Carrier NP034-074 specifications Initial Check, General, HEATING, Units Without Economizer

Page 41

Fig. 32 Ð Condenser-Fan Adjustment

Initial Check

IMPORTANT: Do not attempt to start unit, even mo- mentarily, until all items on the Start-Up Checklist and the following steps have been completed.

1.Verify unit has been installed per the Installation section of this literature.

2.Certify that all auxiliary components (sensors, controls, etc.) have been installed and wired to the control boxes per these instructions, the Controls and Troubleshooting literature (DK,DY,NB,NP units only), and the unit wiring label diagrams.

3.Verify that pressure hoses (static, duct, etc.) are properly attached, routed, and free from pinches or crimps that may affect proper control operation.

4.Set any control con®gurations that are required (®eld- installed accessories, etc.). The unit is factory con®gured for all appropriate factory-installed options with the ap- plicable controls programmed to the default values. See unit Controls and Troubleshooting literature for appli- cable con®guration values.

5.Enter unit set points (if applicable). The unit is shipped with the set point default values shown in the Controls and Troubleshooting literature (as applicable). If a dif- ferent set point is required, change per the example shown under Set Point Function section in appropriate unit Con- trols and Troubleshooting literature.

6.Con®gure schedule subfunctions (if applicable): occu- pied, unoccupied, and holiday periods. See Schedule Func- tion section in Controls and Troubleshooting literature for details on setting periods.

7.Verify that control time periods programmed meet cur- rent requirements.

8.Check all electrical connections to be sure they are tight.

START-UP

General

1.Put the ON/OFF switch in the ON position. Close the con- trol circuit breaker (CCB), which will energize the con- trol circuit and the crankcase heaters.

2.For PIC and VAV units, refer to Controls and Trouble- shooting literature for quick test details.

3.Complete Pre-Start-Up section items and Start-Up Check- list.

Operating Sequences Ð Base unit operating se- quences are presented below. Refer to unit Controls and Trouble- shooting literature for details on VAV and PIC controls op- eration.

COOLING, UNITS WITHOUT ECONOMIZER Ð Unit power on, system selector switch set at COOL or AUTO. position, fan switch set at AUTO. position.

On a call for cooling, Y1 on the thermostat subbase closes, energizing compressor no. 1 as ®rst stage of cooling. (Com- pressor no. 1 is always the larger of the 2 unit compressors.) If cooling load cannot be satis®ed with only ®rst-stage cool- ing, Y2 on the thermostat will close, energizing compressor no. 2.

Condenser fans are energized with compressor no. 1. The no. 1 fan runs continuously while the unit is on mechanical cooling; the no. 2 fan is cycled on and off in response to outdoor ambient temperature for head pressure control. Check cooling effects at a setting below room temperature. Reset thermostat at a setting above room temperature. Compres- sors will shut off.

HEATING, UNITS WITHOUT ECONOMIZER

48 Series Low-Heat Units Ð Unit power on, thermostat sys- tem switch set at HEAT or AUTO. position, and fan switch set at AUTO. position.

First-stage thermostat (W1) calls for heat. Time-delay re- lay (built into constant volume control board), controlling evaporator fan, begins timer sequence (55 ± 10-second de- lay). Induced-draft contactor closes and induced-draft motor starts.

Centrifugal switch closes. Pilot valve opens, allowing gas to ¯ow to ®rst-stage pilot. Spark ignitor ignites pilot ¯ame. Sensor detects ¯ame, energizes main gas valve coil and main gas valve opens. Gas ¯ows to main burners and ®rst-stage burners ignite. Spark ignitor shuts off and pilot remains on.

The spark ignitor will continue to spark for 90 seconds until pilot ¯ame is sensed. If the pilot fails to ignite or the sensor fails to detect ¯ame, the pilot valve closes and the spark ignitor shuts off for 300 seconds (5 minutes). During this time the induced draft motor remains on to purge any unburnt gas from the combustion tubes. This ignition se- quence will repeat inde®nitely.

When time-delay sequence is complete, time-delay relay closes and evaporator-fan motor starts.

