Emerson 20/20 service manual Motor Current, Remote Capacity

Page 68

Section 13 • Instruments Calibration

devices are predefined and if one is selected, then all the setpoints will be set for the operator.

Custom Device:

This option allows the operator to choose the mini- mum and maximum value of the instrument being used.

Offset:

Once the two point calibration is completed, it is not uncommon for there to be a small error. By entering the value of the error from the calibrated value and the actual value into the adjustment entry box, that error will be added/subtracted from the total offset. The offset is applied to the calibrated value which should correct the error.

Range:

This option is available when the custom device op- tion is chosen. Here the operator defines the signal type and range transmitted by the instrument. The operator can choose from several predefined ranges in the drop-down box or enter a value.

Motor Current

The Vission 20/20 has two options for measuring motor current. A 4-20mA signal transmitted from an external device or a 0-5Amp AC current Transformer. The type of device being used is selected in the configuration screen.

The motor current tab has the ability to calibrate both measurement options through the 4-20mA scale and current transformer ratio sections. However, the device type that is selected in the configuration screen will be the only section that will be available to the operator.

The calibration differs from all other calibration proce- dures in that the motor current must be calibrated while the compressor is running at close to full load amps as possible. In addition, the operator will need to enter a value into the “Enter Desired Value” entry box that is equal to the measured value in amps by a calibrating measurement device. After entering the measured val- ue, the displayed motor current may still be off slightly. In this case reenter the desired value and the displayed value should get progressively closer.

4-20mA Scale:

4mA:

Not editable by the operator. Defines the minimum value in amps represented by a 4ma inputs.

20mA:

Defines the maximum value in amps repre- sented by a 20ma inputs.

Enter Desired Value:

The operator enters the correct current value. Each entry will recalculate the point-slope calcu- lations of the current calibration.

Total Error:

Not editable by the operator. Displays the to- tal error offset of entries from the “Enter Desired Value” setpoint.

Current Transformer Ratio:

Primary

Defines the upper value of the current transformer.

Secondary:

Not editable by the operator. Defines the minimum value of the current transformer.

Enter Desired Value:

The operator enters the value of the cor- rect current value. Each entry will recalculate the point-slope calculations of the current calibration.

Total Error:

Not editable by the operator. Displays the to- tal error offset of entries from the “Enter Desired Value” setpoint

Remote Capacity

The remote capacity input allows a system controller such as the PLC to control the capacity position during direct I/O control.

Control Input:

This drop-down box is not used at this time. Scale:

Defines the minimum and maximum Capacity posi- tion between 0% & 100% for the 4-20ma input.

Offset:

Used to correct any error in the capacity position. By entering a value into the Adjustment entry box, that value will be added to the total offset displayed in the “total offset” entry box.

