A list of possible faults, as well as the probable cause and suggested solutions is shown as follows. In the event of a unit malfunction it is recommended to disconnect the power supply and ascertain the cause.

SymptomsCause REMEDY

Unit does not start:

- No power supply;

CONNECT POWER SUPPLY.

- Main switch open;

CLOSE SWITCH.

- Low line voltage;

CHECK VOLTAGE AND REMEDY THE DEFICIENCY.

- A protection has tripped;

RESET.

- Contactor stuck open;

CHECK AND IF NECESSARY REPLACE CONTACTOR.

- Seized compressor;

CHECK AND IF NECESSARY REPLACE COMPRESSOR.

- Loose electrical connections;

CHECK CONNECTIONS.

Unit runs continuously or starts and stops frequently:

-Defective compressor contactor;

-CHECK AND IF NECESSARY REPLACE CONTACTOR.

-Defective compressor;

CHECK AND IF NECESSARY REPLACE COMPRESSOR.

- Refrigerant losses;

CHECK AND ADD THE NECESSARY QUANTITY.

- Total water flow too low

CHECK FOR PRESSURE DROP IN THE HYDRAULIC CIRCUIT.

-Static pressure in the hydraulic circuit too low;

CHECK IT ON THE PRESSURE GAUGE AND RESTORE IT IF NECESSARY.

Unit continuously cuts out at low pressure:

- Refrigerant losses;

CHECK AND ADD THE NECESSARY QUANTITY.

- Low water flow in the exchanger;

CHECK WATER PUMP.

- Unit start-up delay;

WAIT UNTIL THE SYSTEM HAS STABILISED.

Unit continuously cuts out at high pressure:

- Defective high pressurestat;

CHECK AND IF NECESSARY REPLACE PRESSURESTAT.

- Blocked expansion valve;

CHECK AND REPLACE IF NECESSARY.

- Blocked filter drier;

CHECK AND IF NECESSARY REPLACE FILTER.

- The outdoor fan/s does/do not work;

CHECK THE CONDITION OF THE FAN MOTOR/S AND ITS/THEIR ELECTRICAL CONNECTIONS.

-Obstructed or dirty battery;

REMOVE THE OBSTRUCTION OR CLEAN THE BATTERY.

Abnormal system noise:

- Piping vibration;

SUPPORT PIPING.

- Noisy compressor;

CHECK AND CHANGE IF NECESSARY.

- Hissing expansion valve;

CHECK AND ADD REFRIGERANT IF NECESSARY.

- Badly fitting panels;

INSTALL CORRECTLY.

Compressor loses oil:

- Leaking refrigeration circuit;

REPAIR LEAK.

Water loss:

- Defective entering or leaving connections;

CHECK AND TIGHTEN IF NECESSARY.

The unit does not defrost (only for 30RH units):

- Four-way reversing valve faulty;

CHECK AND REPLACE THE VALVE IF NECESSARY.

- Defrost sensor broken;

CHECK AND REPLACE THE SENSOR IF NECESSARY.

GB - 14

Image 15
Contents Aquasnap 30RA / 30RH 30RA/30RH ContentsPhysical data and electrical data Model RA Table I Physical data Model RATable II Electrical data Model RA Physical data and electrical data Model RH Table I Physical data Model RHTable II Electrical data Model RH Mod RA 026 Dimensions and location of hydraulic connections mmUnit installation General information and hydronic moduleHydronic module Water connections Typical water circuit diagram for units with hydronic moduleGlycol Ethylene glycol curvePump leakproof For use with propyleneWater pressure drop of the unit without hydronic module Example Electrical connections and refrigerant chargeElectrical connections Liquid refrigerant chargeElectronic control Refrigerant charge and electronic controlStart-up Compressor replacementPump replacement Necessary checks/precautions before start-upOperating range 30RA units Table III Pressure switch settings30RA Operating limits 30RH Operating limitsGeneral maintenance MaintenanceFinal recommendations Troubleshooting Via R. Sanzio, 9 20058 Villasanta MI Italy Tel /3636.1 L010126H27

30RH, 30RA specifications

Carrier has long been a leader in the heating, ventilation, and air conditioning (HVAC) industry, and the Carrier 30RH and 30RA series showcases this legacy through a combination of advanced technology, energy efficiency, and reliability. These models are designed to meet the diverse needs of both commercial and industrial facilities, providing optimal comfort and air quality.

One of the standout features of the Carrier 30RH and 30RA series is their versatility. These models are equipped with high-efficiency scroll compressors that offer exceptional performance while keeping energy consumption low. This not only translates to reduced operational costs but also helps in meeting stringent environmental regulations. The compressors work efficiently across a range of operating conditions, making these units suitable for various climates and applications.

Incorporating innovative technologies, the Carrier 30RH and 30RA series utilizes advanced controls to optimize performance. The carrier’s proprietary control system allows for seamless integration with building management systems, enabling remote monitoring and management. This connectivity ensures that operators can track energy usage and system performance in real-time, facilitating maintenance and problem-solving before issues escalate.

Both models include high-efficiency heat exchangers that enhance the heat transfer process, further promoting energy savings. The units are also designed to minimize sound levels, making them ideal for installation in noise-sensitive environments. With noise reduction features, the Carrier 30RH and 30RA units operate quietly, ensuring comfort in spaces where silence is paramount.

Durability is another core characteristic of these models. Built with robust materials and innovative engineering, the 30RH and 30RA series is designed to withstand the rigors of demanding commercial and industrial applications. Their reliable performance over time is backed by rigorous testing, ensuring longevity and reducing the likelihood of unexpected failures.

Environmental sustainability is a priority for Carrier, and the 30RH and 30RA series reflect this commitment. By utilizing environmentally friendly refrigerants and energy-efficient technologies, these units significantly reduce greenhouse gas emissions.

In summary, the Carrier 30RH and 30RA series are exemplary models that combine efficiency, advanced technology, and reliability. Their design focuses on optimizing comfort, reducing energy consumption, and ensuring longevity, making them an excellent choice for any commercial or industrial installation. Whether it’s in a bustling city center or a quiet suburban area, these units are engineered to deliver exceptional performance and value throughout their lifecycle.