Emerson AE4-1395 manual 22, R-407C, R-410A Operating Envelope, ZPD34-54K5

Page 14

Application Engineering

 

 

 

 

B U L L E

T

I

N

AE4-1395

 

 

 

R-22, R-407C, R-410A Operating Envelope

ZPD34-54K5

 

 

160

 

 

 

 

 

 

ZPD61-91KC

 

 

 

 

 

 

 

 

ZRD36-81KC

 

 

 

 

 

 

 

 

 

 

 

150

 

 

 

 

 

 

 

 

 

140

 

 

 

 

 

 

 

 

(°F)

130

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Recommended

 

 

Temperature

 

 

 

 

 

 

 

 

120

 

 

 

 

 

Capacity

 

 

 

 

 

 

 

 

Range

 

 

 

 

 

 

 

 

10 -100%

 

 

Condensing

110

 

 

 

Recommended

 

 

 

 

 

 

 

 

Capacity

 

 

 

 

 

 

 

 

Range

 

 

 

 

100

 

Recommended

 

50 -100%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Capacity

 

 

 

 

 

 

 

90

 

Range

 

 

 

 

 

 

 

 

 

75 -100%

 

 

 

 

 

 

 

80

 

 

 

 

 

 

 

 

 

70

 

 

 

 

 

 

 

 

 

-20

-10

0

10

20

30

40

50

60

Evaporating Temperature (°F)

Figure 4

 

 

 

R-22, R-407C, R-410A Operating Envelope

ZPD103-182KC

 

160

 

 

 

 

 

 

ZRD94-125KC

 

 

 

 

 

 

 

 

 

 

150

 

 

 

 

 

 

 

 

 

140

 

 

 

 

 

 

 

 

 

130

 

 

 

 

 

 

 

 

(°F)

120

 

 

 

 

 

Recommended

 

 

 

 

 

 

 

 

 

 

Temperature

110

 

 

 

 

 

Capacity

 

 

 

 

 

 

 

Range

 

 

 

 

 

 

 

 

 

 

100

 

 

 

 

 

10 -100%

 

 

 

 

 

Recommended

 

 

 

 

 

 

 

 

 

 

 

 

Condensing

 

 

 

 

Capacity

 

 

 

 

90

 

 

 

Range

 

 

 

 

 

 

Recommended

 

50 -100%

 

 

 

 

80

 

Capacity

 

 

 

 

 

 

 

 

 

Range

 

 

 

 

 

 

 

70

 

75 -100%

 

 

 

 

 

 

 

60

 

 

 

 

 

 

 

 

 

50

 

 

 

 

 

 

 

 

 

40

 

 

 

 

 

 

 

 

 

-20

-10

0

10

20

30

40

50

60

Evaporating Temperature (°F)

Figure 5

© 2012 Emerson Climate Technologies, Inc.

14

Printed in the U.S.A.

 

Image 14
Contents Service Procedures SafetyAssembly Line Procedures IntroductionSafety Instructions Safety Icon ExplanationPressurized System Hazard Safety StatementsElectrical Shock Hazard Burn HazardHow it Works 410A 22 & R-407CNomenclature Digital Compressor Operation Application ConsiderationsPressure Fluctuations Sound CharacteristicsSolenoid Valve and Coil PipingCrankcase Heaters Scroll Temperature ProtectionPower Factor Oil Type and Oil RemovalOil Level Verification Modulation ControlApplication Tests Digital Compressor Retrofit ApplicationsSystem Modifications Retrofit Applications To AvoidPerformance Modeling Compressor Selection & Change-OutAssembly Line Procedures To 7.5 Ton Modulation Valve Replacement Procedure Service ProceduresModulation Troubleshooting To 15 Ton Modulation Valve Replacement ProcedureCopeland Scroll Compressor Functional Check Form No50% Loaded 80% Loaded To 15 Ton Digital Scroll Cross Sectional View 22, R-407C, R-410A Operating Envelope ZPD34-54K5Second Operating Cycle AE4-1395 Compressor Capacity Graph Discharge ThermistorsTo 7.5 Ton Tandem Yes Foot-Pounds Inch-Pounds Refrigerant Charge Limits Model PoundsPart TBD