PURONR (R-410A) REFRIGERANT QUICK REFERENCE GUIDE

S Puron refrigerant operates at 50-70 percent higher pressures than R-22. Be sure that servicing equipment and replacement components are designed to operate with Puron refrigerant

S Puron refrigerant cylinders are rose colored.

S Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.

S Puron refrigerant systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose when charging into suction line with compressor operating

S Manifold sets should be 700 psig high side and 180 psig low side with 550 psig low-side retard. S Use hoses with 700 psig service pressure rating.

S Leak detectors should be designed to detect HFC refrigerant.

S Puron refrigerant, as with other HFCs, is only compatible with POE oils. S Vacuum pumps will not remove moisture from oil.

S Do not use liquid-line filter driers with rated working pressures less than 600 psig. S Do not leave Puron suction line filter driers in line longer than 72 hours.

S Do not install a suction-line filter drier in liquid line.

S POE oils absorb moisture rapidly. Do not expose oil to atmosphere. S POE oils may cause damage to certain plastics and roofing materials. S Wrap all filter driers and service valves with wet cloth when brazing. S A factory approved liquid-line filter drier is required on every unit.

S Do NOT use an R-22 TXV.

S If indoor unit is equipped with an R-22 TXV or piston metering device, it must be changed to a hard shutoff balanced port Puron TXV. S Never open system to atmosphere while it is under a vacuum.

S When system must be opened for service, recover refrigerant, evacuate then break vacuum with dry nitrogen and replace filter driers. Evacuate to 500 microns prior to recharging.

S Do not vent Puron refrigerant into the atmosphere. S Do not use capillary tube coils.

S Observe all warnings, cautions, and bold text.

S All indoor coils must be installed with a hard shutoff balanced port Puron TXV metering device.

24ANA

15

Image 15
Contents Electrical Shock Hazard Safety ConsiderationsUnit Operation and Safety Hazard Indoor Thermostat Control OptionsCheck Equipment and Job Site Installation RecommendationsInstallation Install on a Solid, Level Mounting PadPersonal Injury and Environmental Hazard Operating AmbientMake Piping Connections Outdoor Unit Connected to Factory Approved Indoor UnitSweat Connection Install Liquid-Line Filter Drier IndoorAccessory Usage Refrigerant Tubing Connection OutdoorInstall Accessories Make Electrical ConnectionsCompressor Crankcase Heater START-UP Make Airflow SelectionsEnvironmental Hazard System Functions And Sequence Of Operation Outdoor Fan Motor Operation Time DelaysCompressor Operation on 24ANA1 Models Crankcase Heater OperationCheck Charge TroubleshootingContactor Shorted Detection 230V Line Power Disconnect DetectionUnloader Test Procedure Compressor Voltage SensingStage Compressor Failed Thermistor Default OperationStage Control Field ConnectionsFinal Checks Care and MaintenanceTroubleshooting Status CodesExample Volt Factory Wiring Puronr R-410A Refrigerant Quick Reference Guide Catalog No 24ANA---6SI