Carrier 38AUQ appendix Installing Weatherproof Cover, Convenience Outlet Location

Page 12

Convenience

Outlet

GFCI

Pwd-CO

Fuse

Switch

Pwd-CO

Transformer

Control Box

Access Panel

Fig. 10 — Convenience Outlet Location

Non-powered type: This type requires the field installation of a general-purpose 125-volt 15-A circuit powered from a source elsewhere in the building. Observe national and local codes when selecting wire size, fuse or breaker requirements and disconnect switch size and location. Route 125-v power supply conductors into the bottom of the utility box containing the duplex receptacle.

Unit-powered type: A unit-mounted transformer is factory- installed to stepdown the main power supply voltage to the unit to 115-v at the duplex receptacle. This option also includes a manual switch with fuse, located in a utility box and mounted on a bracket behind the convenience outlet; access is through the unit's control box access panel. See Fig. 10.

The primary leads to the convenience outlet transformer are not factory-connected. Selection of primary power source is a customer-option. If local codes permit, the transformer primary leads can be connected at the line-side terminals on the unit- mounted non-fused disconnect or HACR breaker switch; this will provide service power to the unit when the unit disconnect switch or HACR switch is open. Other connection methods will result in the convenience outlet circuit being de-energized when the unit disconnect or HACR switch is open. See Fig. 11.

12

UNIT

CONNECT

PRIMARY

TRANSFORMER

VOLTAGE

AS

CONNECTIONS

TERMINALS

208,

240

L1: RED + YEL

H1 + H3

230

L2: BLU + GRA

H2 + H4

 

 

 

L1: RED

H1

460

480

Splice BLU +

H2 + H3

YEL

 

 

H4

 

 

L2: GRA

 

 

 

575

600

L1: RED

H1

L2: GRA

H2

 

 

UNIT

CONNECT

PRIMARY

TRANSFORMER

VOLTAGE

AS

CONNECTIONS

TERMINALS

208,

240

L1: RED + YEL

H1 + H3

230

L2: BLU + GRA

H2 + H4

 

 

 

L1: RED

H1

 

 

Splice BLU +

460

480

H2 + H3

YEL

 

 

H4

 

 

L2: GRA

 

 

 

575

600

L1: RED

H1

L2: GRA

H2

 

 

Fig. 11 - Powered Convenience Outlet Wiring

Duty Cycle: the unit-powered convenience outlet has a duty cycle limitation. The transformer is intended to provide power on an intermittent basis for service tools, lamps, etc; it is not intended to provide 15-amps loading for continuous duty loads (such as electric heaters for overnight use). Observe a 50% limit on circuit loading above 8-amps (i.e., limit loads exceeding 8-amps to 30 minutes of operation every hour).

Test the GFCI receptacle by pressing the TEST button on the face of the receptacle to trip and open the receptacle. Check for proper grounding wires and power line phasing if the GFCI re- ceptacle does not trip as required. Press the RESET button to clear the tripped condition.

Fuse on power type: The factory fuse is a Bussman “Fusetron” T-15, non-renewable screw-in (Edison base) type plug fuse.

Using unit-mounted convenience outlets: Units with unit- mounded convenience outlet circuits will often require that two disconnects be opened to de-energize all power to the unit. Treat all units as electrically energized until the convenience outlet power is also checked and de-energization is confirmed. Observe National Electrical Code Article 210, Branch Circuits, for use of convenience outlets.

Installing Weatherproof Cover

A weatherproof while-in-use cover for the factory-installed convenience outlets is now required by UL standards. This cover cannot be factory-mounted due its depth; it must be installed at unit installation. For shipment, the convenience outlet is covered with a blank cover plate.

The weatherproof cover kit is shipped in the unit's control box. The kit includes the hinged cover, a backing plate and gasket.

DISCONNECT ALL POWER TO UNIT AND CONVENIENCE OUTLET.

Remove the blank cover plate at the convenience outlet; discard the blank cover.

Loosen the two screws at the GFCI duplex outlet, until approximately 1/2-in (13 mm) under screw heads are exposed.

