Carrier 50XCA06-24 manual Model number nomenclature, AHRI* capacity ratings

Page 3

Model number nomenclature

50XC A 24 A A - B 5 A A H 0 AA

50XC – OMNIZONE™ Indoor Packaged Unit

Condenser Option

A Air-Cooled

Unit Size Nominal Tons

06

– 5

14 – 12

08

– 7 1/2

16 – 15

12

– 10

24 – 20

 

 

 

Return Air/Discharge Air Options

A – Rear Return, Vertical Discharge, Single Unit, Ducted

Heating Coil Options

A – No Heating Coil

Evaporator Fan Speed

See unit price pages.

Evaporator Motor Hp Options

B – 1/2 Hp Motor

F – 2 Hp Motor

C – 3/4 Hp Motor

G – 3 Hp Motor

D – 1 Hp Motor

H – 5 Hp Motor

E – 1 1/2 Hp Motor

J – 7 1/2 Hp Motor

Factory-Installed Options Code

See codes in unit price pages

Design Revision Level

0 – Original Release

X – Quote Control

Condenser Motor Hp Options

D – 1 Hp Motor

E – 1 1/2 Hp Motor

F – 2 Hp Motor

G – 3 Hp Motor

H – 5 Hp Motor

J – 7 1/2 Hp Motor

Condenser Coil Options

A – 0.0 to 0.2 ESP

B – 0.2 to 0.5 ESP

C – 0.5 to 1.0 ESP

Control Options

A – Standard Controls

Voltage Options 1 575-3-60

5 208/230-3-60

6460-3-60

a50-8500

AHRI* capacity ratings

 

UNIT

 

NOMINAL

EVAPORATOR

CONDENSER

NET COOLING

TOTAL

EER

IEER

50XCA

TONS

CFM

CFM

(Btuh)

kW

 

 

 

06

 

5

1,875

2,800

65,000

5.8

11.2

11.4

 

08

 

71/2

2,625

3,500

80,000

7.1

11.2

11.4

 

12

 

10

3,500

5,500

119,000

10.6

11.2

11.4

 

14

 

12

4,200

8,000

140,000

12.7

11.0

11.2

 

16

 

15

5,250

8,000

162,000

14.7

11.0

11.2

 

24

 

20

7,000

11,400

240,000

24.0

10.0

10.1

 

 

 

LEGEND

 

 

 

 

 

 

EER

Energy Efficiency Ratio

 

 

 

 

 

 

IEER

Integrated Energy Efficiency Ratio

 

 

 

 

 

*AHRI — Air Conditioning, Heating, and Refrigeration Institute.

NOTE: Unit is tested in accordance with AHRI standard 340/360.

3

Image 3
Contents Product Data Features/BenefitsTable of contents AHRI* capacity ratings Model number nomenclatureCompressor Physical dataFront View Dimensions 50XCA06-14Rear View Dimensions 50XCA16,24Selection procedure 50XCA08 unit example Gross Cooling Capacities Performance dataGross Cooling Capacities 50XCA12 10 Tons 50XCA14 12 Tons 50XCA16 15 Tons 50XCA024 20 Tons Condenser FAN Performance Condenser FAN Performance 50XCA12 10 Tons ESP in. wg 50XCA14 12 Tons ESP in. wg 50XCA16 15 Tons ESP in. wg 50XCA24 20 Tons ESP in. wg Evaporator FAN Performance Evaporator FAN Performance 50XCA012 10 Tons ESP in. wg Bhp Rpm Bhp Rpm 4500 000 Unit Electrical Data Electrical dataFAN Electrical Data GND GND Typical wiring schematicTo Line Operating sequence ControlsA50-8506 Typical piping and wiringLocation Application dataSetting condenser fan speed System Description Guide specificationsPage Carrier Corporation Syracuse, New York 310