Carrier 42GW installation manual Avoid

Page 6

42 GW

 

Avoid...

E N G L I S H

MAX 3 m

MAX 3 m

... any obstruction of the unit air intake or supply grilles.

... exposure to direct sunshine, when the unit is operating in the

 

cooling mode; always use shutters or shades.

 

... positions too close to heating sources which may damage the unit.

... exposure to oil vapours.

... connecting condensate piping to sewage system drain without appropriate trap. Trap height must be calculated according to the unit discharge head in order to allow sufficient and continuous water evacuation.

... installation in areas with high frequency waves.

MAX. 200 mm

... only partial insulation of the piping.

Non-level installation which will cause condensate dripping.

... ascending sections of condensate drain piping.

These may only be used near the unit with a maximum height difference of 200 mm from the top of the unit.

... flattening or kinking the refrigerant pipes or condensate pipes.

... horizontal sections or curves of condensate drain piping with less than 2% slope.

...slack on electrical connections.

GB - 5

Image 6
Contents 42GW Contents 42 GW Hydronic Global Cassette Fan Coil Units004 008 Dimensions and weights42GW 42GW 012 016Technical data General Information Unit installationChoosing the installation site Positions to avoidAvoid Installation InstallationPrior to installation Only restrict the air outlets as indicated in the drawingCondensate drain pipe Installation of grille/frame assembly Water connectionsUse the screws supplied to fix the frame in position Motorized valve and control Mod GWWater connection Electrical wiringOperation of the thermo-electric valve ON-OFF valvesElectrical connections Standard version unit Control panelImportant for units with electric heaters Wiring diagram legendConnections Cables colourSupply Wiring diagram, standard version unitElectric heater Valves connectionAir distribution to adjacent room Air intake grille49 105 Fresh air intakeWinter operation diagram with fresh air intake Fresh air renewalConditioned air supply to an adjacent room Maintenance and owners guide Guide for the ownerL010122H22 Via R. Sanzio, 9 20058 Villasanta MI Italy Tel /3636.1