Application Engineering |
|
|
|
|
B U L L E | T | I | N |
|
bar) for
For heat pumps, a cut out setting no lower than 20 psig (1.4 bar) is recommended for
Scroll Temperature Protection
Most digital scrolls do not have internal discharge gas temperature protection. In order for the Emerson controllers to operate properly an NTC sensor must be attached to the compressor discharge line as close as possible to the compressor discharge fitting. For best response the sensor should be insulated. See Table 1 of
The ZRD61 through ZRD81KC compressors have a discharge thermistor that is inside of a well in the top cap of the compressor. If this thermistor ever needs to be replaced, it should be replaced with either
Crankcase Heaters
A crankcase heater is required if the system charge exceeds the system charge limits listed in Table 2. For more information regarding regarding heater part numbers and installation location please refer to the equivalent
Oil Type and Oil Removal
Mineral oil is used in the ZRD*KC compressors for
&
It is an approved practice to use ZRD*KCE compressors with POE to replace ZRD*KC compressors with mineral oil in
If additional oil is needed in the field for POE applications, Copeland™ Ultra
© 2012 Emerson Climate Technologies, Inc. | 6 |
Printed in the U.S.A. |
|
If additional oil is needed in the field for mineral oil applications, Sonneborn Suniso 3GS or Chevron Texaco Capella WF32 should be used.
CAUTION
POE must be handled carefully and the proper protective equipment (gloves, eye protection, etc.) must be used when handling POE lubricant. POE must not come into contact with any surface or material that might be harmed by POE, including without limitation, certain polymers (e.g. PVC/CPVC and polycarbonate).
Power Factor
During the loaded state the digital scroll compressor operates at full capacity and the power factor is the same as a standard scroll. However, when the scrolls are unloaded, the power factor is much lower. If power factor is an important consideration, the correcting capacitors should be calculated using the full capacity data to avoid problems associated with over correction. See
Tandem Applications
Tandem compressors follow the same application guidelines as single compressors outlined in this bulletin. The refrigerant charge limit for tandem compressors is shown in Table 2. A tandem circuit with a charge over this limit must have crankcase heaters applied to both compressors.
Tandem compressor assemblies are available for purchase from Emerson. In lieu of purchasing the assembled tandem, the OEM has the option to purchase the
For more information on tandems, please refer to the