Carrier NP034-074 specifications Field Wire Routing, Field Electrical Connections

Page 17

NOTES:

1.Switches shown in high enthalpy state. Terminals 2 and 3 close on enthalpy decrease.

2.When standard economizer is used with accessory differential en- thalpy sensor, set enthalpy control to ``D'' setting.

Fig. 14 Ð Wiring Connections for Solid-State

Enthalpy Sensor (HH57AC077)

Fig. 15 Ð Mixed-Air Thermistor and Economizer

Position Setting Adjustments

(Top of Economizer Motor)

Field Wire Routing

UNIT SIZES 034 AND 044 Ð Field wiring can be brought into the unit through the basepan and roof curb or through the corner post in the side of the unit next to the control box.

A 3-1/2 in. NPT coupling for ®eld power and a 3/4-in. NPT coupling for 24 v control wiring are provided in the basepan. There are two 4-5/8 in. knockouts in the corner post for ®eld power wiring.

If ®eld power wiring is brought through the roof curb, route wiring out through one of the 4-5/8 in. knockouts to the ®eld- supplied disconnect and then back into the unit through the other knockout. See Fig. 16 for recommended disconnect location.

If power wiring is brought through the side of the unit, route wiring from ®eld-supplied disconnect through top 4-5/8 in. knockouts into unit.

If control wiring is to be brought in through the side of the unit, a 7/8-in. diameter hole must be drilled in the corner post next to the control box.

UNIT SIZES 054-074 Ð Field wiring is brought into the unit through the bottom of the control box. Wiring can be brought through the roof curb through ®eld-supplied water- tight connections. See Fig. 17.

A 4-5/32 in. hole for ®eld power wiring and a 7/8-in. hole for 24 v control wiring are provided in the bottom of the control box. Field-supplied couplings must be used when rout- ing wiring into the control box.

See Fig. 17 for recommended disconnect location.

Field Electrical Connections

IMPORTANT: The 48/50DK,DY,NB,NP units gener- ate, use, and can radiate radio frequency energy. If units are not installed and used in accordance with these instructions, they may cause radio interference. They have been tested and found to comply with limits of a Class A computing device as de®ned by FCC (Federal Communications Commission) regulations, Subpart J of Part 15, which are designed to provide reasonable protection against such interference when operated in a commercial environment.

Use care when drilling into corner post to avoid damage to con- denser coil.

Fig. 16 Ð Disconnect Location, 034 and 044 Units

(50 Series Vertical Discharge Unit Shown)

