Carrier 42VMC installation manual System configuration, Cooling only configuration of the system

Page 13

42VMC

System configuration

System configuration

Units are factory configured as heat pumps.

When a cooling only system is installed, it is necessary to change the factory configuration.

Such operation must be performed by the installer as follows:

Cooling only configuration (of the system)

Check all electrical connections (instructions and wiring diagram).

Insert the batteries into the remote control and leave it OFF.

Energise the system, turning the power supply ON.

• Press the and buttons of the infrared remote control and hold them pressed for more than 5 seconds.

The display will be cleared, the time segments will display the first configuration item (rAdr = remote address) and the temperature segments will display the default value of this configuration item (Ab = control of both indoor units).

Press button repeatedly until “UCFG” is displayed.

Press either the or button to change the default value (HP) to the new value (AC).

Press button to transmit the new configuration to the unit.

Press button to leave the configuration menu.

For other available configuration options, see table IV.

Note:

When 30 seconds have elapsed and no buttons have been pressed, the remote controller will automatically exit the configuration menu and the procedure has to be restarted.

Cooling only configuration (of the remote controller)

Insert the batteries into the remote controller and leave it OFF.

Energize the system, turning the power supply ON.

• Press the and buttons of the infrared remote control and hold them pressed for more than 5 seconds.

The display will be cleared, the temperature segments will display the first configuration item (CH = remote address) and the time segments will display the default value of this configuration item (Ab = control of both indoor units).

Press button repeatedly until “rc” is displayed.

Press either the or button to change the default value (HP) to the new value (AC).

Press button to transmit the new configuration to the unit.

Press button to leave the configuration menu.

For other available configuration options, see table V.

Note:

When 30 seconds have elapsed and no buttons have been pressed, the remote controller will automatically exit the configuration menu and the procedure has to be restarted.

Table IV

Item

Shown on

Explanation

Description

 

display

 

 

 

 

 

 

 

 

“A”: remote unit A

Remote address indoor unit A.

1

“rAdr”

“b”: remote unit B

Remote address indoor unit B.

 

 

“Ab”: remote units A and B

Default address is both indoor units.

2

“UCFG”

“HP”: heat pump

Default address is heat pump.

“AC”: cooling only

Change address for cooling only.

 

 

 

 

 

 

3

“UAdr”

1-240 with increase of 1

CCN unit address.

 

Default = 1.

 

 

 

4

“ZONE”

1-240 with increase of 1

Number of zone.

 

Default = 0.

 

 

 

5

“GFdn”

1-240 with increase of 1

Number of GFD.

 

Default = 1.

 

 

 

6

“A St”

“OF”: unit in stop mode

Choose of operating mode after a power supply

“On”: automatic restart

interruption.

 

 

Table V

Shown on

Explanation

Description

display

 

 

 

 

 

 

 

“A”: unit A

Address indoor unit A.

“CH”

“b”: unit B

Address indoor unit B.

 

“Ab”: units A and B

Default address is both indoor units.

“tU”

“C”: Degrees Celsius

Temperature.

“F”: Degrees Fahrenheit

Default is °C.

 

“rc”

“HP”: heat pump

Default address is heat pump.

“AC”: cooling only

Change address for cooling only.

 

“HR”

17

– 32: 17°C ÷ 32°C

Heating temperature range °C min. and max.

63

– 90: 63°F ÷ 90°F

Heating temperature range °F min. and max.

 

“CR”

17

– 32: 17°C ÷ 32°C

Cooling temperature range °C min. and max.

63

– 90: 63°F ÷ 90°F

Cooling temperature range °F min. and max.

 

“CL”

12

: 12: 12 hour clock (AM/PM)

Time format (AM = morning; PM = afternoon).

24

: 24: 24 hour clock

Default is 12 : 12.

 

NOTE: If the selection is changed from “rc” (HP operation) to cooling only and the remote control operating mode is auto or heating, the operating mode is set to cool.

NOTE: If the “HR” is set to a value that is lower than “CR” and the remote control operating mode is auto, the operating mode is set to cooling.

GB - 12

Image 13
Contents 42VMC 42VMC ContentsDimensions and weights Dimensions and weights Minimum clearances mmMinimum clearances Table I Nominal dataTable II Material supplied ConnectionsTable III Operating limits Choosing the installation site Unit installationGeneral information Positions to avoid42VMC Ceiling installation InstallationInstallation Vertical wall-mountingFor vertical installation For horizontal installationFlaring the end of the tubing Refrigerant connectionsConnection to the unit CheckElectrical connections Control and safety devicesJumper positioning Make refrigerant connections before electrical connections42VMC 009, 012 Electrical connections Cooling only42VMC 018 N Y O W2 50Hz~ Electrical connections Heat pumpY O W2 S R C Y O W2 S System configuration System configurationCooling only configuration of the system Cooling only configuration of the remote controllerTable VI Fault code Fault codeTable VII Accessories Description Part number Operating testFresh air renewal Air delivery and fresh air renewalVia R. Sanzio, 9 20058 Villasanta MI Italy Tel /3636.1 L010125H33