24 (TYP) |
SERVICE CLEARANCE | 36 |
|
NOTE: Dimensions are in inches.
Selection procedure (50XCA08 unit example)
IDetermine design conditions. Given:
Cooling Requirements
Total Cooling Capacity (TC) . . . . . . . . .82,000 Btuh
Sensible Cooling Capacity (SHC) . . . . .65,000 Btuh
Evaporator Air Quantity. . . . . . . . . . . . . 3,000 Cfm
Condenser Air Quantity . . . . . . . . . . . . . 3,500 Cfm
Summer
Entering dry bulb (edb) . . . . . . . . . . . . . . . . .80 F
Entering wet bulb (ewb) . . . . . . . . . . . . . . . .67 F
Entering Condenser Air Temp (EAT) . . . . . . .95 F
Unit Voltage . . . . . . . . . . . . . . . . . . . . . . . . 460 V
Fan Requirements
External Static Pressure Required
ESP (in. wg) . . . . . . . . . . . . . . . . . . . . . . . . . .0.75
IISelect unit based on cooling requirements.
Enter Gross Cooling Capacities table for 50XCA08 unit at 3000 cfm and required wet bulb of 67 F and read down to the section displaying capacities with 95 F
For example:
Unit selection — 50XCA08
Selected at 3000 cfm of 80 F edb, 67 F ewb enter- ing air.
TC = 83,800 Btuh
SHC = 66,500 Btuh
(See correction factor table, below the cooling capacity tables.)
Compressor — Power Input = 5.85 kW
Leaving Air db = 59.9 F
Leaving Air wb at 67 F wb
=58.3 F
IIIFan requirements.
External static pressure (ESP) required 0.75 in. wg
Enter Evaporator Fan Performance table for cfm, and static pressure required to obtain the following data:
For 3000 cfm and 0.75 ESP, by interpolation the fan operates at 877 rpm and requires 0.98 brake horsepower.
Since standard motor horsepower is 1.0, it will pro- duce the necessary cfm and ESP for this job.
7