Carrier NP034-074 Install Outdoor Hoods, Outdoor-Air Inlet Adjustments, Unit Sizes 034

Page 10

Condensate Drains Ð See Fig. 4A-4D and Fig. 5 for drain locations. The drain assemblies, each consisting of a 10-gage plate with a 11¤4-in. half coupling welded to it, are shipped in the unit fan section. Also included are 16-gage seal plates to cover the drain holes not being used. Open the access door marked FAN SECTION to ®nd the drain assem- blies, seal plates, and 4 screws for each mounting taped to the unit basepan.

After the unit has been set in place on the roof:

1.Select the appropriate drain locations. The 034 units have 6 drain holes (3 per side), and the 044-074 units have 8 drain holes (4 per side). Two holes on each side must be selected for condensate drains as shown in Fig. 5, and the remaining holes must be sealed.

2.Remove the drain assemblies and attach them to the bot- tom of the unit base rails at the preferred drain locations using the screws provided. See Fig. 6.

NOTE: Use a trap at least 4-in. deep.

3.Cover the remaining drain holes with the seal plates and screws provided. See Fig. 7.

4.Apply a bead of RTV or similar sealant around the drain assemblies and seal plates where they attach to the base rail. See Fig. 8.

NOTE: If unit is slab mounted, holes will need to be drilled in the side of the base rail and the holes factory-drilled in the bottom of the base rail will need to be plugged.

Install Outdoor Hoods

UNIT SIZES 034 AND 044

25% Outdoor-Air Hoods (Units Without Economizer Option)

1.Outdoor-air hoods are shipped bolted to the unit in a ship- ping position. Remove the 6 screws holding each 25% air hood shipping cover in place.

2.Replace the 6 screws.

3.Remove the holddown screw from each upper corner of each hood.

4.Pivot hoods outward (2 hoods total).

5.Install 17 screws around outside of each hood. (Screws are in the fastener package taped to the basepan inside the fan section.)

6.Apply a bead of RTV or similar sealant to corner of each hood at pivot point to prevent water leaks. See Fig. 9.

Economizer Hoods (Units With Economizer Option) Ð Fol- low the same procedure described in 25% Outdoor-Air Hoods section above.

UNIT SIZES 054-074

25% Outdoor-Air Hoods Ð The outdoor-air hoods are fac- tory installed on the 054-074 units.

Economizer Hoods (Units With Economizer Option)

1.Remove the 6 screws holding each of the 4 economizer shipping covers in place.

2.Replace the screws.

3.Remove the holddown screw from each upper corner of each economizer hood.

4.Pivot hoods outward. (There is a total of 4 hoods.)

5.Install 18 screws, (5 each side, 6 top, and 2 bottom), around the outside of each hood. (Screws are in the fastener pack- age taped to the basepan inside the fan section.)

6.Apply a bead of RTV or similar sealant to corner of econo- mizer hood at pivot point to prevent water leaks. (See Fig. 9.)

Outdoor-Air Inlet Adjustments

MANUAL OUTDOOR-AIR DAMPER (Units Without Econo- mizer Option) Ð All units except those equipped with a factory- installed economizer have a manual outdoor-air damper to provide ventilation air. This damper can be preset to admit up to 25% outdoor air into the return-air compartment. To adjust, loosen the blade limiter screws as shown in Fig. 10 and move the damper to the desired position. Then retighten the blade limiter screws to secure the damper. See Fig. 10. (To make this adjustment, it is necessary to remove the screens covering the hood opening and make adjustments from in- side the hood.)

ECONOMIZER SETTINGS

Enthalpy Sensor (See Fig. 11.) Ð This sensor is located be- hind the ®lters in the end economizer hood (the upper hood on sizes 054-074). See Fig. 12. For maximum bene®t of out- door air, set enthalpy sensor control to the A setting. At this setting, when the relative humidity is 50%, and the outdoor air is below 74 F, the sensor's relay contacts will be closed. See Fig. 13 and 14.

NOTE: Enthalpy control setting dial is on the economizer motor.

