Burners
Light the burners and allow to operate for a few minutes to establish normal burning conditions. Observe the burner flames. Compare this observation to Figure 10 on page 14 to determine if proper flame adjustment is present. Flame should be predominantly blue in color and strong in appearance. Check that all burners are lit, and that the flame does not impinge on the sides of the heat exchanger.
Distorted flame or yellow tipping of the natural gas burner flame, or long yellow tips on propane, may be caused by lint accumulation or dirt inside the burner or burner ports, at the air inlet between the burner and manifold pipe, or obstructions over the burner orifice.
Use a soft brush or vacuum to clean the affected areas.
Typical Flame Appearance
Heat
Exchanger
Burner
Gas | Burner |
Manifold | Flame |
| (Blue Only) |
Figure 10
Outdoor Coil
Dirt and debris should not be allowed to accumulate on the outdoor coil surface or other parts in the air circuit. Cleaning should be as often as necessary to keep coil clean. Use a brush, vacuum cleaner attachment, or other suitable means. If water is used to clean the coil, be sure the power to unit is shut off prior to cleaning. Care should be used when cleaning the coil so that the coil fins are not damaged.
Do not permit the hot condenser air discharge to be obstructed by overhanging structures or shrubs.
Vent Outlet
Visually inspect vent outlet periodically to make sure there is no buildup of soot and dirt. If necessary, clean to maintain adequate opening to discharge flue products.
CONTROL SYSTEM DIAGNOSTICS
Fault Codes
LED | Flashing | Fault | |
Status | Rate | Description | |
|
|
| |
Slow Flash | One flash | Normal operation: | |
per second | No call for heat | ||
| |||
Fast Flash | Two flashes | Normal operation: | |
per second | Call for heat | ||
| |||
| Two flashes | System lockout: | |
2 Flash | in second with | Failed to detect | |
| or sustain flame | ||
| Three flashes in | Pressure switch | |
3 Flash | 1.5 seconds with | ||
open or closed | |||
| |||
|
| ||
| Four flashes in | High limit or | |
4 Flash | 2 seconds with | rollout switch | |
| open | ||
| Five flashes in | Flame sensed | |
5 Flash | 2.5 seconds with | and gas valve | |
| not energized | ||
|
| Internal failure: | |
Steady | |||
|
| failure; |
Table 5