When additional heat is needed on 034,044 units, W2 is energized and a second coil in the main gas valve is ener- gized. This brings on an additional stage of heat. When second- stage thermostat is satis®ed, the second-stage gas valve coil is deenergized.

When additional heat is needed on 054-074 units, W2 is energized, and pilot valve number 2 opens. Gas ¯ows to second- stage pilot, and spark ignitor ignites pilot ¯ame. Sensor de- tects ¯ame, energizes the main gas valve coil, and main gas valve number 2 opens. Gas ¯ows to main burners and second- stage burners ignite. Second-stage spark ignitor shuts off. When second-stage thermostat is satis®ed, the second-stage gas valve coil is deenergized.

41

Image 41
Contents Installation, Start-Up Service Instructions General ContentsRigging Label Ð Physical Data 034, 044 Units Ð Physical Data 054-074 Units Weight Distribution and Center of Gravity Operating Weights of Options and AccessoriesFt-in Ð Roof Curb 034, 044 UnitsDeg Ð Roof Curb 054-074 Units054,064 270 105¤8 074 255 101¤16 Ð Condenser Section Roof Curb 054-074 Units OnlyOutdoor-Air Inlet Adjustments Install Outdoor HoodsEconomizer Settings Unit Sizes 034Unit Size Weight Ð Base Unit Dimensional Drawing 50DJ,DK,NP034,044 Units 8700 3946 5969 19-7 6717 Weight Ft-in Ð Base Unit Dimensional Drawing 50DJ,DK,NP054-074 UnitsDrain Location Selection AT 50% RH Approx DegField Electrical Connections Field Wire RoutingField Power Wiring Connections Electrical Data, 034 Units 11.0 81.2 100 90.8 110 10.0 15.2 96.4 125 15.0 22.0 103.293.8 110 10.0 15.2 99.4 125 15.0 22.0 106.2 10.0 14.0 84.2 11065.8 73.6 10.0 12.2 78.0 100 15.0 18.0 83.875.6 10.0 12.2 80.0 100 15.0 18.0 85.8 67.8Electrical Data, 044 Units 11.0 96.9 125 106.5 125 10.0 15.2 112.1 15.0 22.0 118.9 150109.5 125 10.0 15.2 115.1 15.0 22.0 121.9 150 10.0 14.0 99.9 12576.3 100 84.1 110 10.0 12.2 88.5 15.0 18.0 94.386.1 110 10.0 12.2 90.5 15.0 18.0 96.3 10.0 11.0 78.3 100Electrical Data, 054 Units 15.0 21.0 129.6 175 10.0 15.2 144.8 175 15.0 22.0 151.6 200 20.0 28.0 157.610.0 15.2 150.8 200 15.0 22.0 157.6 20.0 28.0 163.6 20.0 27.0 135.6 17515.0 17.0 104.3 125 10.0 12.2 116.5 150 15.0 18.0 122.3 20.0 22.0 126.310.0 12.2 121.5 150 15.0 18.0 127.3 20.0 22.0 131.3 20.0 22.0 109.3 125Electrical Data, 064 Units 15.0 21.0 145.6 175 10.0 15.2 160.8 200 15.0 22.0 167.6 20.0 28.0 173.610.0 15.2 166.8 200 15.0 22.0 173.6 20.0 28.0 179.6 225 20.0 27.0 151.6 20015.0 17.0 114.6 150 10.0 12.2 126.8 150 15.0 18.0 132.6 20.0 22.0 136.6 17510.0 12.2 131.8 150 15.0 18.0 137.6 175 20.0 22.0 141.6 20.0 22.0 119.6 150Electrical Data, 074 Units 15.0 21.0 166.8 225 10.0 15.2 182.0 225 15.0 22.0 188.8 250 20.0 28.0 194.810.0 15.2 188.0 250 15.0 22.0 194.8 20.0 28.0 200.8 20.0 27.0 172.8 22515.0 17.0 133.8 175 10.0 12.2 146.0 175 15.0 18.0 151.8 200 20.0 22.0 155.810.0 12.2 151.0 200 15.0 18.0 156.8 20.0 22.0 160.8 20.0 22.0 138.8 175Field Control Thermostat Wiring Field Wiring for Building Pressurization and Smoke Purge Gas Piping Details Installing Flue/Inlet Hoods 48 Series Units OnlyFlue Hood PRE-START-UP Ð Field-Supplied Evaporator-Fan Pulley Data, 034,044 Units Gas Manifold Pressure 48 Series Units OnlyAir Quantity Limits cfm Ð Field-Supplied Evaporator-Fan Pulley Data, 054-074 UnitsHEATING, Units Without Economizer Initial CheckGeneral Compressors ServiceEVAPORATOR-FAN MOTORS, PULLEYS, and Belts Liquid Service VALVES, Filter DRIERS, and Sight GlassesPower Exhaust MOTORS, PULLEYS, and Belts Burner Section Detail 48 Series Units Only Lubrication Modulating Power Exhaust Damper MotorCondenser FAN Adjustment AdjustmentsBelt Installation and Tensioning Pulley Alignment Charging Chart, 044 Units System One Condenser Fan Running Charging Chart, 064 Units System All Condenser Fans Running Main Burner Removal 48 Series Units Only Auxiliary Switch Stroke AdjustmentCompressor Protection Protective DevicesGas Heat 48 Series Units Only Electric Heat 50 Series Units OnlyEconomizer Motor Checkout Economizer Control Board Checkout TestDetailed Check Control Board Component Arrangement Page Compressor Lockout Connections ACC Gas Heat Sections 48DJ,NP034,044 Units Gas Heat Sections 48DJ,NP054-074 Units Gas Heat DK034,044 Units Gas Heat DK054-074 Units Typical Wiring Schematic 48/50DJ,50DW Units 054-074 Shown Typical Wiring Schematic 48/50DJ,50DW Units 054-074 Shown Typical Wiring Schematic 48/50DK,50DY Units 054-074 Shown Typical Wiring Schematic 48/50DK,50DY Units 054-074 Shown Page Page Page Page Packaged Service Training Page RETURN-AIR Temperature OUTDOOR-AIR TemperatureModel no Serial no Date Technician Supply Voltage L1-L2

