Carrier 30RAP010-060 installation instructions Install Accessories, Check Refrigerant Circuit

Page 29

POWER WIRING — All power wiring must comply with applicable local and national codes. Install field-supplied branch circuit fused disconnect per NEC (National Electric Code, U.S.A.) of a type can be locked OFF or ON. Disconnect must be within sight from and readily accessible from unit in compliance with NEC Article 440-14.

General Wiring Notes

1.The control circuit does NOT require a separate power source. Control circuit power is obtained by a step-down transformer from the main three-phase power supply. The LVT (low voltage terminal) strip is provided for field- wired control devices.

2.Cooler and pump heaters (if factory installed) are wired in the control circuit so they are operable as long as the main power supply to the unit is ON. A factory-installed and set overload device protects them.

NOTE: The field-supplied disconnect should never be off except when unit is being serviced or is to be down for a pro- longed period, in which case cooler should be drained.

3.Power entry is at the right-hand side of the unit when fac- ing the control box.

4.Maximum field wire sizes allowed by lugs on terminal block/non-fused disconnect are listed in Table 8.

5.Terminals for field power supply are suitable for copper conductors. Insulation must be rated 167 F (75 C) minimum.

FIELD CONNECTIONS

Main Power — Bring wires from the fused disconnect switch through hole in the middle of the right hand corner post to the bottom of the control box and connect to terminals on terminal block or non-fused disconnect. A 7/8-in. hole is provided in the corner post to locate the center of the field power entry. To comply with NEC Article 440-14, the disconnect must be lo- cated within sight from and readily accessible from unit. Refer to Fig. 19.

IMPORTANT: To ensure power to the heaters, make sure auxiliary power to the unit and the compressor circuit breakers is always on (except for servicing or prolonged shutdown).

CAUTION

Proper rotation of condenser fan(s) MUST be verified before pumps or compressors are started. Consult the Con- trols, Start-Up and Operation manual provided with this chiller for correct procedure. Improper pump rotation can cause permanent damage to pump impeller and housing. If pump(s) have been removed for trimming, verify that wir- ing is reconnected in the original manner.

Control Power — Control power is obtained from the main power supply and does NOT require a separate source. A toggle switch (marked Emergency On-Off on the unit label diagram and by the switch) allows the control circuit to be manually disconnected when necessary. Cooler and pump heaters (if installed) are in an operable state when this switch is in the Off position.

Step 6 — Install Accessories

ELECTRICAL — A number of electrical accessories are available to provide the following optional features (for details, refer to the Controls, Start-Up, Operation, Service, and Troubleshooting book):

Energy Management Module (Used for any of the following types of temperature reset, demand limit and ice features):

4 to 20 mA leaving fluid temperature reset (requires field-supplied 4 to 20 mA generator)

4 to 20 mA cooling set point reset (requires field- supplied 4 to 20 mA generator)

Discrete inputs for 2-step demand limit (requires field- supplied dry contacts)

4 to 20 mA demand limit (requires field-supplied 4 to 20 mA generator)

Discrete input for Ice Done switch (requires field- supplied dry contacts)

Navigator™ Display — The device provides hand-held, mobile capability using an easy to read 4-line display. The key- pad function is the same as the scrolling marquee module. A magnet is provided for ‘hands free’ service of components.

Low Ambient Operation — If outdoor ambient operating temperatures below 45 F (7 C) on size 018-030 units or 32 F (0° C) on size 035-060 units are expected, refer to separate in- stallation instructions for low-ambient operation using accesso- ry Motormaster® V control. Size 010 and 015 units have Mo- tormaster V installed as standard.

Minimum Load Accessory — If minimum load accessory is required, refer to unit Price Pages or contact your local Carrier representative for more details. For installation details, refer to separate installation instructions supplied with the accessory package.

Miscellaneous Accessories — For applications requiring spe- cial accessories, the following packages are available: external vibration, remote enhanced display, temperature reset, con- denser coil covers, storage tank, wind baffles, and remote cool- er. For installation details, refer to separate installation instruc- tions supplied with these accessory packages.

Step 7 — Check Refrigerant Circuit

LEAK TESTING — Units are shipped with complete operat- ing charge of R-410A (refer to physical data tables) and should be under sufficient pressure to conduct a leak test. Perform a leak test to ensure that leaks have not developed during unit shipment. Dehydration of the system is not required unless the entire refrigerant charge has been lost. Repair any leak found using good refrigeration practice.

DEHYDRATION — Refer to Carrier Standard Service Tech- niques Manual, Chapter 1, Refrigerants, Sections 6 and 7 for details. Do not use compressor to evacuate system.

REFRIGERANT CHARGE (Refer to Tables 1A and 1B) — Immediately after the condenser coil in each circuit is a 1/4-in. Schrader connection for charging liquid refrigerant.

Utilization of Novation condenser coil technology enables the 30RAP chiller to have a very low refrigerant charge. There- fore, if field charging is required, accurately charging to the correct quantity is very important. It is necessary to ensure that the system is completely evacuated before charging and that the refrigerant charge is accurately weighed to within 1% of the nameplate quantity or the unit may not operate correctly.

