Selection procedure (50XCA08 unit example)

IDetermine design conditions. Given:

Cooling Requirements

Total Cooling Capacity (TC) . . . . . . . . .82,000 Btuh

Sensible Cooling Capacity (SHC) . . . . .65,000 Btuh

Evaporator Air Quantity. . . . . . . . . . . . . 3,000 Cfm

Condenser Air Quantity . . . . . . . . . . . . . 3,500 Cfm

Summer Entering-Air Conditions:

Entering dry bulb (edb) . . . . . . . . . . . . . . . . .80 F

Entering wet bulb (ewb) . . . . . . . . . . . . . . . .67 F

Entering Condenser Air Temp (EAT) . . . . . . .95 F

Unit Voltage . . . . . . . . . . . . . . . . . . . . . . . . 460 V

Fan Requirements

External Static Pressure Required

ESP (in. wg) . . . . . . . . . . . . . . . . . . . . . . . . . .0.75

IISelect unit based on cooling requirements.

Enter Gross Cooling Capacities table for 50XCA08 unit at 3000 cfm and required wet bulb of 67 F and read down to the section displaying capacities with 95 F entering-air temperature. The 50XCA08 pro- vides a total capacity closest to design requirements.

For example:

Unit selection — 50XCA08

Selected at 3000 cfm of 80 F edb, 67 F ewb enter- ing air.

TC = 83,800 Btuh

SHC = 66,500 Btuh

(See correction factor table, below the cooling capacity tables.)

Compressor — Power Input = 5.85 kW

Leaving Air db = 59.9 F

Leaving Air wb at 67 F wb

=58.3 F

IIIFan requirements.

External static pressure (ESP) required 0.75 in. wg

Enter Evaporator Fan Performance table for cfm, and static pressure required to obtain the following data:

For 3000 cfm and 0.75 ESP, by interpolation the fan operates at 877 rpm and requires 0.98 brake horsepower.

Since standard motor horsepower is 1.0, it will pro- duce the necessary cfm and ESP for this job.

7

Image 7
Contents Product Data Features/BenefitsTable of contents AHRI* capacity ratings Model number nomenclatureCompressor Physical dataFront View Dimensions 50XCA06-14Rear View Dimensions 50XCA16,24Selection procedure 50XCA08 unit example Gross Cooling Capacities Performance dataGross Cooling Capacities 50XCA12 10 Tons 50XCA14 12 Tons 50XCA16 15 Tons 50XCA024 20 Tons Condenser FAN Performance Condenser FAN Performance 50XCA12 10 Tons ESP in. wg 50XCA14 12 Tons ESP in. wg 50XCA16 15 Tons ESP in. wg 50XCA24 20 Tons ESP in. wg Evaporator FAN Performance Evaporator FAN Performance 50XCA012 10 Tons ESP in. wg Bhp Rpm Bhp Rpm 4500 000 Unit Electrical Data Electrical dataFAN Electrical Data GND GND Typical wiring schematicTo Line Operating sequence ControlsA50-8506 Typical piping and wiringLocation Application dataSetting condenser fan speed System Description Guide specificationsPage Carrier Corporation Syracuse, New York 310