Carrier 50XCA06-24 manual 50XCA12 10 Tons ESP in. wg

Page 16

Performance data (cont)

CONDENSER FAN PERFORMANCE (cont)

50XCA12 (10 Tons)

 

 

 

 

 

 

 

 

ESP (in. wg)

 

 

 

 

 

 

 

CFM

0.00

0.00

0.10

0.20

0.30

0.40

0.50

0.60

 

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

4800

594

0.86

598

0.87

655

1.00

708

1.14

757

1.29

803

1.44

846

1.59

5000

588

0.91

618

0.97

673

1.11

725

1.25

773

1.40

818

1.56

861

1.72

5200

582

0.95

638

1.08

692

1.23

742

1.37

789

1.53

833

1.68

875

1.85

915

2.02

5400

601

1.06

658

1.20

711

1.35

759

1.50

805

1.66

849

1.82

890

1.99

930

2.16

5600

623

1.18

679

1.33

729

1.48

777

1.64

822

1.80

865

1.97

905

2.14

944

2.32

5800

646

1.31

699

1.46

749

1.62

795

1.78

839

1.95

881

2.12

921

2.30

959

2.48

6000

668

1.45

720

1.61

768

1.77

813

1.94

856

2.11

897

2.29

936

2.47

974

2.65

6200

690

1.60

740

1.76

787

1.93

832

2.10

874

2.28

914

2.46

952

2.64

989

2.83

6400

713

1.76

761

1.93

807

2.10

850

2.28

891

2.46

931

2.64

969

2.83

1005

3.03

6600

735

1.93

782

2.11

827

2.28

869

2.46

909

2.65

948

2.84

985

3.03

1021

3.23

6800

757

2.11

803

2.29

846

2.47

888

2.66

927

2.85

965

3.04

1002

3.24

1037

3.44

7000

779

2.30

824

2.49

866

2.68

907

2.87

946

3.06

983

3.26

1019

3.46

1053

3.67

7200

802

2.51

845

2.70

887

2.89

926

3.09

964

3.29

1001

3.49

1036

3.70

1070

3.91

7400

824

2.72

866

2.92

907

3.12

945

3.32

983

3.52

1019

3.73

1053

3.94

1087

4.15

7600

846

2.95

887

3.15

927

3.35

965

3.56

1001

3.77

1037

3.98

1071

4.20

1104

4.42

50XCA12 (10 Tons) (cont)

 

 

 

 

 

 

 

ESP (in. wg)

 

 

 

 

 

 

CFM

0.70

0.80

0.90

1.00

1.10

1.20

1.30

 

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

4800

5000

5200

5400

5600

981

2.50

5800

996

2.67

1031

2.86

6000

1010

2.84

1045

3.04

6200

1025

3.03

1060

3.23

1093

3.43

6400

1040

3.23

1074

3.43

1107

3.64

1139

3.85

6600

1056

3.43

1089

3.64

1122

3.85

1153

4.07

6800

1071

3.65

1104

3.86

1136

4.08

1168

4.30

1198

4.52

7000

1087

3.88

1120

4.09

1151

4.31

1182

4.54

1212

4.77

1241

5.00

7200

1103

4.12

1135

4.34

1166

4.56

1197

4.79

1226

5.02

1255

5.26

1284

5.50

7400

1119

4.37

1151

4.60

1182

4.82

1212

5.06

1241

5.29

1270

5.53

1298

5.78

7600

1136

4.64

1167

4.87

1197

5.10

1227

5.33

1256

5.57

1284

5.82

1312

6.06

LEGEND

Bhp — Brake Horsepower

ESP — External Static Pressure

NOTES:

1.Units are available with several motor hp options. Refer to the physical data table.

2.Static pressure losses must be applied to external static pressure before entering the fan performance table.

3.Interpolation is permitted; extrapolation is not.

4.Fan performance is based on filter, unit casing, and wet coil losses.

16

Image 16
Contents Features/Benefits Product DataTable of contents Model number nomenclature AHRI* capacity ratingsPhysical data CompressorDimensions 50XCA06-14 Front ViewDimensions 50XCA16,24 Rear ViewSelection procedure 50XCA08 unit example Performance data Gross Cooling CapacitiesGross Cooling Capacities 50XCA12 10 Tons 50XCA14 12 Tons 50XCA16 15 Tons 50XCA024 20 Tons Condenser FAN Performance Condenser FAN Performance 50XCA12 10 Tons ESP in. wg 50XCA14 12 Tons ESP in. wg 50XCA16 15 Tons ESP in. wg 50XCA24 20 Tons ESP in. wg Evaporator FAN Performance Evaporator FAN Performance 50XCA012 10 Tons ESP in. wg Bhp Rpm Bhp Rpm 4500 000 Electrical data Unit Electrical DataFAN Electrical Data Typical wiring schematic GND GNDTo Line Controls Operating sequenceTypical piping and wiring A50-8506Application data LocationSetting condenser fan speed Guide specifications System DescriptionPage Carrier Corporation Syracuse, New York 310