Carrier 38AUQ appendix Convenience Outlets, Units Without Factory-Installed Disconnect, All units

Page 11

Field power wires are connected to the unit at line-side pres- sure lugs on compressor contactor C and TB1 (see wiring dia- gram label for control box component arrangement) or at facto- ry-installed option non-fused disconnect switch. Max wire size is #4 AWG (copper only).

NOTE: TEST LEADS - Unit may be equipped with short leads (pigtails) on the field line connection points on con- tactor C or optional disconnect switch. These leads are for factory run-test purposes only; remove and discard before connecting field power wires to unit connection points. Make field power connections directly to line connection pressure lugs only.

FIRE HAZARD

Failure to follow this warning could result in intermittent operation or performance satisfaction.

Do not connect aluminum wire between disconnect switch and condensing unit. Use only copper wire.

(See Fig. 8.)

ELECTRIC

DISCONNECT

SWITCH

COPPER

WIRE ONLY

ALUMINUM

WIRE

Fig. 8 — Disconnect Switch and Unit

Units Without Factory-Installed Disconnect —

When installing units, provide a disconnect switch per NEC (National Electrical Code) of adequate size. Disconnect sizing data is provided on the unit informative plate. Locate on unit cabinet or within sight of the unit per national or local codes. Do not cover unit informative plate if mounting the disconnect on the unit cabinet.

Units with Factory-Installed Disconnect —

The factory-installed option disconnect switch is located in a weatherproof enclosure located under the main control box. The manual switch handle is accessible through an opening in the access panel.

All units -

All field wiring must comply with NEC and all local codes. Size wire based on MCA (Minimum Circuit Amps) on the unit informative plate. See Fig. 9 for power wiring connections to the unit power terminal block and equipment ground. Maximum wire size is #4 ga AWG per pole.

Provide a ground-fault and short-circuit over-current protection device (fuse or breaker) per NEC Article 440 (or local codes). Refer to unit informative data plate for MOCP (Maximum Over-current Protection) device size.

Units Without Disconnect Option

C TB1

11 13

Disconnect

per

NEC

L1 L2 L3

208/230-3-60

460-3-60

575-3-60

Units With Disconnect Option

L1

2

 

1

 

 

 

Optional

 

Factory

L2

4

Disconnect

3

Wiring

 

 

Switch

 

 

 

 

 

L3

6

 

5

 

Disconnect factory test leads; discard.

Fig. 9 — Power Wiring Connections

All field wiring must comply with the NEC and local requirements.

Voltage and Current Balance -

Voltage to compressor terminals during operation must be within voltage range indicated on unit nameplate. See Table 10. On 3-phase units, voltages between phases must be balanced within 2% and the current within 10%. Use the formula shown in the legend for Table 8, Note 5 (see page 14) to determine the percent of voltage imbalance. Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation would invalidate any applicable Carrier warranty.

Convenience Outlets

ELECTRICAL OPERATION HAZARD

Failure to follow this warning could result in personal injury or death.

Units with convenience outlet circuits may use multiple disconnects. Check convenience outlet for power status before opening unit for service. Locate its disconnect switch, if appropriate, and open it. Tag-out this switch, if necessary.

Two types of convenience outlets are offered on 38AUQ models: Non-powered and unit-powered. Both types provide a 125-volt GFCI (ground-fault circuit-interrupter) duplex receptacle rated at 15-A behind a hinged waterproof access cover, located on the end panel of the unit. See Fig. 10.

11

Image 11
Contents Safety Considerations ContentsInstallation Installation GuidelineReplacement /Retrofit R22 to Puron 38AUQ*07-12 Unit Dimensions Qty...Type Pressurestat Settings psig High CutoutOperating Charge, Typical lb† Shipping Charge lbOperating Charge, Typical kg† Operating Weight kg Aluminum-Fin CoilsPressurestat Settings kPa High Cutout Nominal Capacity kWRefrigerant Options Service OptionsModel Type Type of CoilInstallation Puron-duty Filter Driers 38AUQ*07-12 Piping Recommendations Single-Circuit UnitMaximum Vertical Separation Insulation for Vapor Line Exposed To Outdoor Conditions Refrigerant Specialties Part NumbersComplete Electrical Connections Install AccessoriesField Power Supply All units Units Without Factory-Installed DisconnectUnits with Factory-Installed Disconnect Convenience OutletsConvenience Outlet Location Installing Weatherproof CoverThermostat Field Control WiringElectrical Data 38AUQ*07-12 Hz Units START-UP PRE-START-UPFinal Checks Advanced Scroll Temperature Protection AstpAdjust Refrigerant Charge Start Unit38AUQ*07 Charging Chart 38AUQ Wiring Diagram 208/230-3-60 shown Base Unit Controls Operating SequenceRefrigeration System Routine System MaintenanceService Quarterly Inspection 30 days after initial startOutdoor Coil Metering Devices Field Refrigerant Access PortsRefrigerant System Pressure Access Ports Liquid Line Filter DrierCommercial Defrost Control Heat Pump ControlsCompressor Protection Crankcase HeaterCompressor control Dip Switch PositionDefrost Reversing valve controlDefrost Speedup Functions Indoor Fan Off DelayDefrost Thermostats Fans Service Valves 38AUQ*08 Exterior 38AUQ*12 Exterior Input Comfort Alert Diagnostic ModuleLockout LED Status CodesLubrication Outdoor Coil Maintenance and Cleaning RecommendationPeriodic Clean Water Rinse Routine Cleaning of Indoor Coil SurfacesTorque Values Service PartsFastener Torque Values Troubleshooting Appendix B Appendix aCatalog No 38AUQ-01SI Appendix CPreliminary Information CUT Along Dotted Linecut Along Dotted Line

38AUQ specifications

The Carrier 38AUQ is a versatile and efficient air conditioning unit designed to meet a variety of residential and light commercial cooling needs. Known for its advanced technology and robust performance, the 38AUQ model showcases Carrier's commitment to sustainability and energy efficiency.

One of the standout features of the Carrier 38AUQ is its use of variable-speed inverter technology. This allows the unit to adjust its cooling output in response to the temperature demands of the environment. By operating at multiple speed levels, it minimizes energy consumption and maximizes comfort, ensuring a consistent, quiet cooling experience.

The 38AUQ is equipped with a high-efficiency compressor, which helps to further enhance its energy performance. This component plays a critical role in ensuring that the unit operates smoothly, reducing both electricity bills and the environmental impact. Efficiency ratings often exceed industry standards, making the 38AUQ a suitable choice for those looking to reduce their carbon footprint while enjoying a comfortable indoor climate.

In terms of design, the Carrier 38AUQ boasts a compact and sleek profile that allows for easy installation in a variety of settings. Its durable construction is built to withstand harsh weather conditions, ensuring longevity and reliability. Additionally, an advanced air purification system is integrated, featuring filters that capture airborne particles, improving indoor air quality.

The unit also offers a range of smart features, including compatibility with smart home systems. Users can remotely control their air conditioning via smartphone apps, allowing for customizable settings and energy management from anywhere. This connectivity aligns with modern living preferences, enhancing convenience and control.

Furthermore, the Carrier 38AUQ is designed with noise reduction in mind. The advanced sound-absorbing materials and quiet operation of its fan and compressor make it one of the quieter air conditioning options on the market. This is particularly beneficial for residential applications, where noise can be a significant concern.

Overall, the Carrier 38AUQ combines cutting-edge technology, energy efficiency, and user-friendly features, making it a top choice for both homeowners and small business operators seeking reliable cooling solutions. Its commitment to performance and efficiency makes it a standout model in the Carrier air conditioning lineup.