Carrier NP034-074 specifications Rigging Label

Page 3

NOTES:

1.Sizes 034,044: Rig with 4 cables and spread with two 95 in. (2413 mm) and 2 A 1 A long spreader bars.

Sizes 054-074: Rig with 4 cables and spread with four 95 in. (2413 mm) and 2 A 1 B 1 A long spreader bars.

2.Center of gravity includes economizer.

1.All panels must be in place when rigging.

2.Unit is not designed for handling by forklift truck.

RIGGING WEIGHTS AND DIMENSIONS

UNIT

UNIT WEIGHT*

A

 

 

B

Lb

Kg

in.

 

mm

in.

 

mm

 

 

 

48DJD,DKD,NPD034

5941

2694.8

86.0

 

2185

109.4

 

2780

48DJE,NPE034

6070

2753.4

 

110.4

 

2804

 

 

 

 

48DJD,DKD,NPD044

6841

3103.1

92.6

 

2353

127.6

 

3240

48DJE,NPE044

6970

3161.6

 

128.6

 

3267

 

 

 

 

48DJD,DKD,NPD054

9230

4186.7

 

 

 

 

 

 

48DJE,NPE054

9350

4241.2

121.5

 

3086

126.8

 

3221

48DJD,DKD,NPD064

9530

4322.8

 

 

 

 

 

 

 

 

48DJE,NPE064

9650

4377.2

 

 

 

 

 

 

48DJD,DKD,NPD074

9950

4513.3

134.7

 

3421

134.7

 

3421

48DJE,NPE074

10,080

4572.3

 

 

 

 

 

 

 

 

50DJ,DK,NP034

5700

2585.5

84.8

 

2153

120.8

 

3067

50DW,DY,NB034

6270

2844.1

76.4

 

1940

102.5

 

2604

50DJ,DK,NP044

6350

2880.4

92.6

 

2353

126.6

 

3216

50DW,DY,NB044

6920

3138.9

86.0

 

2185

108.4

 

2753

50DJ,DK,NP054

8230

3733.1

120.8

 

3066

126.8

 

3221

50DW,DY,NB054

8780

3982.6

109.0

 

2769

109.0

 

2769

50DJ,DK,NP064

8530

3869.2

120.9

 

3071

120.9

 

3071

50DW,DY,NB064

9080

4119.7

120.8

 

3066

126.8

 

3221

50DJ,DK,NP074

8960

4064.3

131.7

 

3345

137.6

 

3495

50DW,DY,NB074

9500

4309.2

109.0

 

2769

109.0

 

2769

*Includes optional economizer.

Fig. 1 Ð Rigging Label

If roof curb is not used, support unit with steel beams along its entire length and then support steel as required. As a mini- mum, unit must be supported across its width at each lifting lug location.

Positioning Ð Provide clearance around and above unit for air¯ow, safety, and service access. Do not restrict top (area above condenser fans) in any way. Allow at least 6 ft on all sides for rated performance, code compliance, and service.

Do not install unit in an indoor location. Do not locate air inlets near exhaust vents or other sources of contaminated air.

On units equipped with or power exhaust option, high ve- locity air is exhausted out the hoods. Unit should be posi- tioned with at least 10 ft clearance between the exhaust hoods and any obstruction. Although unit is weatherproof, guard against water from higher level runoff and overhangs.

