Carrier 30RAP010-060 Maximum Field Wiring Sizes, 30RAP Electrical Data No Hydronic Package

Page 21

Table 9 — Maximum Field Wiring Sizes

 

CONNECTION

WIRE SIZE RANGE

 

TYPE

 

 

 

TERMINAL BLOCK, MCA UP TO 175 AMPS

14 AWG to 2/0 AWG

 

TERMINAL BLOCK, MCA 175 TO 420 AMPS

2 AWG to 600 kcmil

 

NON-FUSED DISCONNECT, UP TO 100 AMPS

14 AWG to 1/0 AWG

 

NON-FUSED DISCONNECT, 100 TO 200 AMPS

6 AWG to 350 kcmil

 

NON-FUSED DISCONNECT, 200 TO 450 AMPS

3/0 AWG to 500 kcmil

AWG

American Wire Gage, kcmil

 

MCA

Minimum Circuit Amps

 

Table 10 — 30RAP Electrical Data — No Hydronic Package

 

UNIT VOLTAGE

 

POWER

 

NO HYDRONIC PACKAGE

 

 

 

NO HYDRONIC PACKAGE

 

 

 

STANDARD LOW-SOUND AEROACOUSTIC™ FAN

 

OPTIONAL VALUE SOUND FANS

 

UNIT

 

 

 

SUPPLY

 

 

30RAP

V-Hz

Supplied

QTY

 

 

 

Rec

 

 

 

 

 

Rec

 

(3 Ph)

Min

Max

REQD.

MCA

MOCP

ICF

Fuse

MCA

 

MOCP

ICF

 

Fuse

 

 

 

 

Size

 

 

 

 

 

Size

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230-60

187

253

1

66.1

110

251.0

80

66.7

 

110

251.6

 

80

010

380-60

342

418

1

33.5

50

148.9

40

33.5

 

50

148.9

 

40

460-60

414

506

1

26.2

40

127.9

35

26.6

 

45

128.3

 

35

 

 

 

 

575-60

518

633

1

20.8

35

102.4

25

21.0

 

35

102.6

 

25

 

208/230-60

187

253

1

75.8

125

346.0

90

76.4

 

125

346.6

 

100

015

380-60

342

418

1

46.4

80

199.9

60

46.4

 

80

199.9

 

60

460-60

414

506

1

36.5

60

181.9

45

36.9

 

60

182.3

 

45

 

 

 

 

575-60

518

633

1

32.0

50

134.4

40

32.2

 

50

134.6

 

40

 

208/230-60

187

253

1

87.2

110

270.4

100

88.4

 

110

271.6

 

100

018

380-60

342

418

1

51.1

70

167.0

60

51.1

 

70

167.0

 

60

460-60

414

506

1

43.4

60

136.5

50

44.2

 

60

137.3

 

50

 

 

 

 

575-60

518

633

1

34.9

45

98.2

40

35.3

 

45

98.6

 

40

 

208/230-60

187

253

1

92.6

125

286.8

110

93.8

 

125

288.0

 

110

020

380-60

342

418

1

61.2

80

176.5

70

61.2

 

80

176.5

 

70

460-60

414

506

1

46.1

60

148.7

60

46.9

 

60

149.5

 

60

 

 

 

 

575-60

518

633

1

37.0

50

99.1

45

37.4

 

50

99.5

 

45

 

208/230-60

187

253

1

127.4

175

363.3

150

128.6

 

175

364.5

 

150

025

380-60

342

418

1

68.3

90

173.7

80

68.3

 

90

173.7

 

80

460-60

414

506

1

57.8

80

178.9

70

58.6

 

80

179.7

 

70

 

 

 

 

575-60

518

633

1

49.8

60

133.7

60

50.0

 

60

134.1

 

60

 

208/230-60

187

253

1

137.6

175

407.8

175

138.8

 

175

409.0

 

175

030

380-60

342

418

1

84.3

110

237.8

100

84.3

 

110

237.8

 

