Start-up, compressor and pump replacement, unit protection devices E N G L I S H

Start-up

Unit start-up is done by the electronic control described above, and must always be carried out under the supervision of a qualified air conditioning engineer.

Necessary checks/precautions before start-up

-Ensure that all electrical connections are properly tightened.

-Ensure that the unit is level and well-supported.

-Check that the hydraulic circuit has sufficient water flow and that the pipe connections correspond to the installation diagram.

-Ensure that there are no water losses. Check the correct operation of the valves installed.

-All panels should be fitted and firmly secured with the corresponding screws.

-Make sure that there is sufficient space for servicing and maintenance purposes.

-Ensure that there are no refrigerant leaks.

-Confirm that the electrical power source agrees with the unit nameplate rating, wiring diagram and other documentation for the unit.

-Ensure that the power supply corresponds to the applicable standards.

-Make sure that compressors float freely on the mounting springs.

Compressor replacement

As the compressors are hermetic, when an internal fault occurs, the compressor must be replaced.

This must be done as detailed below:

-Disconnect the unit from the electrical supply.

-Remove the access panels.

-Remove the gas from the refrigerant circuit using recovery equipment to avoid harming the atmosphere.

-Electrically disconnect the compressor.

-Unbraze or unscrew the suction and discharge lines, taking care not to damage the rest of the components.

-Remove the compressor fastenings.

-Replace the compressor, ensuring that it contains sufficient oil.

-Braze or screw in the lines.

-Connect the compressor according to the wiring diagram.

-Evacuate the compressor.

-Introduce the quantity of refrigerant indicated on the nameplate through the service couplings located on the high and low pressure side.

NOTE:

This operation must be carried out by a qualified person.

Pump replacement

If the water pump needs to be replaced, proceed as follows:

-Disconnect the unit from the power supply.

-Remove the access panel.

-Electrically disconnect the pump.

-Empty all water from the hydronic module.

-Loosen the pipe unions a and c.

-Remove the four pump fixing screws b.

-Replace the pump.

-Fit the pump fixing screws b.

-Tighten the pipe unions a and c.

-Electrically connect the pump

-Connect the unit to the power supply

-Make sure the pump rotates in the right direction using the hole in the back panel.

-Reinstall the lateral access panel.

Pipe union

Screw

Pipe union

Description of unit protection devices

The unit includes the following protection devices:

-Internal compressor protection.

-Fan motor internal thermal protection.

-Main switch.

-Anti-short-cycle protection.

-Thermomagnetic main switch.

-Thermomagnetic control switch.

-Fans and electric heaters thermomagnetic switch.

-Defrost thermostat.

-Fault detector for the temperature and pressure sensors.

-High pressurestat: this protects the unit against excessive condensing pressure.

The high pressurestat has factory-fixed non-adjustable settings. The appliance stops due to the intervention of the high pressure alarm threshold, before the high pressurestat intervenes.

This function is performed by the electronic control device via a pressure transducer.

-Low pressurestat: This function is performed by the electronic control device via a pressure transducer.

Only on appliances with hydronic module

- Pump motor external thermal protection.

GB - 11

Image 12
Contents Aquasnap 30RA / 30RH Contents 30RA/30RHPhysical data and electrical data Model RA Table I Physical data Model RATable II Electrical data Model RA Physical data and electrical data Model RH Table I Physical data Model RHTable II Electrical data Model RH Dimensions and location of hydraulic connections mm Mod RA 026Unit installation General information and hydronic moduleHydronic module Typical water circuit diagram for units with hydronic module Water connectionsEthylene glycol curve Pump leakproofFor use with propylene GlycolWater pressure drop of the unit without hydronic module Electrical connections and refrigerant charge Electrical connectionsLiquid refrigerant charge ExampleRefrigerant charge and electronic control Electronic controlCompressor replacement Pump replacementNecessary checks/precautions before start-up Start-upTable III Pressure switch settings 30RA Operating limits30RH Operating limits Operating range 30RA unitsGeneral maintenance MaintenanceFinal recommendations Troubleshooting L010126H27 Via R. Sanzio, 9 20058 Villasanta MI Italy Tel /3636.1

30RH, 30RA specifications

Carrier has long been a leader in the heating, ventilation, and air conditioning (HVAC) industry, and the Carrier 30RH and 30RA series showcases this legacy through a combination of advanced technology, energy efficiency, and reliability. These models are designed to meet the diverse needs of both commercial and industrial facilities, providing optimal comfort and air quality.

One of the standout features of the Carrier 30RH and 30RA series is their versatility. These models are equipped with high-efficiency scroll compressors that offer exceptional performance while keeping energy consumption low. This not only translates to reduced operational costs but also helps in meeting stringent environmental regulations. The compressors work efficiently across a range of operating conditions, making these units suitable for various climates and applications.

Incorporating innovative technologies, the Carrier 30RH and 30RA series utilizes advanced controls to optimize performance. The carrier’s proprietary control system allows for seamless integration with building management systems, enabling remote monitoring and management. This connectivity ensures that operators can track energy usage and system performance in real-time, facilitating maintenance and problem-solving before issues escalate.

Both models include high-efficiency heat exchangers that enhance the heat transfer process, further promoting energy savings. The units are also designed to minimize sound levels, making them ideal for installation in noise-sensitive environments. With noise reduction features, the Carrier 30RH and 30RA units operate quietly, ensuring comfort in spaces where silence is paramount.

Durability is another core characteristic of these models. Built with robust materials and innovative engineering, the 30RH and 30RA series is designed to withstand the rigors of demanding commercial and industrial applications. Their reliable performance over time is backed by rigorous testing, ensuring longevity and reducing the likelihood of unexpected failures.

Environmental sustainability is a priority for Carrier, and the 30RH and 30RA series reflect this commitment. By utilizing environmentally friendly refrigerants and energy-efficient technologies, these units significantly reduce greenhouse gas emissions.

In summary, the Carrier 30RH and 30RA series are exemplary models that combine efficiency, advanced technology, and reliability. Their design focuses on optimizing comfort, reducing energy consumption, and ensuring longevity, making them an excellent choice for any commercial or industrial installation. Whether it’s in a bustling city center or a quiet suburban area, these units are engineered to deliver exceptional performance and value throughout their lifecycle.