Bard CH4S1, CH5S1, CH3S1 Wiring Main Power, TAP Range, Thermostat Wire Size

Page 15

FIGURE 10

COMMON WALL MOUNTING INSTALLATIONS

Closet Installation

Note: duct maybe in attic or below rafters as shown.

WIRING – LOW VOLTAGE WIRING

230 / 208V, 1 phase and 3 phase equipment have 24V transformers with dual primary voltage. All equipment leaves the factory wired on 240V tap. For 208V operation, reconnect from 240V to 208V tap. The

Unit (outside)

Rafters

acceptable operating voltage range for the 240 and 208V taps are:

 

 

Supply Air

Duct

 

 

Finished Ceiling

Grille

 

 

Wall Sleeve

 

Outside Wall

Return Air

Closet Wall

Closet Wall

 

 

Raised Closet Floor

Grille

 

 

Return Air

 

TAP

RANGE

240

253 – 216

208

220 – 187

NOTE: 460V units require no action. The voltage should be measured at the field power connection point in the unit and while the unit is operating at full load (maximum amperage operating condition).

FIGURE 11

UNIT 24V ThERMOstat connections

OPTIONAL

THERMOSTAT BARD PART

#8403-052, 8403-053, 8403-055

8403-061

OUTDOOR

 

WIRING – MAIN POWER

MIS-2240

SENSOR

C G Rc Rh Y1 Y2 B

W1

AUX

Refer to the unit rating plate for wire sizing information and maximum fuse or “HACR” type circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. Depending on the installed KW of electric heat, there may be two field power circuits required. If this is the case, the unit serial plate will so indicate. All models are suitable only for connection with copper wire. Each unit and/or wiring diagram will be marked “Use Copper Conductors Only”. These instructions must be adhered to. Refer to the National Electrical Code (NEC) for complete current carrying capacity data on the various insulation grades of wiring material. All wiring must conform to NEC and all local codes.

The electrical data lists fuse and wire sizes (75°C copper) for all models including the most commonly used heater sizes. Also shown are the number of field power circuits required for the various models with heaters.

The unit rating plate lists a “Maximum Time Delay Relay Fuse” or “HACR” type circuit breaker that is to be used with the equipment. The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor.

The disconnect access door on this unit may be locked to prevent unauthorized access to the disconnect. To convert for the locking capability, bend the tab located in the bottom left hand corner of the disconnect opening under the disconnect access panel straight out. This tab will now line up with the slot in the door. When shut, a padlock may be placed through the hole in the tab preventing entry.

See “Start Up” section for important information on three phase scroll compressor start ups.

GND OD

 

 

 

 

 

 

 

THERMOSTAT

 

 

 

 

 

 

 

 

BARD PART #8403-060

 

 

 

 

 

 

 

 

GND ID

C

G

R

Y1

Y2

O/B

W2

W1/E

L

D/YO

A

 

 

 

 

 

 

 

 

 

 

 

1

OPTIONAL

C

G

R

Y

Y1

B

W1 W2

W3 E

L

DH

O1

8403-062

 

 

 

 

 

 

 

 

 

 

 

INDOOR

 

 

 

 

 

 

 

UNIT LOW VOLTAGE

SENSOR

 

 

Factory Jumper

 

TERMINAL BLOCK

MIS-2026 C

Only needed if dehumidification is used.

Eleven (11) wires should be run from thermostat subbase to the 24V terminal board in the unit. An eleven conductor, 18 gauge copper color-coded thermostat cable is recommended. The connection points are shown in Figure 11. An additional wire is needed if dehumidification is used.

IMPORTANT

Only the thermostat combinations as shown above will work with this equipment.

Table 3

THERMOSTAT WIRE SIZE

Transformer

 

 

Maximum

FLA

Wire Gauge

Distance

VA

 

 

In Feet

 

 

 

 

 

20 gauge

45

 

 

 

 

 

 

18 gauge

60

 

 

 

 

65

2.3

16 gauge

100

 

 

 

 

 

 

14 gauge

160

 

 

12 gauge

250

 

 

 

 

Manual 2100-455M

Page

15 of 28

Image 15
Contents Models CH3S1 CH4S1 CH5S1Contents For more information, contact these publishers Getting Other Information and PublicationsElectric Heat Table Heat Pump Wall Mount Model NomenclatureCH 4S 1 a X X XUnit Dimensions CH3S1 Unit DimensionsCH4S1 and CH5S1 Unit Dimensions Single Circuit Dual Circuit Electrical SpecificationsFilters Shipping DamageGeneral Duct WorkMounting the Unit OPTiOnal top outlet flangeCH3S1 Wall Mounting Instructions CH4S1 and CH5S1 Wall Mounting Instructions Electric Heat Clearance Optional Clearance RecommendedReturn Opening Wall Mounting InstructionsCommon Wall Mounting Installations False Wall InstallationWiring Main Power Thermostat Wire SizeTAP Range Application Low voltage connectionsImportant Installer Note Pressure Service PortsStart UP cont’d COmpressor current & pressure control module Phase MonitorService Hints Sequence of OperationDefrost Control Board Defrost CycleManual 2100-455M Troubleshooting Solid State Heat Pump Control Troubleshooting ProcedureTemperature F VS Resistance R of Temperature Checking Temperature Sensor Outside Unit CircuitRefrigerant CHARGe FAN Blade Setting DimensionsCompressor SOlenoid Removal of FAN ShroudMaximum ESP of Operation Indoor Blower PerformancePressure Table TemperaturePressure Table Symptom Cause/Procedure Troubleshooting GE ECM MotorsReplacing ECM Control Module Troubleshooting GE ECM Motors Contd
Related manuals
Manual 25 pages 23.1 Kb Manual 14 pages 10.23 Kb

CH3S1, CH5S1, CH4S1 specifications

Bard CH3S1, CH4S1, and CH5S1 represent a formidable trio of advanced technologies in the field of AI-driven natural language processing. These models are designed to facilitate seamless communication, enhance productivity, and deliver personalized experiences across various applications.

One of the main features of the Bard CH series is its ability to understand and generate human-like text. This is achieved through deep learning algorithms that analyze vast datasets to learn language patterns, context, and nuances. The CH3S1 model, for instance, excels in basic conversational tasks, making it suitable for customer support, virtual assistants, and simple content generation. Its training allows it to respond efficiently to user inputs while maintaining clarity and engagement.

As we progress to the CH4S1 model, we observe significant enhancements in contextual understanding. This model can handle more complex conversations, making it adept at tasks requiring greater cognitive processing, such as technical support and nuanced dialogue-based applications. The increased parameter count and refined training methods contribute to its ability to grasp intricate sentence structures and varied linguistic styles, leading to more coherent and relevant responses.

Building upon the capabilities of its predecessors, the CH5S1 model represents the pinnacle of the Bard CH series. It integrates advanced features such as multi-modal processing, allowing it to work with text, images, and even sound. This model is engineered to perform in more specialized fields, such as healthcare, legal, and creative writing, where precise language and context are critical. The CH5S1 leverages feedback loops from real-time interactions to continuously improve its understanding and output, making it not only a tool for communication but also an intelligent partner for businesses and individuals alike.

In terms of technology, all three models utilize transformer architecture, which has proven effective in tasks requiring attention and context retention. They also implement reinforcement learning techniques to adapt and refine their models based on user engagement data. Furthermore, security and data privacy are prioritized, with strict adherence to ethical AI guidelines to ensure user trust.

Overall, the Bard CH series signifies a leap forward in artificial intelligence, combining advanced linguistic capabilities with a user-centric approach, thus redefining how we interact with machines and enhancing our digital experiences.