Mixed-Air Thermistor (MAT) Ð This control set point ad- justment is on the top of the economizer motor. This motor is located in the return-air section, and is accessed by open- ing the access panel marked FILTER SECTION. See Fig. 15. Set MAT set point adjustment dial to the desired setting. The factory setting is 55 F ± 5° F; range is 40 to 90 F. The MAT is located on the ®lter rack.

Damper Vent Position Ð The position setting adjustment is located on the cover of the economizer motor. See Fig. 15. Adjust by setting the fan switch at ON position (continuous fan operation), and setting the system selector switch to OFF position. Then turn adjustment screw slowly until the damp- ers assume the desired vent position. Do not manually op- erate the damper motor; damage to the motor may result.

Economizer Damper Linkage Adjustment Ð When replac- ing economizer damper motors, or if the linkage has come loose, it is critical that the linkages be adjusted correctly. They are sensitive, and incorrect adjustment can cause the motor to stall.

NB,NP Unit Minimum Position Set Point Ð Minimum econo- mizer position is set using the keypad and display module. Refer to Control and Troubleshooting literature for more details.

10

Image 10
Contents Installation, Start-Up Service Instructions Contents GeneralRigging Label Ð Physical Data 034, 044 Units Ð Physical Data 054-074 Units Operating Weights of Options and Accessories Weight Distribution and Center of GravityÐ Roof Curb 034, 044 Units Ft-inÐ Roof Curb 054-074 Units DegÐ Condenser Section Roof Curb 054-074 Units Only 054,064 270 105¤8 074 255 101¤16Economizer Settings Install Outdoor HoodsOutdoor-Air Inlet Adjustments Unit Sizes 034Unit Size Weight Ð Base Unit Dimensional Drawing 50DJ,DK,NP034,044 Units 8700 3946 5969 19-7 6717 Ð Base Unit Dimensional Drawing 50DJ,DK,NP054-074 Units Weight Ft-inDrain Location Selection Approx Deg AT 50% RHField Wire Routing Field Electrical ConnectionsField Power Wiring Connections Electrical Data, 034 Units 93.8 110 10.0 15.2 99.4 125 15.0 22.0 106.2 90.8 110 10.0 15.2 96.4 125 15.0 22.0 103.211.0 81.2 100 10.0 14.0 84.2 11075.6 10.0 12.2 80.0 100 15.0 18.0 85.8 73.6 10.0 12.2 78.0 100 15.0 18.0 83.865.8 67.8Electrical Data, 044 Units 109.5 125 10.0 15.2 115.1 15.0 22.0 121.9 150 106.5 125 10.0 15.2 112.1 15.0 22.0 118.9 15011.0 96.9 125 10.0 14.0 99.9 12586.1 110 10.0 12.2 90.5 15.0 18.0 96.3 84.1 110 10.0 12.2 88.5 15.0 18.0 94.376.3 100 10.0 11.0 78.3 100Electrical Data, 054 Units 10.0 15.2 150.8 200 15.0 22.0 157.6 20.0 28.0 163.6 10.0 15.2 144.8 175 15.0 22.0 151.6 200 20.0 28.0 157.615.0 21.0 129.6 175 20.0 27.0 135.6 17510.0 12.2 121.5 150 15.0 18.0 127.3 20.0 22.0 131.3 10.0 12.2 116.5 150 15.0 18.0 122.3 20.0 22.0 126.315.0 17.0 104.3 125 20.0 22.0 109.3 125Electrical Data, 064 Units 10.0 15.2 166.8 200 15.0 22.0 173.6 20.0 28.0 179.6 225 10.0 15.2 160.8 200 15.0 22.0 167.6 20.0 28.0 173.615.0 21.0 145.6 175 20.0 27.0 151.6 20010.0 12.2 131.8 150 15.0 18.0 137.6 175 20.0 22.0 141.6 10.0 12.2 126.8 150 15.0 18.0 132.6 20.0 22.0 136.6 17515.0 17.0 114.6 150 20.0 22.0 119.6 150Electrical Data, 074 Units 10.0 15.2 188.0 250 15.0 22.0 194.8 20.0 28.0 200.8 10.0 15.2 182.0 225 15.0 22.0 188.8 250 20.0 28.0 194.815.0 21.0 166.8 225 20.0 27.0 172.8 22510.0 12.2 151.0 200 15.0 18.0 156.8 20.0 22.0 160.8 10.0 12.2 146.0 175 15.0 18.0 151.8 200 20.0 22.0 155.815.0 17.0 133.8 175 20.0 22.0 138.8 175Field Control Thermostat Wiring Field Wiring for Building Pressurization and Smoke Purge Installing Flue/Inlet Hoods 48 Series Units Only Gas Piping DetailsFlue Hood PRE-START-UP Gas Manifold Pressure 48 Series Units Only Ð Field-Supplied Evaporator-Fan Pulley Data, 034,044 UnitsÐ Field-Supplied Evaporator-Fan Pulley Data, 054-074 Units Air Quantity Limits cfmGeneral Initial CheckHEATING, Units Without Economizer Service CompressorsPower Exhaust MOTORS, PULLEYS, and Belts Liquid Service VALVES, Filter DRIERS, and Sight GlassesEVAPORATOR-FAN MOTORS, PULLEYS, and Belts Burner Section Detail 48 Series Units Only Modulating Power Exhaust Damper Motor LubricationBelt Installation and Tensioning AdjustmentsCondenser FAN Adjustment Pulley Alignment Charging Chart, 044 Units System One Condenser Fan Running Charging Chart, 064 Units System All Condenser Fans Running Auxiliary Switch Stroke Adjustment Main Burner Removal 48 Series Units OnlyProtective Devices Compressor ProtectionEconomizer Motor Checkout Electric Heat 50 Series Units OnlyGas Heat 48 Series Units Only Economizer Control Board Checkout TestDetailed Check Control Board Component Arrangement Page Compressor Lockout Connections ACC Gas Heat Sections 48DJ,NP034,044 Units Gas Heat Sections 48DJ,NP054-074 Units Gas Heat DK034,044 Units Gas Heat DK054-074 Units Typical Wiring Schematic 48/50DJ,50DW Units 054-074 Shown Typical Wiring Schematic 48/50DJ,50DW Units 054-074 Shown Typical Wiring Schematic 48/50DK,50DY Units 054-074 Shown Typical Wiring Schematic 48/50DK,50DY Units 054-074 Shown Page Page Page Page Packaged Service Training Page Model no Serial no Date Technician OUTDOOR-AIR TemperatureRETURN-AIR Temperature Supply Voltage L1-L2

