Carrier 42VMC Installation, Vertical wall-mounting, Ceiling installation, 009 012 014 018 024

Page 7

42VMC

Installation

Vertical wall-mounting

The preferred arrangement is generally under a window sill on an external wall.

This makes it easier to install the interconnecting tubing, electrical connections and condensate pipework to the outdoor unit.

The indoor unit can also be installed against an internal partition if the connections to the outdoor unit can be concealed.

For better operation of the thermostat located on the unit, it is advisable to avoid unit installation in enclosed spaces.

There are three alternatives for the connections to the unit: parallel to the wall, through the wall or through the side.

Preparation

Unpack the unit.

Open and remove the suction grille.

To remove suction grille, remove the central lock using a pliers, then with a screwdriver remove the two side screws fixing the fasteners.

Locate the mounting template, supplied with the unit.

Installation

Use the template supplied, and drill the four fixing holes in the wall. Use the four dowels provided.

Fix the attachment plate (using the two upper holes).

Attach the unit.

Fix the unit to the wall, using the two holes, positioned in the lower part.

Verify that the unit is level.

￿

￿

 

￿

￿

￿

 

￿

￿ Hole

￿ Plate

￿ Template

Ceiling installation

Using the template supplied, drill the four holes in the ceiling and position four tie rods (not supplied).

Attach the unit to the tie-rods, as shown in the illustration.

Ensure a minimum slope of 5 mm (refrigerant connection side must be lower) by modifying on the tie-rod fixing.

C

D

A

B

 

 

42VMC

009

012

014

018

024

A

mm

850

850

1000

1000

1000

B

mm

786

786

940

940

940

C

mm

237

237

250

250

250

D

mm

237

237

285

285

285

 

 

 

 

 

 

 

GB - 6

Image 7
Contents 42VMC 42VMC ContentsTable I Nominal data Dimensions and weights Minimum clearances mmDimensions and weights Minimum clearancesTable II Material supplied ConnectionsTable III Operating limits Positions to avoid Unit installationChoosing the installation site General information42VMC Vertical wall-mounting InstallationCeiling installation InstallationFor vertical installation For horizontal installationCheck Refrigerant connectionsFlaring the end of the tubing Connection to the unitMake refrigerant connections before electrical connections Control and safety devicesElectrical connections Jumper positioning42VMC 009, 012 Electrical connections Cooling only42VMC 018 N Y O W2 50Hz~ Electrical connections Heat pumpY O W2 S R C Y O W2 S Cooling only configuration of the remote controller System configurationSystem configuration Cooling only configuration of the systemOperating test Fault codeTable VI Fault code Table VII Accessories Description Part numberFresh air renewal Air delivery and fresh air renewalVia R. Sanzio, 9 20058 Villasanta MI Italy Tel /3636.1 L010125H33