System Functions And Sequence Of Operation

The outdoor unit control system has special functions. The following is an overview of the 2-stage control functions:

Cooling Operation

24ANA7 and 24ANA1 (containing circuit board HK38EA015 or newer) models utilize either a 2-stage cooling indoor thermostat or an Infinity communicating User Interface. With a call for first stage cooling, the outdoor fan and low-stage compressor are energized. If low-stage cannot satisfy cooling demand, high-stage is energized by the second stage of indoor thermostat or User Interface. After second stage is satisfied, the unit returns to low-stage operation until first stage is satisfied or until second stage is required again. When both first stage and second stage cooling are satisfied, the compressor will shut off.

NOTE: On 24ANA7 models, if unit has not operated within the past 12 hrs, or following a unit power-up, upon the next thermostat high- or low-stage demand, unit operates for a minimum of 5 minutes in high-stage.

NOTE: With non-communicating (non-Infinity) systems, with first stage of cooling, (Y1) is powered on; and with second stage of cooling, (Y1 and Y2) are on.

NOTE: When 2-stage unit is operating at low-stage, system vapor (suction) pressure will be higher than a standard single-stage system or high-stage operation.

NOTE: Outdoor fan motor will continue to operate for one minute after compressor shuts off, when outdoor ambient is greater than or equal to 100_F (37.78_C). This reduces pressure differential for easier starting on the next cycle.

Communication and Status Function Lights

For Infinity Control Only, Green communications (COMM) Light

A green LED (COMM light) on the outdoor board (see Fig. 6) indicates successful communication with the other system

products. The green LED will remain OFF until communications is established. Once a valid command is received, the green LED will turn ON continuously. If no communication is received within 2 minutes, the LED will be turned OFF until the next valid communication.

Amber Status Light

An amber colored STATUS light is used to display the operation mode and fault codes as specified in the troubleshooting section. See Table 6 for codes and definitions.

NOTE: Only one code will be displayed on the outdoor unit control board (the most recent, with the highest priority).

Utility Interface

With Infinity Control

The utility curtailment relay should be wired between R and Y2 connections on the control board for Infinity Communicating Systems only (see Fig. 6.) This input allows a power utility device to interrupt compressor operation during peak load periods. When the utility sends a signal to shut the system down, the User Interface will display, “Curtailment Active”.

One Minute Stage Change Time Delay on 24ANA7 Models

When compressor changes stages from high to low or low to high, there is a 1-minute time delay before compressor restarts. The outdoor fan motor remains running.

Compressor Operation on 24ANA7 Models

When the compressor operates in high-stage operation, the motor rotates clockwise. Both the lower and upper pistons are eccentric with the rotating crankshaft and both compress refrigerant.

When the compressor operates in low-stage operation the motor reverses direction (rotates counterclockwise). The lower piston becomes idle and the upper piston compresses refrigerant. The start and run windings are reversed.

24ANA

UTILITY RELAY *

UTILITY SIGNAL

OPEN RELAY

MODEL

PLUG

LLS

* SUPPLIED BY UTILITY PROVIDER

Liquid Line Solenoid

A06526

Fig. 6 - 2-Stage Control Board

7

Image 7
Contents Electrical Shock Hazard Safety ConsiderationsUnit Operation and Safety Hazard Indoor Thermostat Control OptionsCheck Equipment and Job Site Installation RecommendationsInstallation Install on a Solid, Level Mounting PadPersonal Injury and Environmental Hazard Operating AmbientMake Piping Connections Outdoor Unit Connected to Factory Approved Indoor UnitSweat Connection Install Liquid-Line Filter Drier IndoorAccessory Usage Refrigerant Tubing Connection OutdoorMake Electrical Connections Install AccessoriesCompressor Crankcase Heater Make Airflow Selections START-UPEnvironmental Hazard System Functions And Sequence Of Operation Outdoor Fan Motor Operation Time DelaysCompressor Operation on 24ANA1 Models Crankcase Heater OperationCheck Charge TroubleshootingContactor Shorted Detection 230V Line Power Disconnect DetectionUnloader Test Procedure Compressor Voltage SensingStage Compressor Failed Thermistor Default OperationStage Control Field ConnectionsFinal Checks Care and MaintenanceStatus Codes TroubleshootingExample Volt Factory Wiring Puronr R-410A Refrigerant Quick Reference Guide Catalog No 24ANA---6SI