Carrier 42VMC installation manual Air delivery and fresh air renewal, Fresh air renewal

Page 15

42VMC

Air delivery and fresh air renewal

Air delivery direction

Wall installation, cooling

Wall installation, heating

Ceiling installation, cooling

Ceiling installation, heating

 

 

 

 

 

 

 

 

“No draught”

(guide vane fully open)

(position recommended for ceiling installation in cooling mode, to avoid draughts)

IMPORTANT:

Air is supplied into the room through the grilles located on top of the cabinet; air from the room is drawn into the unit through the grilles and filter at the bottom of the unit.

Make absolutely sure that the above parts are not obstructed (even partially).

Fresh air renewal

Units are prearranged for introduction of renewal air through a prepunched hole located on back side.

Back knockout allows connection of fresh air inlet duct.

Model 009 - 012

Model 014 - 018 - 024

Use locally purchased material, suitable for operating temperatures of 60 °C (continuous).

Conduits can be of flexible polyester (with spiral core) or corrugated aluminium, externally covered with anti-condensate material (fibre glass from 12 to 25 mm thickness).

To complete the installation, all non-insulated ducts must be covered with anti-condensate insulation (ex. expanded neoprene, 6 mm thickness).

Not observing of these instructions may cause condensate dripping; the manufacturer will not be held responsible for any damage caused.

The supplementary fan motor for outside air intake has to be supplied separately and controlled by a bipolar ON-OFF switch with safety fuses (field-installed).

To adjust the fan motor air flow to the required values it is advisable to install a speed controller.

Fresh air flow must be less than 10% of the total air flow, to avoid operating problems.

For fresh air ventilation rates higher than 10%, a primary air treatment system with separate deflectors is recommended.

Install an air inlet grille with filter inspection port to prevent dust and dirt from entering and fouling the indoor unit heat exchanger.

Filter installation also makes the installation of a duct closing damper during shutdown periods unnecessary.

GB - 14

Image 15
Contents 42VMC 42VMC ContentsTable I Nominal data Dimensions and weights Minimum clearances mmDimensions and weights Minimum clearancesConnections Table II Material suppliedTable III Operating limits Positions to avoid Unit installationChoosing the installation site General information42VMC Vertical wall-mounting InstallationCeiling installation InstallationFor vertical installation For horizontal installationCheck Refrigerant connectionsFlaring the end of the tubing Connection to the unitMake refrigerant connections before electrical connections Control and safety devicesElectrical connections Jumper positioningElectrical connections Cooling only 42VMC 009, 01242VMC 018 Electrical connections Heat pump N Y O W2 50Hz~Y O W2 S R C Y O W2 S Cooling only configuration of the remote controller System configurationSystem configuration Cooling only configuration of the systemOperating test Fault codeTable VI Fault code Table VII Accessories Description Part numberFresh air renewal Air delivery and fresh air renewalVia R. Sanzio, 9 20058 Villasanta MI Italy Tel /3636.1 L010125H33