Carrier 24ANA Stage Control, Field Connections, Stage Compressor, Compressor Internal Relief

Page 11

Table 5 – 2---Stage Compressor

(Winding Resistance at 70_F ± 20_ / 21.11_C ± 11.11_C)

Winding

24ANA724

24ANA736

24ANA748

24ANA760

Start (S---C)

2.74

1.98

1.55

0.74

Run (R---C)

0.80

0.75

0.48

0.36

 

 

 

 

 

Winding

24ANA124

24ANA136

24ANA148

24ANA160

Start (S---C)

1.40

1.29

1.52

0.60

Run (R--- C)

1.32

0.89

0.64

0.49

MAJOR COMPONENTS

2-Stage Control

The 2-stage control board controls the following functions:

-Low- and high-stage compressor contactor operation

-Outdoor fan motor operation

-Low ambient cooling

-Crankcase heater operation

-Compressor external protection

-Pressure switch monitoring

-Time delays

-On 24ANA7 models, start relay and capacitor

Field Connections

On 24ANA7 models with non-communicating (non-Infinity) system, the 2-stage control receives 24vac low-voltage control system inputs through the R, C, Y1, and Y2 connections located at the bottom of the control board (see Fig. 6). The 24ANA7 can be controlled using a standard 2-stage thermostat or Infinity User Interface.

All 24ANA1 models are part of a complete Infinity communicating system and use only the ABCD connections on the circuit board. The 24ANA1 must be controlled using an Infinity User Interface for proper equipment staging and operation

2-Stage Compressor

The 2-stage compressor contains motor windings that provide 2-pole (3500 RPM) operation. Refer to Table 5 for correct winding resistance.

Compressor Internal Relief

The compressor is protected by an internal pressure relief (IPR) which relieves discharge gas into compressor shell when differential between suction and discharge pressures exceeds 500 - 550 psi on 24ANA7 models and 550 - 625 psi on 24ANA1 models. The compressor is also protected by an internal overload attached to motor windings.

Compressor Control Contactors

The contactor(s) have a 24 volt coil. The electronic control board controls the operation of the appropriate contactors.

TEMPERATURE THERMISTORS

Thermistors are electronic devices which sense temperature. As the temperature increases, the resistance decreases. Thermistors are used to sense outdoor ambient (OAT) and coil temperature (OCT). Refer to Fig. 7 for resistance values versus temperature.

If the outdoor ambient or coil thermistor should fail, the control will flash the appropriate fault code (see Table 6.)

THERMISTOR CURVE

 

90

(KOHMS)

80

70

 

 

60

RESISTANCE

50

20

 

40

 

30

 

10

 

0

0

20

40

60

80

100

120

(-17.77)

(-6.67)

(4.44)

(15.56)

(26.67)

(37.78)

(48.89)

 

 

TEMPERATURE °F (°C)

 

 

A08054

Fig. 7 - Resistance Values Versus Temperature

IMPORTANT: Outdoor air thermistor and coil thermistor are factory mounted in the final locations. Check to insure thermistors are mounted properly per Fig. 8 and Fig. 9.

Thermistor Sensor Comparison

The control continuously monitors and compares the outdoor air temperature sensor and outdoor coil temperature sensor to ensure proper operating conditions. The comparison is:

SIf the outdoor air sensor indicates 10_F/5.56_C warmer than the coil sensor (or) the outdoor air sensor indicates 20_F/11.11_C cooler than the coil sensor, the sensors are out of range.

If the sensors are out of range, the control will flash the appropriate fault code as shown in Table 6.

The thermistor comparison is not performed during low ambient cooling or defrost operation.

Failed Thermistor Default Operation

Factory defaults have been provided in the event of failure of outdoor air thermistor and/or coil thermistor.

If the OAT sensor should fail, low ambient cooling will not be allowed and the one-minute outdoor fan off delay will not occur.

If the OCT sensor should fail, low ambient cooling will not be allowed.

24ANA

11

Image 11
Contents Electrical Shock Hazard Safety ConsiderationsUnit Operation and Safety Hazard Indoor Thermostat Control OptionsCheck Equipment and Job Site Installation RecommendationsInstallation Install on a Solid, Level Mounting PadPersonal Injury and Environmental Hazard Operating AmbientMake Piping Connections Outdoor Unit Connected to Factory Approved Indoor UnitSweat Connection Install Liquid-Line Filter Drier IndoorAccessory Usage Refrigerant Tubing Connection OutdoorCompressor Crankcase Heater Install AccessoriesMake Electrical Connections Environmental Hazard START-UPMake Airflow Selections System Functions And Sequence Of Operation Outdoor Fan Motor Operation Time DelaysCompressor Operation on 24ANA1 Models Crankcase Heater OperationCheck Charge TroubleshootingContactor Shorted Detection 230V Line Power Disconnect DetectionUnloader Test Procedure Compressor Voltage SensingStage Compressor Failed Thermistor Default OperationStage Control Field ConnectionsFinal Checks Care and MaintenanceExample TroubleshootingStatus Codes Volt Factory Wiring Puronr R-410A Refrigerant Quick Reference Guide Catalog No 24ANA---6SI