Carrier NP034-074 Adjustments, Belt Installation and Tensioning, Condenser FAN Adjustment

Page 46

Adjustments

EVAPORATOR FAN AND POWER EXHAUST MOTOR PLATE Ð Adjust using a 15¤16-in. wrench on the adjusting bolts:

1.Loosen holddown bolts. (See Fig. 44.)

2.Turn the adjusting bolts to move the motor mounting plate toward or away from the fan to loosen or tighten the belts. Make the same number of turns to each bolt.

3.Retighten holddown bolts.

MODULATING POWER EXHAUST DIFFERENTIAL PRESSURE SWITCH Ð On 034,044 units, the differential pressure switch is located in the auxiliary control box. The auxiliary control box is mounted in the corner next to the power exhaust motor door. To gain access to the auxiliary control box, remove the auxiliary control box cover. When replacing the auxiliary control box cover, be sure to secure the cover properly in order to prevent water from being drawn into the auxiliary control box.

On 054-074 units, the differential pressure switch is mounted below the auxiliary control box next to the access door la- beled FILTER SECTION.

INLET GUIDE VANE DIFFERENTIAL PRESSURE SWITCH (Units With Optional Inlet Guide Vanes and Static Pressure Control) Ð On 034,044 units, the inlet guide vane differential pressure switch is located in the auxiliary control box. The auxiliary control box is mounted in the corner of the unit under the side air hood that is next to the access door marked FILTER SECTION. To gain access to the aux- iliary box, remove the auxiliary control box cover. When re- placing the auxiliary control box cover, be sure to secure the cover properly in order to prevent water from being drawn into the auxiliary control box.

On 054-074 units, the inlet guide vane differential pressure switch is mounted on an upright located behind the evaporator- fan motor. See Fig. 43.

BELT INSTALLATION AND TENSIONING

IMPORTANT: When installing or replacing belts, al- ways use a complete set of new, matched belts to pre- vent potential vibration problems. Mixing belts often results in premature breakage of the new belts.

1.Turn off unit power.

2.Adjust motor plate so belts can be installed without stretch- ing over the grooves of the pulley. (Forcing the belts can result in uneven belt stretching and a mismatched set of belts.)

3.Before tensioning the belts, equalize belt slack so that it is on the same side of the belt for all belts. Failure to do so may result in uneven belt stretching.

4.Tighten belts using the motor plate adjusting bolts.

5.Adjust until proper belt tension (1/2-in. de¯ection with one ®nger) is obtained. Be sure to adjust both adjusting bolts the same number of turns.

NOTE: Check the tension at least twice during the ®rst day of operation, as there is normally a rapid decrease in tension until the belts have run in. Check tension periodically thereafter and keep it at the recommended tension.

With the correct belt tension, belts may slip and squeal momentarily on start-up. This slippage is normal and dis- appears after wheel reaches operating speed. Excessive belt tension shortens belt life and may cause bearing and shaft damage.

Fig. 44 Ð Motor Plate Adjustment

PULLEY ALIGNMENT Ð For proper belt life, the motor and fan pulleys must be properly aligned. To check, ®rst turn off unit power. Place a straightedge against the motor and fan pulleys. See Fig. 45. If the pulleys are properly aligned, the straightedge should be parallel to the belts.

If they are not parallel, check that the motor shaft and fan shaft are parallel. If they are not, adjust the motor plate ad- justing bolts until they are.

After verifying that the shafts are parallel, loosen the set- screws on the motor pulley. Move pulley on the shaft until the pulleys are parallel. To move the sheave on the shaft, loosen the belts. If necessary, blower sheave can also be moved on the shaft.

INSTALLING ALTERNATE MOTOR PULLEY (Evapora- tor Fan Only) Ð On all units, the alternate motor pulley is ®eld-supplied. To install the alternate pulley:

1.Turn off unit power.

2.Loosen belts using motor adjusting bolts until belts can be removed without stretching them over the grooves of the pulley.

3.Remove belts.

4.Loosen setscrews on motor pulley.

