Allied Air Enterprises 4PGE manual Safety, Installation, Inspection

Page 2

SAFETY

The following is a list of safety rules and precautions that must be followed when installing this furnace.

1.Use only with the type of gas approved for this furnace. Refer to the furnace rating plate.

2.Install this furnace only in a location and position as specified in the Location section on page 3 of these instructions.

3.Adequate clearance must be provided around the vent hood as specified in the Clearances section on page 4 of these instructions.

4.Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections, as specified in Gas Supply and Piping beginning on page 6 of these instructions.

5.Always install furnace to operate within the furnace’s intended temperature-rise range with a duct system which has an external static pressure within the allowable range, as specified in Temperature Rise on page 11 of these instructions. See furnace rating plate.

6.The furnace is not recommended for use for temporary heating of buildings or structures under construction unless certain installation and operating conditions are adhered to, as specified in the Location section on page 3 of these instructions.

WARNING

In the State of Massachusetts:

This product must be installed by a licensed Plumber or Gas Fitter. When flexible connectors are used, the maximum length shall not exceed 36". When lever- type gas shutoffs are used, they shall be T-handle type.

INSTALLATION

These instructions must be hung on or near the furnace in a conspicuous place.

These units are single package air conditioners with gas heat designed for outdoor installation on a rooftop or a slab.

The units are completely assembled. All piping, refrigerant charge, and electrical wiring are factory installed and tested. The units require only electric power, gas piping, condensate drain, and duct connections, plus assembly of the heating vent hood at the point of installation.

If components are to be added to a unit to meet local codes, they are to be installed at the dealer’s and/or customer’s expense.

The size of unit for the proposed installation should be based on heat loss/heat gain calculation made according to the methods of Air Conditioning Contractors of America (ACCA).

These installation instructions are intended as a general guide only, for use by an experienced, qualified contractor.

These units are listed by UL:

For use as a forced air furnace with cooling unit.

For outdoor installation only.

For installation on combustible material.

For use with natural gas or propane gas. (Conversion kit required for propane gas application.)

These units are not suitable for use with conventional venting systems.

IMPORTANT: The 15 SEER models have been designed and manufactured to meet ENERGY STAR criteria for energy efficiency. However, proper refrigerant charge and proper air flow are critical to achieve rated capacity and efficiency. Installation of this product should follow the manufacturer’s refrigerant charging and air flow instructions. Failure to confirm proper charge and airflow may reduce energy efficiency and shorten equipment life.

Inspection

As soon as the unit is received, it should be inspected for possible damage during transit. If damage is evident, the extent of the damage should be noted on the carrier’s freight bill. A separate request for inspection by the carrier’s agent should be made in writing.

Page 2

Issue 1008

506488-01

Image 2
Contents 4PGE/SG13,15 Series Inspection SafetyInstallation Using Accessory Lift Kit LocationService Access Roof Curb InstallationRoof Curb Assembly Clearances Minimum Clearance RequirementsVent Hood Installing Vent HoodCarbon Monoxide Poisoning Hazard Existing Venting SystemsRemoving Bottom Duct Covers Condensate DrainFilters DuctworkMinimum Required Surface Area For Disposable Filters Gas and Electrical AccessFire or Explosion Hazard LPG/Propane Units, Tanks, and PipingCompressor Single Phase Three Phase Typical Wiring ConnectionsTo Light Burners START-UPPre-Start Check List To Shut Down BurnersCooling Sequence of Operation Blower Delay CoolingOperation System PerformanceHeating Sequence of Operation Adjusting Airflow Variable Speed Motor Equipped Units OnlyHeating System Circulating Air BlowerMaintenance Electrical SHOCK, Fire Or Explosion Hazard Typical Flame Appearance Fault CodesBurners Outdoor CoilDiagram PSC Motor Connection Single Phase Connection Diagram Single Phase Variable Speed Motor