Emerson AE4-1395 manual Refrigerant Charge Limits Model Pounds, Part, Foot-Pounds Inch-Pounds

Page 18

Application Engineering

 

 

 

 

B U L L E

T

I

N

AE4-1395

Table 1

Copeland Scroll Digital Family Features

 

Digital

 

 

 

Discharge

Internal

 

 

Discharge Gas Temperature

Pressure

Modulation

Model

Modulation

Check

Protection

Relief (IPR)

Control

 

Valve

Valve

 

 

 

 

Valve

 

 

 

 

 

 

 

 

 

ZPD34-54K5

 

 

 

 

 

 

 

 

ZRD36-48KC

Required

External Sensor Required

No

Yes

 

ZPD61-91KC

Accessory

 

 

 

15 Second

 

 

 

 

 

 

ZRD61-81KC

 

Internal Top Cap Thermistor

 

 

 

Cycle

ZPD103-182KC

Installed On

External Sensor Required

Yes

No

 

ZRD94-125KC

Compressor

 

 

 

 

 

 

 

 

 

 

 

Table 2

 

 

 

 

 

 

Refrigerant Charge Limits

 

 

 

 

 

 

 

 

 

 

 

 

 

Model

 

Charge Limit

 

 

 

 

 

 

Pounds

kg

 

 

 

 

 

 

 

 

 

 

 

 

ZPD34-54K5

 

8

3.6

 

 

 

 

 

ZPD61-91KC

 

10

4.8

 

 

 

 

 

ZPD103-137KC

 

16

7.2

 

 

 

 

 

ZPD154-182KC

 

18

8.2

 

 

 

 

 

ZPDT12-18MC

 

12

5.4

 

 

 

 

 

ZPDU13MC

 

12

5.4

 

 

 

 

 

ZPDT21-27MC

 

24

10.9

 

 

 

 

 

ZPDT31-36MC

 

27

12.2

 

 

 

 

 

ZRD36-48KC

 

8

3.6

 

 

 

 

 

ZRD61-81KC

 

10

4.8

 

 

 

 

 

ZRD94-125KC

 

16

7.2

 

 

 

 

 

ZRDU11-13MC

 

12

5.4

 

 

 

 

 

ZRDT12-16MC

 

12

5.4

 

 

 

 

 

ZRDT25MC

 

27

12.2

 

 

 

 

 

Table 3

 

 

 

Torque Values

 

 

 

 

 

 

 

 

Part

 

Torque

 

 

 

Foot-Pounds

Inch-Pounds

 

 

 

 

Modulation Valve

 

18.8-19.5

 

225-235

 

(ZPD103-182KC & ZRD94-125KC)

 

 

 

 

Solenoid Coil Screw

 

1.9-2.3

 

22.5-27.5

© 2012 Emerson Climate Technologies, Inc.

18

 

 

 

Printed in the U.S.A.

 

 

 

 

Image 18
Contents Service Procedures SafetyAssembly Line Procedures IntroductionSafety Instructions Safety Icon ExplanationPressurized System Hazard Safety StatementsElectrical Shock Hazard Burn HazardHow it Works 410A 22 & R-407CNomenclature Digital Compressor Operation Application ConsiderationsPressure Fluctuations Sound CharacteristicsSolenoid Valve and Coil PipingCrankcase Heaters Scroll Temperature ProtectionPower Factor Oil Type and Oil RemovalOil Level Verification Modulation ControlApplication Tests Digital Compressor Retrofit ApplicationsSystem Modifications Retrofit Applications To AvoidPerformance Modeling Compressor Selection & Change-OutAssembly Line Procedures To 7.5 Ton Modulation Valve Replacement Procedure Service ProceduresModulation Troubleshooting To 15 Ton Modulation Valve Replacement ProcedureCopeland Scroll Compressor Functional Check Form No50% Loaded 80% Loaded To 15 Ton Digital Scroll Cross Sectional View 22, R-407C, R-410A Operating Envelope ZPD34-54K5 Second Operating Cycle AE4-1395 Compressor Capacity Graph Discharge ThermistorsTo 7.5 Ton Tandem Yes Refrigerant Charge Limits Model Pounds PartFoot-Pounds Inch-Pounds TBD