Chapter 1: Specifications
1. Specifications
Cable Knockout Size — (2) 2.4" (6.1 cm) diameter sliding grommet on top rear of cabinet;
(1)2.4" x 13.7" (6.1 x 34.8 cm) brush grommet on bottom rear of cabinet Fans — QC12UBE, QC12UWA, QC12ULG: (1)
Total Maximum Airflow: 276 CFM;
Total Maximum Power Consumption: 36 W;
QC24UBE, QC24UWA, QC24ULG: (2)
Total Maximum Airflow: 552 CFM;
Total Maximum Power Consumption: 72 W;
QC42UBE, QC42UWA, QC42ULG: (3)
Total Maximum Airflow: 828 CFM;
Total Maximum Power Consumption: 108 W
Light — 8 W T5 fluorescent (F8T5/D)
Maximum Heat Load — QC12UBE, QC12UWA, QC12ULG: 1.2 kW; QC24UBE, QC24UWA, QC24ULG: 2.4 kW;
QC42UBE, QC42UWA, QC42ULG: 3.6 kW
Weight Capacity — QC12UBE, QC12UWA, QC12ULG: 1100 lb. (499 kg); QC24UBE, QC24UWA, QC24ULG, QC42UBE, QC42UWA, QC42ULG:
1760 lb. (798 kg)
Noise Reduction — Up to 15 dB
Rack Units — 12U, 24U, or 42U
RoHS — Yes
Size — QC12UBE, QC12UWA, QC12ULG:
External: 27.7"H x 29.5"W x 44.6"D (70.4 x 75 x 113.2 cm),
Internal: 21.8"H x 22.4"W x 40"D (55.4 x 56.9 x 101.6 cm) QC24UBE, QC24UWA, QC24ULG:
External: 48.7"H x 29.5"W x 44.6"D (123.8 x 75 x 113.2 cm);
Internal: 43.8"H x 22.4"W x 40"D (111.2 x 56.9 x 101.6 cm); QC42UBE, QC42UWA, QC42ULG:
External: 81"H x 29.5"W x 44.6"D (203.8 x 75 x 113.2 cm);
Internal: 74"H x 22.5"W x 40.5"D (187.9 x 57.2 x 102.8 cm)
| Page 7 |