100

460-60

414

506

1

66.3

90

211.7

80

67.1

 

90

212.5

 

80

 

 

 

 

575-60

518

633

1

58.1

80

160.5

70

58.5

 

80

160.9

 

70

 

208/230-60

187

253

1

165.4

200

341.6

175

167.2

 

200

341.6

 

200

035

380-60

342

418

1

84.3

110

237.8

100

84.3

 

110

237.8

 

100

460-60

414

506

1

82.4

100

176.3

90

83.6

 

100

176.3

 

90

 

 

 

 

575-60

518

633

1

66.1

80

121.0

70

66.7

 

80

121.0

 

80

 

208/230-60

187

253

1

194.8

225

377.0

225

196.6

 

225

377.0

 

225

040

380-60

342

418

1

112.5

125

216.1

125

112.5

 

125

216.1

 

125

460-60

414

506

1

86.2

100

180.1

100

87.4

 

100

180.1

 

100

 

 

 

 

575-60

518

633

1

68.8

80

143.7

80

69.4

 

80

143.7

 

80

 

208/230-60

187

253

1

229.6

250

450.7

250

231.4

 

250

450.7

 

250

045

380-60

342

418

1

119.6

125

216.5

125

119.6

 

125

216.5

 

125

460-60

414

506

1

97.9

110

214.8

110

99.1

 

110

214.8

 

110

 

 

 

 

575-60

518

633

1

81.4

100

163.5

90

82.0

 

100

163.5

 

90

 

208/230-60

187

253

1

236.0

250

453.9

250

237.8

 

250

453.9

 

250

050

380-60

342

418

1

126.0

150

219.7

150

126.0

 

150

219.7

 

150

460-60

414

506

1

106.9

125

219.3

125

108.1

 

125

219.3

 

125

 

 

 

 

575-60

518

633

1

91.8

110

168.7

100

92.4

 

110

168.7

 

100

 

208/230-60

187

253

1

252.2

300

502.9

300

254.6

 

300

502.9

 

300

055

380-60

342

418

1

145.9

175

290.9

175

145.9

 

175

290.9

 

175

460-60

414

506

1

118.3

125

255.9

125

119.9

 

125

255.9

 

125

 

 

 

 

575-60

518

633

1

102.7

125

199.3

110

103.5

 

125

199.3

 

110

 

208/230-60

187

253

1

261.2

317

507.4

300

263.6

 

320

507.4

 

300

060

380-60

342

418

1

160.1

175

298.0

175

160.1

 

175

298.0

 

175

460-60

414

506

1

125.9

150

259.7

150

127.5

 

150

259.7

 

150

 

 

 

 

575-60

518

633

1

110.3

125

203.1

125

111.1

 

125

203.1

 

125

LEGEND

ICF — Instantaneous Current Flow

MCA — Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection

NOTES:

1.Units are suitable for use on electrical systems where voltage supplied to the unit ter- minals is not below or above the listed minimum and maximum limits. Maximum allow- able phase imbalance is: voltage, 2%; amps 10%.

2.All units/modules have single point primary power connection. (Each unit/module requires its own power supply.) Main power must be supplied from a field-supplied disconnect.

3.Cooler heater is wired into the control circuit so it is always operable as long as the power supply disconnect is on, even if any safety device is open.