17

Image 17
Contents Installation, Start-Up Service Instructions General ContentsRigging Label Ð Physical Data 034, 044 Units Ð Physical Data 054-074 Units Weight Distribution and Center of Gravity Operating Weights of Options and AccessoriesFt-in Ð Roof Curb 034, 044 UnitsDeg Ð Roof Curb 054-074 Units054,064 270 105¤8 074 255 101¤16 Ð Condenser Section Roof Curb 054-074 Units OnlyOutdoor-Air Inlet Adjustments Install Outdoor HoodsEconomizer Settings Unit Sizes 034Unit Size Weight Ð Base Unit Dimensional Drawing 50DJ,DK,NP034,044 Units 8700 3946 5969 19-7 6717 Weight Ft-in Ð Base Unit Dimensional Drawing 50DJ,DK,NP054-074 UnitsDrain Location Selection AT 50% RH Approx DegField Electrical Connections Field Wire RoutingField Power Wiring Connections Electrical Data, 034 Units 11.0 81.2 100 90.8 110 10.0 15.2 96.4 125 15.0 22.0 103.293.8 110 10.0 15.2 99.4 125 15.0 22.0 106.2 10.0 14.0 84.2 11065.8 73.6 10.0 12.2 78.0 100 15.0 18.0 83.875.6 10.0 12.2 80.0 100 15.0 18.0 85.8 67.8Electrical Data, 044 Units 11.0 96.9 125 106.5 125 10.0 15.2 112.1 15.0 22.0 118.9 150109.5 125 10.0 15.2 115.1 15.0 22.0 121.9 150 10.0 14.0 99.9 12576.3 100 84.1 110 10.0 12.2 88.5 15.0 18.0 94.386.1 110 10.0 12.2 90.5 15.0 18.0 96.3 10.0 11.0 78.3 100Electrical Data, 054 Units 15.0 21.0 129.6 175 10.0 15.2 144.8 175 15.0 22.0 151.6 200 20.0 28.0 157.610.0 15.2 150.8 200 15.0 22.0 157.6 20.0 28.0 163.6 20.0 27.0 135.6 17515.0 17.0 104.3 125 10.0 12.2 116.5 150 15.0 18.0 122.3 20.0 22.0 126.310.0 12.2 121.5 150 15.0 18.0 127.3 20.0 22.0 131.3 20.0 22.0 109.3 125Electrical Data, 064 Units 15.0 21.0 145.6 175 10.0 15.2 160.8 200 15.0 22.0 167.6 20.0 28.0 173.610.0 15.2 166.8 200 15.0 22.0 173.6 20.0 28.0 179.6 225 20.0 27.0 151.6 20015.0 17.0 114.6 150 10.0 12.2 126.8 150 15.0 18.0 132.6 20.0 22.0 136.6 17510.0 12.2 131.8 150 15.0 18.0 137.6 175 20.0 22.0 141.6 20.0 22.0 119.6 150Electrical Data, 074 Units 15.0 21.0 166.8 225 10.0 15.2 182.0 225 15.0 22.0 188.8 250 20.0 28.0 194.810.0 15.2 188.0 250 15.0 22.0 194.8 20.0 28.0 200.8 20.0 27.0 172.8 22515.0 17.0 133.8 175 10.0 12.2 146.0 175 15.0 18.0 151.8 200 20.0 22.0 155.810.0 12.2 151.0 200 15.0 18.0 156.8 20.0 22.0 160.8 20.0 22.0 138.8 175Field Control Thermostat Wiring Field Wiring for Building Pressurization and Smoke Purge Gas Piping Details Installing Flue/Inlet Hoods 48 Series Units OnlyFlue Hood PRE-START-UP Ð Field-Supplied Evaporator-Fan Pulley Data, 034,044 Units Gas Manifold Pressure 48 Series Units OnlyAir Quantity Limits cfm Ð Field-Supplied Evaporator-Fan Pulley Data, 054-074 UnitsHEATING, Units Without Economizer Initial CheckGeneral Compressors ServiceEVAPORATOR-FAN MOTORS, PULLEYS, and Belts Liquid Service VALVES, Filter DRIERS, and Sight GlassesPower Exhaust MOTORS, PULLEYS, and Belts Burner Section Detail 48 Series Units Only Lubrication Modulating Power Exhaust Damper MotorCondenser FAN Adjustment AdjustmentsBelt Installation and Tensioning Pulley Alignment Charging Chart, 044 Units System One Condenser Fan Running Charging Chart, 064 Units System All Condenser Fans Running Main Burner Removal 48 Series Units Only Auxiliary Switch Stroke AdjustmentCompressor Protection Protective DevicesGas Heat 48 Series Units Only Electric Heat 50 Series Units OnlyEconomizer Motor Checkout Economizer Control Board Checkout TestDetailed Check Control Board Component Arrangement Page Compressor Lockout Connections ACC Gas Heat Sections 48DJ,NP034,044 Units Gas Heat Sections 48DJ,NP054-074 Units Gas Heat DK034,044 Units Gas Heat DK054-074 Units Typical Wiring Schematic 48/50DJ,50DW Units 054-074 Shown Typical Wiring Schematic 48/50DJ,50DW Units 054-074 Shown Typical Wiring Schematic 48/50DK,50DY Units 054-074 Shown Typical Wiring Schematic 48/50DK,50DY Units 054-074 Shown Page Page Page Page Packaged Service Training Page RETURN-AIR Temperature OUTDOOR-AIR TemperatureModel no Serial no Date Technician Supply Voltage L1-L2

NP034-074 specifications

The Carrier NP034-074 is an advanced rooftop unit designed for commercial heating, ventilation, and air conditioning (HVAC) applications. This unit is part of Carrier’s extensive range of rooftop units that are known for their energy efficiency, reliability, and innovative features. The NP034-074 series is particularly recognized for its robust performance in diverse environmental conditions, making it ideal for a variety of commercial building types.

One of the standout features of the NP034-074 is its high-efficiency compressor. Equipped with a scroll compressor, the unit offers enhanced performance and quieter operation compared to traditional reciprocating compressors. This design not only improves energy efficiency but also reduces operating costs over time. The unit is designed to meet or exceed the latest efficiency standards, ensuring that businesses can enjoy optimal indoor comfort while keeping energy consumption low.

The NP034-074 also integrates advanced control technologies that provide users with greater flexibility and ease of operation. The intuitive control system allows for precise temperature management and can be easily integrated with building automation systems. This enables users to monitor and adjust settings remotely, ensuring consistent and efficient climate control throughout the facility.

Another key characteristic of the NP034-074 is its robust construction. Built to withstand various weather conditions, the unit features a galvanized steel cabinet with a powder-coated finish for corrosion resistance. Its design also facilitates easy access for maintenance and service, which minimizes downtime and operational interruptions.

In terms of air distribution, the NP034-074 incorporates a powerful blower system that ensures even and effective airflow throughout the space. This design improves indoor air quality by enhancing ventilation while maintaining comfort levels. Additionally, the unit can be customized with options such as economizers and variable speed fans to optimize performance based on specific building needs.

The NP034-074 is a versatile and reliable choice for businesses looking to enhance their HVAC systems. With its combination of energy efficiency, advanced technology, and robust construction, this rooftop unit stands out as a top choice for commercial climate control solutions.