 

Wind Baffle

See Low-Ambient Instructions

No

No

 

 

 

 

Coastal Filter

No

No

Yes

 

 

 

 

Support Feet

Recommended

No

Recommended

 

 

 

 

Liquid-Line Solenoid Valve

 

See Long-Line

 

or

No

Application

No

Hard Shutoff TXV

 

Guideline

 

 

 

 

 

Ball Bearing Fan Motor

Yes‡

No

No

 

 

 

 

*For tubing line sets greater than 50 ft, refer to Residential Split-System Long-Line Application Guideline and Service Manual.

† Only when low-pressure switch is used.

‡ Required for Low-Ambient Controller (full modulation feature) and MotorMaster® Control only.

ACCESSORY DESCRIPTION AND USAGE (Listed Alphabetically)

1.Ball Bearing Fan Motor

A fan motor with ball bearings which permits speed reduction while maintaining bearing lubrication.

SUGGESTED USE: Required on all units where Low-Ambient Controller (full modulation feature) or MotorMaster® Control has been added.

2.Coastal Filter

A mesh screen inserted under the top cover and inside base pan to protect the condenser coil from corrosive atmosphere without restricting airflow. SUGGESTED USE: In geographic areas where salt damage could occur.

In areas with high pollution levels.

3.Compressor Start Assist—Capacitor/Relay Type

Start capacitor and start relay which gives a “hard” boost to compressor motor at each start-up.

SUGGESTED USE: Installations where interconnecting tube length exceeds 50 ft.

Installations where outdoor design temperature exceeds 105°F (40.6°C).

Installations where Liquid-Line Solenoid Valve or hard shutoff TXV has been added.

4.Compressor Start Assist—PTC Type

Solid-state electrical device which gives a “soft” boost to compressor motor at each start-up.

SUGGESTED USE: Installations with marginal power supply.

5.Crankcase Heater

An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles. Improves compressor lubrication

on restart and minimizes chance of refrigerant slugging. May or may not include a thermostat control. SUGGESTED USE: When interconnecting tube length exceeds 50 ft.

When unit will be operated below 55°F (12.8°C) outdoor air temperature. Use with Low-Ambient Controller. All commercial installations.

6.Cycle Protector

Solid state timing device which prevents compressor rapid recycling. Control provides an approximate 5-minute delay after power to the compressor has been interrupted for any reason, including normal room thermostat cycling.

SUGGESTED USE: Installations in areas where power interruptions are frequent. Where user is likely to “play” with the room thermostat.

All commercial installations.

Installations where interconnecting tube length exceeds 50 ft. High-rise applications.

7.Evaporator Freeze Thermostat

An SPST temperature actuated switch which stops unit operation when evaporator reaches freeze-up conditions.

SUGGESTED USE: All units where Winter Start Control has been added.

8.Filter Drier (Suction Line)

A device for removing contaminants from refrigerant circulating in an air conditioner: 1-direction flow.

SUGGESTED USE: All split-system air conditioners.

—6—

Image 6
Contents 533A 60 Hz Unit Dimensions Minimum Mounting DimensionsDimensions SizeRecommended Tube Diameters CHECK-FLO-RATER PistonCharging Subcooling TXV-TYPE Expansion Device Specifications ElectricalSpecifications KSAHS1601AAA/NAAccessory Usage Guideline Applications AccessoryRequired for LOW-AMBIENT LONG-LINE SEA Coast Unit Size Sound Blanket SizeCombination Ratings Coils + 355MAV060080 Variable Speed Furnace Combination RatingsCoils + 333B,JAV048080 Variable Speed Furnace Coils + 355MAV060100 Variable Speed FurnaceCoils + 333B,JAV060100 Variable Speed Furnace Coils + 333B,JAV060120 Variable Speed FurnaceFX4ANF048 11.45 Tested combination 533AN024-A Outdoor Section With CK5AA030 Indoor Section Evap Condenser Entering AIR Temperatures FDetailed Cooling Capacities CFM EWBDetailed Cooling Capacities 533AN030-A Outdoor Section With CK5AA036 Indoor SectionCoils + 333B,JAV036060 Variable Speed Furnace 533AN036-A Outdoor Section With CK5AA042 Indoor Section Coils + 333B,JAV048080 Variable Speed Furnace533AN042-A Outdoor Section With CK5AA048 Indoor Section Coils + 333B,JAV060100 Variable Speed Furnace533AN048-A Outdoor Section With CK5AA060 Indoor Section 533AN060-A Outdoor Section With CK5AA060 Indoor Section Coils + 333B,JAV060120 Variable Speed Furnace533AN024-A SST Condenser Entering AIR Temperatures FCondenser only Ratings 533AN030-A533AN048-A Condenser only Ratings533AN042-A 533AN060-ASystem Design Summary Page Guide Specifications GeneralProducts