NP034-074 specifications

The Carrier NP034-074 is an advanced rooftop unit designed for commercial heating, ventilation, and air conditioning (HVAC) applications. This unit is part of Carrier’s extensive range of rooftop units that are known for their energy efficiency, reliability, and innovative features. The NP034-074 series is particularly recognized for its robust performance in diverse environmental conditions, making it ideal for a variety of commercial building types.

One of the standout features of the NP034-074 is its high-efficiency compressor. Equipped with a scroll compressor, the unit offers enhanced performance and quieter operation compared to traditional reciprocating compressors. This design not only improves energy efficiency but also reduces operating costs over time. The unit is designed to meet or exceed the latest efficiency standards, ensuring that businesses can enjoy optimal indoor comfort while keeping energy consumption low.

The NP034-074 also integrates advanced control technologies that provide users with greater flexibility and ease of operation. The intuitive control system allows for precise temperature management and can be easily integrated with building automation systems. This enables users to monitor and adjust settings remotely, ensuring consistent and efficient climate control throughout the facility.

Another key characteristic of the NP034-074 is its robust construction. Built to withstand various weather conditions, the unit features a galvanized steel cabinet with a powder-coated finish for corrosion resistance. Its design also facilitates easy access for maintenance and service, which minimizes downtime and operational interruptions.

In terms of air distribution, the NP034-074 incorporates a powerful blower system that ensures even and effective airflow throughout the space. This design improves indoor air quality by enhancing ventilation while maintaining comfort levels. Additionally, the unit can be customized with options such as economizers and variable speed fans to optimize performance based on specific building needs.

The NP034-074 is a versatile and reliable choice for businesses looking to enhance their HVAC systems. With its combination of energy efficiency, advanced technology, and robust construction, this rooftop unit stands out as a top choice for commercial climate control solutions.