Page 8

WARNING

Any conversion of a natural gas unit to propane gas must be done by qualified personnel using a conversion kit available from the manufacturer, following the instructions in the conversion kit. If done improperly, overfiring of the burners and improper burner operation can result. This can create carbon monoxide which could cause asphyxiation.

Check all connections for leaks when piping is completed, using a soapy solution. Some soaps used for leak detection are corrosive to certain metals. Carefully rinse piping thoroughly after completing leak detection.

Electrical Wiring

All wiring should be done in accordance with the National Electrical Code, ANSI/NFPA No. 70 (latest edition); Canadian Electrical Code Part 1, CSA C22.1 (latest edition); or local codes where they prevail. Use wiring with a temperature limitation of 75°C minimum. Run the electric power supply through a fused disconnect switch to the connection box of the unit and connect as shown in the wiring diagram located on the inside of the control access panel.

Power supply to the unit must comply with all applicable codes and the National Electical Code (NEC) or Canadian Electrical Code (CEC). A fused disconnect switch should be field provided for the unit. The switch must be separate from all other circuits.

If any of the wire supplied with the unit must be replaced, replacement wire must be of the type shown on the wiring diagram. Electrical wiring must be sized to carry minimum circuit ampacity marked on the unit. Use copper conductors only. Each unit must be wired with a separate branch circuit and be properly fused.

Thermostat

The room thermostat should be located on an inside wall where it will not be subject to drafts, sun exposure, or heat from electrical fixtures or appliances. Follow the manufacturer’s instructions enclosed with thermostat for general installation procedure. Color-coded insulated wires (#18 AWG) should be used to connect thermostat to unit.

CAUTION

When connecting electrical power and control wiring to the unit, waterproof type connectors must be used so that water or moisture cannot be drawn into the unit during normal operation.

Four wires are required for cooling. The heat anticipator setting is 0.7 amp.

Compressor

Units are shipped with compressor mountings factory- adjusted and ready for operation. Caution: Do not loosen compressor mounting bolts.

Page 8

Issue 1008

506488-01

Image 8
Contents 4PGE/SG13,15 Series Inspection SafetyInstallation Using Accessory Lift Kit LocationRoof Curb Installation Roof Curb Assembly ClearancesService Access Minimum Clearance RequirementsInstalling Vent Hood Carbon Monoxide Poisoning HazardVent Hood Existing Venting SystemsCondensate Drain FiltersRemoving Bottom Duct Covers DuctworkGas and Electrical Access Fire or Explosion HazardMinimum Required Surface Area For Disposable Filters LPG/Propane Units, Tanks, and PipingCompressor Single Phase Three Phase Typical Wiring ConnectionsSTART-UP Pre-Start Check ListTo Light Burners To Shut Down BurnersBlower Delay Cooling OperationCooling Sequence of Operation System PerformanceAdjusting Airflow Variable Speed Motor Equipped Units Only Heating SystemHeating Sequence of Operation Circulating Air BlowerMaintenance Electrical SHOCK, Fire Or Explosion Hazard Fault Codes BurnersTypical Flame Appearance Outdoor CoilDiagram PSC Motor Connection Single Phase Connection Diagram Single Phase Variable Speed Motor