3

Image 3
Contents Installation, Start-Up Service Instructions General ContentsRigging Label Ð Physical Data 034, 044 Units Ð Physical Data 054-074 Units Weight Distribution and Center of Gravity Operating Weights of Options and AccessoriesFt-in Ð Roof Curb 034, 044 UnitsDeg Ð Roof Curb 054-074 Units054,064 270 105¤8 074 255 101¤16 Ð Condenser Section Roof Curb 054-074 Units OnlyUnit Sizes 034 Install Outdoor HoodsOutdoor-Air Inlet Adjustments Economizer SettingsUnit Size Weight Ð Base Unit Dimensional Drawing 50DJ,DK,NP034,044 Units 8700 3946 5969 19-7 6717 Weight Ft-in Ð Base Unit Dimensional Drawing 50DJ,DK,NP054-074 UnitsDrain Location Selection AT 50% RH Approx DegField Electrical Connections Field Wire RoutingField Power Wiring Connections Electrical Data, 034 Units 10.0 14.0 84.2 110 90.8 110 10.0 15.2 96.4 125 15.0 22.0 103.211.0 81.2 100 93.8 110 10.0 15.2 99.4 125 15.0 22.0 106.267.8 73.6 10.0 12.2 78.0 100 15.0 18.0 83.865.8 75.6 10.0 12.2 80.0 100 15.0 18.0 85.8Electrical Data, 044 Units 10.0 14.0 99.9 125 106.5 125 10.0 15.2 112.1 15.0 22.0 118.9 15011.0 96.9 125 109.5 125 10.0 15.2 115.1 15.0 22.0 121.9 15010.0 11.0 78.3 100 84.1 110 10.0 12.2 88.5 15.0 18.0 94.376.3 100 86.1 110 10.0 12.2 90.5 15.0 18.0 96.3Electrical Data, 054 Units 20.0 27.0 135.6 175 10.0 15.2 144.8 175 15.0 22.0 151.6 200 20.0 28.0 157.615.0 21.0 129.6 175 10.0 15.2 150.8 200 15.0 22.0 157.6 20.0 28.0 163.620.0 22.0 109.3 125 10.0 12.2 116.5 150 15.0 18.0 122.3 20.0 22.0 126.315.0 17.0 104.3 125 10.0 12.2 121.5 150 15.0 18.0 127.3 20.0 22.0 131.3Electrical Data, 064 Units 20.0 27.0 151.6 200 10.0 15.2 160.8 200 15.0 22.0 167.6 20.0 28.0 173.615.0 21.0 145.6 175 10.0 15.2 166.8 200 15.0 22.0 173.6 20.0 28.0 179.6 22520.0 22.0 119.6 150 10.0 12.2 126.8 150 15.0 18.0 132.6 20.0 22.0 136.6 17515.0 17.0 114.6 150 10.0 12.2 131.8 150 15.0 18.0 137.6 175 20.0 22.0 141.6Electrical Data, 074 Units 20.0 27.0 172.8 225 10.0 15.2 182.0 225 15.0 22.0 188.8 250 20.0 28.0 194.815.0 21.0 166.8 225 10.0 15.2 188.0 250 15.0 22.0 194.8 20.0 28.0 200.820.0 22.0 138.8 175 10.0 12.2 146.0 175 15.0 18.0 151.8 200 20.0 22.0 155.815.0 17.0 133.8 175 10.0 12.2 151.0 200 15.0 18.0 156.8 20.0 22.0 160.8Field Control Thermostat Wiring Field Wiring for Building Pressurization and Smoke Purge Gas Piping Details Installing Flue/Inlet Hoods 48 Series Units OnlyFlue Hood PRE-START-UP Ð Field-Supplied Evaporator-Fan Pulley Data, 034,044 Units Gas Manifold Pressure 48 Series Units OnlyAir Quantity Limits cfm Ð Field-Supplied Evaporator-Fan Pulley Data, 054-074 UnitsInitial Check GeneralHEATING, Units Without Economizer Compressors ServiceLiquid Service VALVES, Filter DRIERS, and Sight Glasses Power Exhaust MOTORS, PULLEYS, and BeltsEVAPORATOR-FAN MOTORS, PULLEYS, and Belts Burner Section Detail 48 Series Units Only Lubrication Modulating Power Exhaust Damper MotorAdjustments Belt Installation and TensioningCondenser FAN Adjustment Pulley Alignment Charging Chart, 044 Units System One Condenser Fan Running Charging Chart, 064 Units System All Condenser Fans Running Main Burner Removal 48 Series Units Only Auxiliary Switch Stroke AdjustmentCompressor Protection Protective DevicesEconomizer Control Board Checkout Test Electric Heat 50 Series Units OnlyGas Heat 48 Series Units Only Economizer Motor CheckoutDetailed Check Control Board Component Arrangement Page Compressor Lockout Connections ACC Gas Heat Sections 48DJ,NP034,044 Units Gas Heat Sections 48DJ,NP054-074 Units Gas Heat DK034,044 Units Gas Heat DK054-074 Units Typical Wiring Schematic 48/50DJ,50DW Units 054-074 Shown Typical Wiring Schematic 48/50DJ,50DW Units 054-074 Shown Typical Wiring Schematic 48/50DK,50DY Units 054-074 Shown Typical Wiring Schematic 48/50DK,50DY Units 054-074 Shown Page Page Page Page Packaged Service Training Page Supply Voltage L1-L2 OUTDOOR-AIR TemperatureRETURN-AIR Temperature Model no Serial no Date Technician

NP034-074 specifications

The Carrier NP034-074 is an advanced rooftop unit designed for commercial heating, ventilation, and air conditioning (HVAC) applications. This unit is part of Carrier’s extensive range of rooftop units that are known for their energy efficiency, reliability, and innovative features. The NP034-074 series is particularly recognized for its robust performance in diverse environmental conditions, making it ideal for a variety of commercial building types.

One of the standout features of the NP034-074 is its high-efficiency compressor. Equipped with a scroll compressor, the unit offers enhanced performance and quieter operation compared to traditional reciprocating compressors. This design not only improves energy efficiency but also reduces operating costs over time. The unit is designed to meet or exceed the latest efficiency standards, ensuring that businesses can enjoy optimal indoor comfort while keeping energy consumption low.

The NP034-074 also integrates advanced control technologies that provide users with greater flexibility and ease of operation. The intuitive control system allows for precise temperature management and can be easily integrated with building automation systems. This enables users to monitor and adjust settings remotely, ensuring consistent and efficient climate control throughout the facility.

Another key characteristic of the NP034-074 is its robust construction. Built to withstand various weather conditions, the unit features a galvanized steel cabinet with a powder-coated finish for corrosion resistance. Its design also facilitates easy access for maintenance and service, which minimizes downtime and operational interruptions.

In terms of air distribution, the NP034-074 incorporates a powerful blower system that ensures even and effective airflow throughout the space. This design improves indoor air quality by enhancing ventilation while maintaining comfort levels. Additionally, the unit can be customized with options such as economizers and variable speed fans to optimize performance based on specific building needs.

The NP034-074 is a versatile and reliable choice for businesses looking to enhance their HVAC systems. With its combination of energy efficiency, advanced technology, and robust construction, this rooftop unit stands out as a top choice for commercial climate control solutions.