21

Image 21
Contents Installation Instructions Quality Assurance A30-4861 Unit Operating WeightsUnit 30RAP Physical Data, 30RAP EnglishPhysical Data, 30RAP SI Check Compressor Mounting As Cooler Fluid and Drain Piping Con- nectionsA30-4916 A30-4948 Dimensions 30RAP010 and 015 UnitsA30-4949 Dimensions 30RAP018-030 UnitsDimensions 30RAP035-060 Units A30-4879 Accessory Storage Tank Dimensions 30RAP010,015 UnitsA30-4880 Accessory Storage Tank Dimensions 30RAP018-030 UnitsA30-4880 A30-4881 Accessory Storage Tank Dimensions 30RAP035-060 UnitsTypical Piping Diagram 30RAP Units with Hydronic Package A30-4635 Factor for Setting Tank PressureFill the Chilled Water Loop Water Quality Characteristics LimitationsTypical Set Up for Cleaning Process Head kPa as Read on Balancing Valve for 30RAP010-030 Head Ft Water as Read on Balancing Valve for 30RAP010-030Head Ft Water as Read on Balancing Valve for 30RAP035-060 Head kPa as Read on Balancing Valve for 30RAP035-060Heat Exchanger Pressure Drop 30RAP035-060 English Heat Exchanger Pressure Drop 30RAP035-060 SI Minimum Fluid Volume In CirculationMake Electrical Connections Wind Baffle Accessory Quantities30RAP Electrical Data No Hydronic Package Maximum Field Wiring Sizes38RAP Unit Voltage Pump Size 3 hp Pump Size 5 hp Pump Size 7.5 hp Hz 3 Ph 208/230-60 75.3 110 260.2 80.1 125 265.0 100 86.7 271.6 Fan Electrical Data Optional Value Sound Fans Fan Electrical Data Standard Low-Sound AeroAcoustic FansPump Electrical Data Accessory Tank Electrical DataPER Circuit RLA LRA Compressor Electrical DataCheck Refrigerant Circuit Install AccessoriesTypical Main Power and Control Connections Suction Access Port Sizes 018-030 Shown Units Without Hydronic Package English Unit Pressure Drop Curves, 30RAP010-060KPa Drop Water Pressure Liters/Second Appendix a Unit Pressure Drop Curves, 30RAP010-060Units with Single Pump Hydronic Package English Units with Single Pump Hydronic Package SI Units with Dual Pump Hydronic Package English Units with Dual Pump Hydronic Package SI Accessory Tank Flow Rate L/s Appendix a Pressure Drop Curves, Accessory Storage TanksPage Copyright 2009 Carrier Corporation
Related manuals
Manual 124 pages 40.33 Kb

30RAP010-060 specifications

The Carrier 30RAP010-060 is a series of rooftop air conditioning units designed for effective climate control in commercial applications. Engineered with advanced technologies, these units are known for their reliability, energy efficiency, and ease of installation, making them a suitable choice for a range of settings including offices, retail spaces, and industrial facilities.

One of the standout features of the 30RAP series is its robust construction. Designed to withstand various environmental conditions, these units come equipped with a weather-resistant cabinet and a corrosion-resistant finish. This durability ensures long-term performance and reduced maintenance costs.

Energy efficiency is a significant characteristic of the Carrier 30RAP series. These units utilize advanced technologies such as a high-efficiency compressor and variable speed fans. The inclusion of economizers also contributes to energy savings by allowing the system to take advantage of outdoor air when the conditions are favorable. With high SEER (Seasonal Energy Efficiency Ratio) ratings, the 30RAP units help businesses reduce operating costs while minimizing their environmental footprint.

The 30RAP series is equipped with smart control systems that provide enhanced operational efficiency and comfort. With features such as programmable thermostats and remote access capabilities, building managers can easily monitor and adjust the system to maintain optimal indoor climate conditions. Additionally, the units are compatible with building automation systems, allowing for seamless integration into a larger HVAC network.

The installation process of the Carrier 30RAP010-060 is streamlined thanks to a compact design and lightweight construction, which simplifies the transportation and placement on rooftops. Moreover, the unit's modular components facilitate easy access for maintenance and repairs, minimizing downtime and improving overall reliability.

In summary, the Carrier 30RAP010-060 series stands out for its combination of durability, energy efficiency, and advanced control technologies. It is an ideal solution for businesses seeking reliable climate control systems that balance performance with cost-effectiveness. Whether for new installations or replacements, these rooftop units provide the necessary flexibility and efficiency needed in today’s commercial environments. With strong backing from Carrier, a leader in HVAC technology, the 30RAP series ensures lasting comfort and operational efficiency.