NP034-074 specifications

The Carrier NP034-074 is an advanced rooftop unit designed for commercial heating, ventilation, and air conditioning (HVAC) applications. This unit is part of Carrier’s extensive range of rooftop units that are known for their energy efficiency, reliability, and innovative features. The NP034-074 series is particularly recognized for its robust performance in diverse environmental conditions, making it ideal for a variety of commercial building types.

One of the standout features of the NP034-074 is its high-efficiency compressor. Equipped with a scroll compressor, the unit offers enhanced performance and quieter operation compared to traditional reciprocating compressors. This design not only improves energy efficiency but also reduces operating costs over time. The unit is designed to meet or exceed the latest efficiency standards, ensuring that businesses can enjoy optimal indoor comfort while keeping energy consumption low.

The NP034-074 also integrates advanced control technologies that provide users with greater flexibility and ease of operation. The intuitive control system allows for precise temperature management and can be easily integrated with building automation systems. This enables users to monitor and adjust settings remotely, ensuring consistent and efficient climate control throughout the facility.

Another key characteristic of the NP034-074 is its robust construction. Built to withstand various weather conditions, the unit features a galvanized steel cabinet with a powder-coated finish for corrosion resistance. Its design also facilitates easy access for maintenance and service, which minimizes downtime and operational interruptions.

In terms of air distribution, the NP034-074 incorporates a powerful blower system that ensures even and effective airflow throughout the space. This design improves indoor air quality by enhancing ventilation while maintaining comfort levels. Additionally, the unit can be customized with options such as economizers and variable speed fans to optimize performance based on specific building needs.

The NP034-074 is a versatile and reliable choice for businesses looking to enhance their HVAC systems. With its combination of energy efficiency, advanced technology, and robust construction, this rooftop unit stands out as a top choice for commercial climate control solutions.