Emerson AE4-1395 manual Modulation Control, Application Tests, Oil Level Verification

Page 7

Application Engineering

 

 

 

 

B U L L E

T

I

N

AE4-1395

Modulation Control

Two different controls are available from Emerson to provide digital scroll modulation control, the Copeland ScrollDigital Compressor Controller and the Emerson Commercial Comfort Controller.

The Copeland ScrollDigital Compressor Controller is an open loop controller that provides control, protection, and diagnostics for the digital scroll and is suited for OEM applications. The system controller supplied by the OEM calculates the required compressor capacity and communicates that capacity to the digital scroll controller via a 1-5 VDC analog signal. For more information on the Copeland Scroll Digital Compressor Controller please refer to AE8-1328.

The Emerson Commercial Comfort Controller is a closed loop controller that provides modulation control based on space temperature and is suited for both OEM and retrofit applications. This controller is typically located in the conditioned space and controls the modulation cycle of the compressor without the need for an additional system controller. For more information on the Emerson Commercial Comfort Controller, please refer to AE8-1393.

NOTICE

For OEMs that choose their own controls package, the controls must include the protection features incorporated into the Copeland ScrollDigital Compressor Controller. Please consult with Application Engineering for a list of these requirements.

APPLICATION TESTS

Oil Level Verification

If the system configuration is more complex than a single circuit packaged system with one compressor, evaporator, and condenser, an oil return test is highly recommended during system development testing. For this test a sample compressor with a sight-tube should be used to observe the oil level over the entire operating range of the system at the expected compressor modulation rates, to ensure an adequate oil level in the compressor at all times. The oil level should not go below the weld points of the lower bearing bracket for the 3 through 7.5 ton compressors. For the 8 ton and larger digital scrolls the minimum oil level is 1.5" (40 mm) below the center of the standard oil sight- glass on the compressor. If the oil level falls below the prescribed level for more than a few minutes either more oil is required in the system or an oil recovery cycle is needed. For more information on what an oil recovery cycle is, please consult with Application Engineering.

© 2012 Emerson Climate Technologies, Inc.

7

Printed in the U.S.A.

 

If the system contains more than 20 pounds (9 kg) of refrigerant, it is our recommendation to add one fluid ounce of additional oil for every 5 pounds (15 ml/kg) of refrigerant over this amount. This is a starting point and oil should be added as determined through system testing or as required by the end use application in the field.

The compressor oil level should be checked with the compressor "off" to avoid the sump turbulence when the compressor is running. Manifolded compressors should have their oil levels checked after 20 to 30 seconds of off time, to allow oil balancing between the manifolded compressors.

Excessive Liquid Flood Back Tests

It is expected that the design will not flood during operation at all of the varying loaded and modulation conditions. This places demanding requirements on the flow control device to control refrigerant flow and superheat all the way down to 10% of full load.

Throughout the operating range of the unit, the suction superheat must remain positive. If the flow control device is unable to maintain superheat, an electronic expansion valve, accumulator, or other means must be taken to maintain at least 20°F of compressor sump superheat.

Operating Envelope Test

The operating envelopes and recommended modulation ranges are shown in Figures 4 and 5. System testing must be performed if operation outside of these recommended ranges is desired. System testing should consist of unit/ system operation at abnormal operating conditions to verify that suction superheat and compressor discharge temperatures stay in a range that is healthy for the compressor and tripping of the compressor overload is avoided. Please consult with application engineering for recommended tests and analysis of test data.

DIGITAL COMPRESSOR RETROFIT APPLICATIONS

Reasons To Retrofit

There are a number of reasons why retrofitting a non- modulating system to one that modulates will benefit the building owner and its occupants. Some of these reasons include:

1.Reduced indoor temperature and humidity swings

2.Reduced power consumption and operating costs

3.Reduced cyclic losses

4.Qualification for special utility rebates

Applications that have excess cooling capacity and are single zone, constant or variable air-flow are certainly in the scope of retrofit opportunities. Units that employ

Image 7
Contents Introduction SafetyAssembly Line Procedures Service ProceduresSafety Icon Explanation Safety InstructionsBurn Hazard Safety StatementsElectrical Shock Hazard Pressurized System HazardApplication Considerations 410A 22 & R-407CNomenclature Digital Compressor Operation How it WorksPiping Sound CharacteristicsSolenoid Valve and Coil Pressure FluctuationsOil Type and Oil Removal Scroll Temperature ProtectionPower Factor Crankcase HeatersDigital Compressor Retrofit Applications Modulation ControlApplication Tests Oil Level VerificationCompressor Selection & Change-Out Retrofit Applications To AvoidPerformance Modeling System ModificationsAssembly Line Procedures To 15 Ton Modulation Valve Replacement Procedure Service ProceduresModulation Troubleshooting To 7.5 Ton Modulation Valve Replacement ProcedureForm No Copeland Scroll Compressor Functional Check50% Loaded 80% Loaded To 15 Ton Digital Scroll Cross Sectional View ZPD34-54K5 22, R-407C, R-410A Operating EnvelopeCompressor Capacity Graph Discharge Thermistors Second Operating Cycle AE4-1395To 7.5 Ton Tandem Yes Part Refrigerant Charge Limits Model PoundsFoot-Pounds Inch-Pounds TBD