5.Slide pulley off motor shaft. Make sure setscrews on new pulley are loose.

6.Slide new pulley onto fan shaft and align it with the fan pulley as described in Pulley Alignment section above.

7.Tighten setscrews.

8.Install belts and tension properly as described in Pulley Alignment section above.

CONDENSER FAN ADJUSTMENT

1.Turn off unit power.

2.Remove fan guard and loosen fan hub setscrew.

3.See Fig. 32 and adjust fan height using a straight edge laid across the fan deck.

4.Tighten setscrew and replace rubber hubcap to prevent hub from rusting to the motor shaft. Fill hub recess with Permagum if hub has no rubber hubcap.

5.Replace fan guard.

46

Image 46
Contents Installation, Start-Up Service Instructions Contents GeneralRigging Label Ð Physical Data 034, 044 Units Ð Physical Data 054-074 Units Operating Weights of Options and Accessories Weight Distribution and Center of GravityÐ Roof Curb 034, 044 Units Ft-inÐ Roof Curb 054-074 Units DegÐ Condenser Section Roof Curb 054-074 Units Only 054,064 270 105¤8 074 255 101¤16Economizer Settings Install Outdoor HoodsOutdoor-Air Inlet Adjustments Unit Sizes 034Unit Size Weight Ð Base Unit Dimensional Drawing 50DJ,DK,NP034,044 Units 8700 3946 5969 19-7 6717 Ð Base Unit Dimensional Drawing 50DJ,DK,NP054-074 Units Weight Ft-inDrain Location Selection Approx Deg AT 50% RHField Wire Routing Field Electrical ConnectionsField Power Wiring Connections Electrical Data, 034 Units 93.8 110 10.0 15.2 99.4 125 15.0 22.0 106.2 90.8 110 10.0 15.2 96.4 125 15.0 22.0 103.211.0 81.2 100 10.0 14.0 84.2 11075.6 10.0 12.2 80.0 100 15.0 18.0 85.8 73.6 10.0 12.2 78.0 100 15.0 18.0 83.865.8 67.8Electrical Data, 044 Units 109.5 125 10.0 15.2 115.1 15.0 22.0 121.9 150 106.5 125 10.0 15.2 112.1 15.0 22.0 118.9 15011.0 96.9 125 10.0 14.0 99.9 12586.1 110 10.0 12.2 90.5 15.0 18.0 96.3 84.1 110 10.0 12.2 88.5 15.0 18.0 94.376.3 100 10.0 11.0 78.3 100Electrical Data, 054 Units 10.0 15.2 150.8 200 15.0 22.0 157.6 20.0 28.0 163.6 10.0 15.2 144.8 175 15.0 22.0 151.6 200 20.0 28.0 157.615.0 21.0 129.6 175 20.0 27.0 135.6 17510.0 12.2 121.5 150 15.0 18.0 127.3 20.0 22.0 131.3 10.0 12.2 116.5 150 15.0 18.0 122.3 20.0 22.0 126.315.0 17.0 104.3 125 20.0 22.0 109.3 125Electrical Data, 064 Units 10.0 15.2 166.8 200 15.0 22.0 173.6 20.0 28.0 179.6 225 10.0 15.2 160.8 200 15.0 22.0 167.6 20.0 28.0 173.615.0 21.0 145.6 175 20.0 27.0 151.6 20010.0 12.2 131.8 150 15.0 18.0 137.6 175 20.0 22.0 141.6 10.0 12.2 126.8 150 15.0 18.0 132.6 20.0 22.0 136.6 17515.0 17.0 114.6 150 20.0 22.0 119.6 150Electrical Data, 074 Units 10.0 15.2 188.0 250 15.0 22.0 194.8 20.0 28.0 200.8 10.0 15.2 182.0 225 15.0 22.0 188.8 250 20.0 28.0 194.815.0 21.0 166.8 225 20.0 27.0 172.8 22510.0 12.2 151.0 200 15.0 18.0 156.8 20.0 22.0 160.8 10.0 12.2 146.0 175 15.0 18.0 151.8 200 20.0 22.0 155.815.0 17.0 133.8 175 20.0 22.0 138.8 175Field Control Thermostat Wiring Field Wiring for Building Pressurization and Smoke Purge Installing Flue/Inlet Hoods 48 Series Units Only Gas Piping DetailsFlue Hood PRE-START-UP Gas Manifold Pressure 48 Series Units Only Ð Field-Supplied Evaporator-Fan Pulley Data, 034,044 UnitsÐ Field-Supplied Evaporator-Fan Pulley Data, 054-074 Units Air Quantity Limits cfmGeneral Initial CheckHEATING, Units Without Economizer Service CompressorsPower Exhaust MOTORS, PULLEYS, and Belts Liquid Service VALVES, Filter DRIERS, and Sight GlassesEVAPORATOR-FAN MOTORS, PULLEYS, and Belts Burner Section Detail 48 Series Units Only Modulating Power Exhaust Damper Motor LubricationBelt Installation and Tensioning AdjustmentsCondenser FAN Adjustment Pulley Alignment Charging Chart, 044 Units System One Condenser Fan Running Charging Chart, 064 Units System All Condenser Fans Running Auxiliary Switch Stroke Adjustment Main Burner Removal 48 Series Units OnlyProtective Devices Compressor ProtectionEconomizer Motor Checkout Electric Heat 50 Series Units OnlyGas Heat 48 Series Units Only Economizer Control Board Checkout TestDetailed Check Control Board Component Arrangement Page Compressor Lockout Connections ACC Gas Heat Sections 48DJ,NP034,044 Units Gas Heat Sections 48DJ,NP054-074 Units Gas Heat DK034,044 Units Gas Heat DK054-074 Units Typical Wiring Schematic 48/50DJ,50DW Units 054-074 Shown Typical Wiring Schematic 48/50DJ,50DW Units 054-074 Shown Typical Wiring Schematic 48/50DK,50DY Units 054-074 Shown Typical Wiring Schematic 48/50DK,50DY Units 054-074 Shown Page Page Page Page Packaged Service Training Page Model no Serial no Date Technician OUTDOOR-AIR TemperatureRETURN-AIR Temperature Supply Voltage L1-L2

