Status Codes
Table 6 shows the status codes flashed by the amber status light. Most system problems can be diagnosed by reading the status code as flashed by the amber status light on the control board.
The codes are flashed by a series of short and long flashes of the status light. The short flashes indicate the first digit in the status code, followed by long flashes indicating the second digit of the error code. The short flash is 0.25 seconds ON and the long flash is 1.0 second ON. Time between flashes is 0.25 seconds. Time
between short flash and first long flash is 1.0 second. Time between code repeating is 2.5 seconds with LED OFF.
Count the number of short and long flashes to determine the appropriate flash code. Table 6 gives possible causes and actions related to each error.
EXAMPLE:
3 short flashes followed by 2 long flashes indicates a 32 code. Table 6 shows this to be low pressure switch open.
Table 6 – TROUBLESHOOTING
|
| AMBER |
| |
OPERATION | FAULT | LED | POSSIBLE CAUSE AND ACTION | |
FLASH | ||||
|
|
| ||
|
| CODE |
| |
Standby – no call for unit operation | None | On solid, no | Normal operation | |
flash | ||||
|
|
| ||
None | 1, pause | Normal operation | ||
high | None | 2, pause | Normal operation | |
| System Commu- | 16 | Communication with user interface lost. Check wiring to User Interface, | |
| nications Failure |
| indoor and outdoor units | |
|
|
|
| |
| Invalid Model Plug | 25 | Control does not detect a model plug or detects an invalid model plug. Unit | |
| will not operate without correct model plug. | |||
|
|
| ||
| High Pressure | 31* | High | |
| Switch Open | and coils for airflow restrictions. | ||
|
| |||
| Low Pressure | 32* | Low pressure switch trip. Check refrigerant charge and indoor air flow | |
| Switch Open | |||
|
|
| ||
| Control Fault | 45 | Outdoor unit control board has failed. Control board needs to be replaced. | |
| Brown Out (230 v) | 46 | Line voltage < 187v for at least 4 seconds. Compressor and fan operation | |
| not allowed until voltage>190v. Verify line voltage. | |||
|
|
| ||
|
|
| There is no 230v at the contactor when indoor unit is powered and cooling/ | |
| No 230v at Unit | 47 | heating demand exists. Verify the disconnect is closed and 230v wiring is | |
|
|
| connected to the unit. | |
| Outdoor Air Temp | 53 | Outdoor air sensor not reading or out of range. Ohm out sensor and check | |
| Sensor Fault | wiring. | ||
|
| |||
| Outdoor Coil Sen- | 55 | Coil sensor not reading or out of range. Ohm out sensor and check wiring. | |
| sor Fault | |||
|
|
| ||
| Thermistors out of | 56 | Improper relationship between coil sensor and outdoor air sensor. Ohm out | |
| range | sensors and check wiring. | ||
|
| |||
|
| Compressor operation detected then disappears while | ||
| 71* | exists. Possible causes are internal compressor overload trip or start relay | ||
| mal Cutout | |||
|
| and capacitor held in circuit too long(if installed) | ||
|
|
| ||
| high |
| Compressor operation detected then disappears while high | |
| 72* | exists. Possible causes are internal compressor overload trip or start relay | ||
| mal Cutout | |||
|
| and capacitor held in circuit too long (if installed) | ||
|
|
| ||
| Contactor Shorted | 73 | Compressor voltage sensed when no demand for compressor operation | |
| exists. Contactor may be stuck closed or there is a wiring error. | |||
|
|
| ||
| No 230V at Com- |
| Compressor voltage not sensed when compressor should be starting. Con- | |
| pressor | 74 | ||
| tactor may be stuck open or there is a wiring error. | |||
| (24ANA1 Only) |
| ||
|
|
| ||
|
| Specified start voltage at VR terminal was not achieved in | ||
| Start | 75 | ||
| relay was | |||
| (24ANA7 Only) |
| ||
|
|
| ||
|
| For 3 consecutive | ||
| Start 3 times | 76 | was not achieved & start relay was | |
| (24ANA7Only) |
| 30 minutes. | |
| high |
| Specified start voltage at VS terminal was not achieved in high | |
| Not Start | 77 | ||
| relay was | |||
| (24ANA7 Only) |
| ||
|
|
| ||
| high |
| For 3 consecutive high | |
| Not Start 3 times | 78 | nal was not achieved & start relay was | |
| (24ANA7 Only) |
| out for 30 minutes. | |
| 81 | Thermal cutout occurs in three consecutive low/ high | ||
| mal Lockout | stage locked out for 4 hours or until 24v power recycled. | ||
|
| |||
| high | 82 | Thermal cutout occurs in three consecutive | |
| mal Lockout | stage locked out for 4 hours or until 24v power recycled. | ||
|
| |||
| Low Pressure | 83 | Low pressure switch trip has occurred during 3 consecutive cycles. Unit | |
| Lockout | operation locked out for 4 hours or until 24v power recycled. | ||
|
| |||
| High Pressure | 84 | High pressure switch trip has occurred during 3 consecutive cycles. Unit | |
| Lockout | operation locked out for 4 hours or until 24v power recycled. | ||
|
| |||
| Low Contactor |
| Compressor voltage not sensed when compressor should be starting. | |
| Open | 85 | ||
| stage contactor may be stuck open or there is a wiring error. | |||
| (24ANA7 Only) |
| ||
|
|
| ||
| High Contactor |
| Compressor voltage not sensed when compressor should be starting. high | |
| Open | 87 | ||
| stage contactor may be stuck open or there is a wiring error. | |||
| (24ANA7 Only) |
| ||
|
|
|
*Sequence: Compressor contactor is