Carrier 42GW Air intake grille, 49 105, Air distribution to adjacent room, Fresh air intake

Page 15

42 GW

Fresh air renewal and conditioned air supply to an adjacent room

49 105 120

C

B

A Ø

216

A Ø

 

 

 

 

Duct connection flange

 

 

 

 

Clip

 

 

 

 

6 mm neoprene gasket

Model

 

004-008-010

012-016-020

 

Insulated flexible duct

Ø A

mm

150

150

Fresh air intake

 

 

 

 

Conditioned air supply to an

B

mm

120

120

adjacent room

Ø C

mm

70

100

Polystyrene partition

 

 

 

 

Baffle

 

 

 

 

 

 

 

 

Frame

Air intake grille

Wall

Undercut door

Wall-fitted grille

Door-fitted grille

Side knockouts allow connection of fresh air inlet ducts and ducts to deliver conditioned air to an adjacent room.

Remove the external prepunched anti-condensate insulation and take away the knockout panels using a punch.

Air distribution to adjacent room

With a pencil, trace a line on the polystyrene around the inside edges of the panel that was previously removed.

Cut away the polystyrene with a knife, taking care not to damage the heat exchange coil.

Fresh air intake

Remove the polystyrene partition.

Introduce the baffle supplied after the frame has been hooked as per above figure (ref. ).

Following that tighten the assembly frame/grille using the 4 screws.

Use locally purchased material, suitable for operating temperatures of 60 ° C (continuous).

Conduits can be of flexible polyester (with spiral core) or corrugated aluminium, externally covered with anti-condensate material (fibre glass of 12 +/- 25 mm thickness).

To complete the installation, all non-insulated ducts must be covered with anti-condensate insulation (ex. expanded neoprene, 6 mm thickness).

If these instructions are not observed, condensate may drip; the manufacturer will not be held responsible for any damage caused.

The two prepunched side knockouts must not be used at the same time to deliver conditioned air to an adjacent room.

The return and supply duct lengths can be calculated in accordance with the "air distribution to an adjacent room" and "fresh air renewal" diagrams (also taking into account the pressure drop through air diffusers, grilles and fresh air filters), as well as the increase in noise caused by these ducts.

GB - 14

Image 15
Contents 42GW 42 GW Hydronic Global Cassette Fan Coil Units Contents42GW 012 016 Dimensions and weights42GW 004 008Technical data Positions to avoid Unit installationChoosing the installation site General InformationAvoid Only restrict the air outlets as indicated in the drawing InstallationPrior to installation InstallationCondensate drain pipe Installation of grille/frame assembly Water connectionsUse the screws supplied to fix the frame in position Mod GW Motorized valve and controlON-OFF valves Electrical wiringOperation of the thermo-electric valve Water connectionStandard version unit Control panel Electrical connectionsCables colour Wiring diagram legendConnections Important for units with electric heatersValves connection Wiring diagram, standard version unitElectric heater SupplyFresh air intake Air intake grille49 105 Air distribution to adjacent roomWinter operation diagram with fresh air intake Fresh air renewalConditioned air supply to an adjacent room Guide for the owner Maintenance and owners guideVia R. Sanzio, 9 20058 Villasanta MI Italy Tel /3636.1 L010122H22