Carrier 30RA Electrical connections and refrigerant charge, Liquid refrigerant charge, Example

Page 10

30RA/30RH

Electrical connections and refrigerant charge

E N G L I S H

Electrical connections

WARNING:

To prevent electrical shock or equipment damage, make sure disconnects are open before electrical connections are made. If this action is not taken, personal injury may occur.

Power supply cable size and external connection must be made by the installer according to the unit installation characteristics and the applicable standards. The power supply and earthing multicore cable of the unit must be connected to the main disconnecting switch by passing it through the grommet on the front pedestal after removing the lateral access panel. The maximum section allowable for flexible copper cable is 25 mm2.

Before connection, check that phase sequence L1 – L2 – L3 is correct.

Take special care when making the earth connection.

The maximum permitted voltage and current imbalance is 10% of the values indicated in Table II.

Contact your local power company for correction of an incorrect line voltage.

Before selecting the power supply line fuses - which must be of the type "gG" - check the voltage and the size indicated on the unit name plate is.

WARNING:

Operation of the unit on improper line voltage constitutes abuse and is not covered by the Carrier warranty.

IMPORTANT:

To ensure the correct unit power supply (cable entry, conductor cross section, protection devices etc.), consult the electrical data table, the wiring diagram supplied with the unit and the applicable standards concerning the installation of air conditioning equipment.

Never operate a unit if the voltage imbalance exceeds 2%.

The following formula must be used to determine the percentage of voltage imbalance.

Voltage imbalance (%) =

Largest deviation from average voltage x 100

———————————————————————————-

Average voltage

Example:

Nominal supply: 400-3-50

AB =

404 V

 

BC =

399 V

Motor

AC =

394 V

 

Average voltage = 404 + 399 + 394 = 399 400 V 3

Determine maximum deviation from average voltage

AB = 404 - 400 = 4

BC = 400 - 399 = 1

AC = 400 - 394 = 6

Largest deviation is 6 volts. Percentage voltage imbalance is therefore:

6x 100 = 1,5 %

400

CAUTION:

The installer must install protection devices, as required by the applicable legislation.

Liquid refrigerant charge

Checking the charge

WARNING:

When adjusting the refrigerant charge always ensure that water is circulating in the heat exchanger to prevent any possibility of freezing up. Damage caused by freezing is not covered by the product warranty.

30RA-RH units are shipped with a full operating charge of refrigerant. Refer to Table I.

If it is nevertheless necessary to add more refrigerant, run the unit for some time in cooling mode and then slowly add liquid refrigerant into the suction side until there are no bubbles in the sight glass.

WARNING:

To ensure proper operation of 30RA-RH units there must be at least 5 K of subcooling as the liquid refrigerant enters the expansion valve.

30RA-RH units use a HFC-407C refrigerant charge. For your information, we are reproducing here some extracts from the official publication dealing with the design, installation, operation and maintenance of air conditioning and refrigeration systems and the training of people involved in these activities, agreed by the air conditioning and refrigeration industry.

Refrigerant guidelines

Refrigeration installations must be inspected and maintained regularly and rigorously by specialists. Their activities must be overseen and checked by properly trained people.

To minimise discharge to the atmosphere, refrigerants and lubricating oil must be transferred using methods which reduce leaks and losses to a minimum.

Leaks must be repaired immediately.

Service valves fitted to the flow and return lines permit charge transfer to a suitably arranged external container.

It is indispensable to use a dedicated transfer station.

Compressor lubricating oil contains refrigerant. Any oil drained from a system during maintenance must therefore be handled and stored accordingly.

Refrigerant under pressure must never be discharged to the atmosphere.

Recharging liquid refrigerant

CAUTION:

30RA-RH units are charged with liquid HFC-407C refrigerant.

This non-azeotropic refrigerant blend consists of 23% R-32, 25% of R-125 and 52% R-134a, and is characterised by the fact that at the time of the change in state the temperature of the liquid/vapour mixture is not constant, as with azeotropic refrigerants.

All checks must be pressure tests, and the appropriate pressure/ temperature ratio table must be used for the interpretation of the values.

Leak detection is especially important for units charged with refrigerant R-407C.

Depending on whether the leak occurs in the liquid or in the vapour phase, the proportion of the different components in the remaining fluid is not the same.

NOTE:

Regularly carry out leak checks and immediately repair any leak found.

GB - 9

Image 10
Contents Aquasnap 30RA / 30RH Contents 30RA/30RHTable I Physical data Model RA Physical data and electrical data Model RATable II Electrical data Model RA Table I Physical data Model RH Physical data and electrical data Model RHTable II Electrical data Model RH Dimensions and location of hydraulic connections mm Mod RA 026General information and hydronic module Unit installationHydronic module Typical water circuit diagram for units with hydronic module Water connectionsFor use with propylene Ethylene glycol curvePump leakproof GlycolWater pressure drop of the unit without hydronic module Liquid refrigerant charge Electrical connections and refrigerant chargeElectrical connections ExampleRefrigerant charge and electronic control Electronic controlNecessary checks/precautions before start-up Compressor replacementPump replacement Start-up30RH Operating limits Table III Pressure switch settings30RA Operating limits Operating range 30RA unitsMaintenance General maintenanceFinal recommendations Troubleshooting L010126H27 Via R. Sanzio, 9 20058 Villasanta MI Italy Tel /3636.1

30RH, 30RA specifications

Carrier has long been a leader in the heating, ventilation, and air conditioning (HVAC) industry, and the Carrier 30RH and 30RA series showcases this legacy through a combination of advanced technology, energy efficiency, and reliability. These models are designed to meet the diverse needs of both commercial and industrial facilities, providing optimal comfort and air quality.

One of the standout features of the Carrier 30RH and 30RA series is their versatility. These models are equipped with high-efficiency scroll compressors that offer exceptional performance while keeping energy consumption low. This not only translates to reduced operational costs but also helps in meeting stringent environmental regulations. The compressors work efficiently across a range of operating conditions, making these units suitable for various climates and applications.

Incorporating innovative technologies, the Carrier 30RH and 30RA series utilizes advanced controls to optimize performance. The carrier’s proprietary control system allows for seamless integration with building management systems, enabling remote monitoring and management. This connectivity ensures that operators can track energy usage and system performance in real-time, facilitating maintenance and problem-solving before issues escalate.

Both models include high-efficiency heat exchangers that enhance the heat transfer process, further promoting energy savings. The units are also designed to minimize sound levels, making them ideal for installation in noise-sensitive environments. With noise reduction features, the Carrier 30RH and 30RA units operate quietly, ensuring comfort in spaces where silence is paramount.

Durability is another core characteristic of these models. Built with robust materials and innovative engineering, the 30RH and 30RA series is designed to withstand the rigors of demanding commercial and industrial applications. Their reliable performance over time is backed by rigorous testing, ensuring longevity and reducing the likelihood of unexpected failures.

Environmental sustainability is a priority for Carrier, and the 30RH and 30RA series reflect this commitment. By utilizing environmentally friendly refrigerants and energy-efficient technologies, these units significantly reduce greenhouse gas emissions.

In summary, the Carrier 30RH and 30RA series are exemplary models that combine efficiency, advanced technology, and reliability. Their design focuses on optimizing comfort, reducing energy consumption, and ensuring longevity, making them an excellent choice for any commercial or industrial installation. Whether it’s in a bustling city center or a quiet suburban area, these units are engineered to deliver exceptional performance and value throughout their lifecycle.