NP034-074 specifications

The Carrier NP034-074 is an advanced rooftop unit designed for commercial heating, ventilation, and air conditioning (HVAC) applications. This unit is part of Carrier’s extensive range of rooftop units that are known for their energy efficiency, reliability, and innovative features. The NP034-074 series is particularly recognized for its robust performance in diverse environmental conditions, making it ideal for a variety of commercial building types.

One of the standout features of the NP034-074 is its high-efficiency compressor. Equipped with a scroll compressor, the unit offers enhanced performance and quieter operation compared to traditional reciprocating compressors. This design not only improves energy efficiency but also reduces operating costs over time. The unit is designed to meet or exceed the latest efficiency standards, ensuring that businesses can enjoy optimal indoor comfort while keeping energy consumption low.

The NP034-074 also integrates advanced control technologies that provide users with greater flexibility and ease of operation. The intuitive control system allows for precise temperature management and can be easily integrated with building automation systems. This enables users to monitor and adjust settings remotely, ensuring consistent and efficient climate control throughout the facility.

Another key characteristic of the NP034-074 is its robust construction. Built to withstand various weather conditions, the unit features a galvanized steel cabinet with a powder-coated finish for corrosion resistance. Its design also facilitates easy access for maintenance and service, which minimizes downtime and operational interruptions.

In terms of air distribution, the NP034-074 incorporates a powerful blower system that ensures even and effective airflow throughout the space. This design improves indoor air quality by enhancing ventilation while maintaining comfort levels. Additionally, the unit can be customized with options such as economizers and variable speed fans to optimize performance based on specific building needs.

The NP034-074 is a versatile and reliable choice for businesses looking to enhance their HVAC systems. With its combination of energy efficiency, advanced technology, and robust construction, this rooftop unit stands out as a top choice for commercial climate control solutions.