CAUTION

When charging, circulate water through the cooler at all times to prevent freezing. Freezing damage is considered abuse and may impair or otherwise negatively affect the Carrier warranty.

CAUTION

DO NOT OVERCHARGE system. Overcharging results in higher discharge pressure, increased power consump- tion, and possible compressor damage.

The suction lines are provided with a 1/4-in. Schrader fitting for connecting to low-side system pressure. The location of the suction access port is shown in Fig. 20.

29

Image 29
Contents Installation Instructions Quality Assurance A30-4861 Unit Operating WeightsUnit 30RAP Physical Data, 30RAP EnglishPhysical Data, 30RAP SI A30-4916 Check Compressor Mounting AsCooler Fluid and Drain Piping Con- nections A30-4948 Dimensions 30RAP010 and 015 UnitsA30-4949 Dimensions 30RAP018-030 UnitsDimensions 30RAP035-060 Units A30-4879 Accessory Storage Tank Dimensions 30RAP010,015 UnitsA30-4880 Accessory Storage Tank Dimensions 30RAP018-030 UnitsA30-4880 A30-4881 Accessory Storage Tank Dimensions 30RAP035-060 UnitsTypical Piping Diagram 30RAP Units with Hydronic Package A30-4635 Factor for Setting Tank PressureFill the Chilled Water Loop Water Quality Characteristics LimitationsTypical Set Up for Cleaning Process Head kPa as Read on Balancing Valve for 30RAP010-030 Head Ft Water as Read on Balancing Valve for 30RAP010-030Head Ft Water as Read on Balancing Valve for 30RAP035-060 Head kPa as Read on Balancing Valve for 30RAP035-060Heat Exchanger Pressure Drop 30RAP035-060 English Heat Exchanger Pressure Drop 30RAP035-060 SI Minimum Fluid Volume In CirculationMake Electrical Connections Wind Baffle Accessory Quantities30RAP Electrical Data No Hydronic Package Maximum Field Wiring Sizes38RAP Unit Voltage Pump Size 3 hp Pump Size 5 hp Pump Size 7.5 hp Hz 3 Ph 208/230-60 75.3 110 260.2 80.1 125 265.0 100 86.7 271.6 Fan Electrical Data Optional Value Sound Fans Fan Electrical Data Standard Low-Sound AeroAcoustic FansPump Electrical Data Accessory Tank Electrical DataPER Circuit RLA LRA Compressor Electrical DataCheck Refrigerant Circuit Install AccessoriesTypical Main Power and Control Connections Suction Access Port Sizes 018-030 Shown Units Without Hydronic Package English Unit Pressure Drop Curves, 30RAP010-060KPa Drop Water Pressure Liters/Second Appendix a Unit Pressure Drop Curves, 30RAP010-060Units with Single Pump Hydronic Package English Units with Single Pump Hydronic Package SI Units with Dual Pump Hydronic Package English Units with Dual Pump Hydronic Package SI Accessory Tank Flow Rate L/s Appendix a Pressure Drop Curves, Accessory Storage TanksPage Copyright 2009 Carrier Corporation
Related manuals
Manual 124 pages 40.33 Kb

30RAP010-060 specifications

The Carrier 30RAP010-060 is a series of rooftop air conditioning units designed for effective climate control in commercial applications. Engineered with advanced technologies, these units are known for their reliability, energy efficiency, and ease of installation, making them a suitable choice for a range of settings including offices, retail spaces, and industrial facilities.

One of the standout features of the 30RAP series is its robust construction. Designed to withstand various environmental conditions, these units come equipped with a weather-resistant cabinet and a corrosion-resistant finish. This durability ensures long-term performance and reduced maintenance costs.

Energy efficiency is a significant characteristic of the Carrier 30RAP series. These units utilize advanced technologies such as a high-efficiency compressor and variable speed fans. The inclusion of economizers also contributes to energy savings by allowing the system to take advantage of outdoor air when the conditions are favorable. With high SEER (Seasonal Energy Efficiency Ratio) ratings, the 30RAP units help businesses reduce operating costs while minimizing their environmental footprint.

The 30RAP series is equipped with smart control systems that provide enhanced operational efficiency and comfort. With features such as programmable thermostats and remote access capabilities, building managers can easily monitor and adjust the system to maintain optimal indoor climate conditions. Additionally, the units are compatible with building automation systems, allowing for seamless integration into a larger HVAC network.

The installation process of the Carrier 30RAP010-060 is streamlined thanks to a compact design and lightweight construction, which simplifies the transportation and placement on rooftops. Moreover, the unit's modular components facilitate easy access for maintenance and repairs, minimizing downtime and improving overall reliability.

In summary, the Carrier 30RAP010-060 series stands out for its combination of durability, energy efficiency, and advanced control technologies. It is an ideal solution for businesses seeking reliable climate control systems that balance performance with cost-effectiveness. Whether for new installations or replacements, these rooftop units provide the necessary flexibility and efficiency needed in today’s commercial environments. With strong backing from Carrier, a leader in HVAC technology, the 30RAP series ensures lasting comfort and operational efficiency.