13 – 2

Vission 20/20 • Operation and Service Manual •Vilter/Emerson • 35391SC 1.8.5153

Image 68
Contents Vission 20/20 micro-controller Page Table of Contents TOC Digital I/O Board Layout Top Status BarCompressor Sequencing Event List Data Backup List of Tables and Figures END of TOC How to Use This Manual Operational Flow Charts Requirements to Start CompressorCritical Compressor Run Logic at Compressor Start Compressor Amperage Load LimitingOperational Flow Charts 2 Voltage Source Installation RecommendationsProper Wiring Sizing Mixing Voltages DC signalsGrounding Wiring Methods Correct Transformer Wiring MethodBest Practices Hardware Architecture OverviewDigital Input/Output I/O Digital I/O 1 Board Description TypeAnalog Inputs Refer to -2. Analog Inputs Motor CurrentDigital I/O 2 Analog Inputs 1Analog Outputs Digital & Analog I/O Boards LayoutAnalog Inputs 2 Digital I/O Board LayoutDigital Output Boards Digital Output Board LayoutDigital Input Boards Digital Input Board LayoutDigital In-Out Boards Digital Input-Output Board LayoutAnalog Input Boards Analog Input Board LayoutChannel Signal Analog Input Jumper TablesJP-13 JP-14 JP-15 JP-31 Analog Output Boards Analog Output Board LayoutMain Screen Main ScreenTop Status Bar Parameter Bar Unit Start Pop-Up Window Bottom Status Bar Splash Screen Menu Screen Navigation ButtonsMenu Screen Compressor Control Pulse Proportional ControlAuto-Cycle Proportional Band & SetpointVariable Frequency Drive VFD VFD One-Step Control MethodPumpdown Control Pulldown Control Control Mode Volume Slide Position OffsetStop Load and Force Unload Capacity Slide Triggered OutputsLiquid Injection Load AnticipatingOil Control Compressor Control Alarms and Trips Alarms and Trips SetpointsAlarms and Trips Safety Failure Messages Compressor InhibitsFalse Start Timers Timer SetpointsOil Separator Level #2 Safety Trip Delay Timers Blank Compressor Scheduling Scheduling SetpointCompressor Scheduling Compressor Sequencing Pressure Control SetpointsCFM Equipment List 10 4 / Blank Condenser Control Condenser Control SetpointStep Control VFD Settings Step Control Screen11 4 / Blank Service Options Digital OutputsAnalog Outputs Pressure and Temperature Inputs Instruments CalibrationMotor Current Remote CapacityAnalog Inputs 13 4 / Blank Slide Calibration Capacity Slide Valve PotentiometerSlide Valve Actuator Calibration for Optical Style Motors Volume Slide Valve PotentiometerSlide Valve Operation Photochopper Command Shaft Rotation Command Shaft Rotation Required By ActuatorSlide Valve Troubleshooting Guide Slide Valve Troubleshooting Guide 1Slide Valve Troubleshooting Guide 2 Slide Valve Actuator Troubleshooting Guide Blink Code LED Blink Codes and Troubleshooting Guide 1LED Blink Codes and Troubleshooting Guide 2 Pleted. The actuator will not move while this error codeTrend Chart Chart OperationTrend Data Storage Setup Trend Setup Screen15 4 / Blank Event List Event list Columns16 2 / Blank Input / Output Input/Output Screen17 2 / Blank Auxiliary Input / Output Digital InputsDigital Outputs Control 18 4 / Blank Time & Date ConfigurationUnits Anti-Recycle CommunicationsTouchscreen Restart On Power Failure Compressor SequencingLanguage Model & RefrigerantCompressor Control Optional Function SelectionCondenser Control Oil PumpOil Cooling Motor Current DeviceDigital Inputs Analog Inputs Analog Outputs Configuration 19 10 / Blank Data Backup Save / LoadData Backup Factory Reset Migrate20 4 / Blank Maintenance ChecklistChart LogUser Access ApplyLogin Manage AccountsSecurity Access Levels Screen Security Levels22 4 / Blank Screen Features Help ScreenVersion Pop-Up Screen Twin Screw Control Twin Screw Control ScreenOperation Cool Compression Control Cool Compression Control ScreenControl Functions Cool Compression Control Functions ScreenAuto Load Timer Operational Differences from Single ScrewCool Compression Control

20/20 specifications

Emerson 20/20 is an advanced platform designed for real-time data analytics, visualization, and operational optimization in industrial settings. This robust solution aims to empower organizations by providing actionable insights derived from their operational data, enabling enhanced decision-making and improved efficiency.

One of the standout features of Emerson 20/20 is its ability to integrate seamlessly with various sources of data, whether structured or unstructured. It consolidates information from different systems, such as historians, control systems, and ERP software, allowing users to gain a comprehensive view of their operations. This integration capability is crucial for businesses looking to maximize their data utilization without being confined to a single data source.

The platform employs powerful analytics tools that utilize machine learning and artificial intelligence technologies. These tools are designed to automatically identify patterns, anomalies, and trends in real-time. By leveraging predictive analytics, Emerson 20/20 helps organizations forecast potential issues before they escalate, allowing for proactive maintenance and minimizing downtime.

Emerson 20/20 also features user-friendly visualization dashboards, which provide customizable views tailored to individual user roles. This means that whether you are a plant manager, a process engineer, or an executive, you can access relevant data that speaks directly to your needs. These dashboards facilitate easier understanding of complex data sets, promoting informed decision-making across the organization.

One notable characteristic of Emerson 20/20 is its adaptability and scalability. Businesses of all sizes can implement the platform and scale its features according to their needs. This flexibility ensures that both small operations and large enterprises can derive value from the solution, making it an attractive option for various industries.

Additionally, the platform is designed with cybersecurity in mind, ensuring that data integrity and confidentiality are maintained. This aspect is increasingly important as industries become more interconnected and target more sophisticated cyber threats.

In summary, Emerson 20/20 stands out as a powerful tool for organizations seeking to harness their operational data effectively. With its advanced analytics capabilities, seamless integration, customizable visualization, and scalable design, it offers a comprehensive solution to optimize industrial performance and support data-driven decision-making. As businesses continue to navigate the complexities of modern operations, Emerson 20/20 provides the insights necessary to stay competitive and responsive to changing market demands.