Image 12
Contents Contents Safety ConsiderationsInstallation Guideline Replacement /Retrofit R22 to PuronInstallation 38AUQ*07-12 Unit Dimensions Pressurestat Settings psig High Cutout Operating Charge, Typical lb†Shipping Charge lb Qty...TypeOperating Weight kg Aluminum-Fin Coils Pressurestat Settings kPa High CutoutNominal Capacity kW Operating Charge, Typical kg†Service Options Model TypeType of Coil Refrigerant OptionsInstallation 38AUQ*07-12 Piping Recommendations Single-Circuit Unit Maximum Vertical SeparationPuron-duty Filter Driers Refrigerant Specialties Part Numbers Insulation for Vapor Line Exposed To Outdoor ConditionsInstall Accessories Field Power SupplyComplete Electrical Connections Units Without Factory-Installed Disconnect Units with Factory-Installed DisconnectConvenience Outlets All unitsInstalling Weatherproof Cover Convenience Outlet LocationField Control Wiring ThermostatElectrical Data 38AUQ*07-12 Hz Units PRE-START-UP START-UPAdvanced Scroll Temperature Protection Astp Adjust Refrigerant ChargeStart Unit Final Checks38AUQ*07 Charging Chart 38AUQ Wiring Diagram 208/230-3-60 shown Operating Sequence Base Unit ControlsRoutine System Maintenance ServiceQuarterly Inspection 30 days after initial start Refrigeration SystemField Refrigerant Access Ports Refrigerant System Pressure Access PortsLiquid Line Filter Drier Outdoor Coil Metering DevicesHeat Pump Controls Compressor ProtectionCrankcase Heater Commercial Defrost ControlDip Switch Position DefrostReversing valve control Compressor controlIndoor Fan Off Delay Defrost ThermostatsDefrost Speedup Functions Fans Service Valves 38AUQ*08 Exterior 38AUQ*12 Exterior Comfort Alert Diagnostic Module InputLED Status Codes LockoutOutdoor Coil Maintenance and Cleaning Recommendation Periodic Clean Water RinseRoutine Cleaning of Indoor Coil Surfaces LubricationService Parts Fastener Torque ValuesTorque Values Troubleshooting Appendix a Appendix BAppendix C Catalog No 38AUQ-01SIPreliminary Information CUT Along Dotted Linecut Along Dotted Line

38AUQ specifications

The Carrier 38AUQ is a versatile and efficient air conditioning unit designed to meet a variety of residential and light commercial cooling needs. Known for its advanced technology and robust performance, the 38AUQ model showcases Carrier's commitment to sustainability and energy efficiency.

One of the standout features of the Carrier 38AUQ is its use of variable-speed inverter technology. This allows the unit to adjust its cooling output in response to the temperature demands of the environment. By operating at multiple speed levels, it minimizes energy consumption and maximizes comfort, ensuring a consistent, quiet cooling experience.

The 38AUQ is equipped with a high-efficiency compressor, which helps to further enhance its energy performance. This component plays a critical role in ensuring that the unit operates smoothly, reducing both electricity bills and the environmental impact. Efficiency ratings often exceed industry standards, making the 38AUQ a suitable choice for those looking to reduce their carbon footprint while enjoying a comfortable indoor climate.

In terms of design, the Carrier 38AUQ boasts a compact and sleek profile that allows for easy installation in a variety of settings. Its durable construction is built to withstand harsh weather conditions, ensuring longevity and reliability. Additionally, an advanced air purification system is integrated, featuring filters that capture airborne particles, improving indoor air quality.

The unit also offers a range of smart features, including compatibility with smart home systems. Users can remotely control their air conditioning via smartphone apps, allowing for customizable settings and energy management from anywhere. This connectivity aligns with modern living preferences, enhancing convenience and control.

Furthermore, the Carrier 38AUQ is designed with noise reduction in mind. The advanced sound-absorbing materials and quiet operation of its fan and compressor make it one of the quieter air conditioning options on the market. This is particularly beneficial for residential applications, where noise can be a significant concern.

Overall, the Carrier 38AUQ combines cutting-edge technology, energy efficiency, and user-friendly features, making it a top choice for both homeowners and small business operators seeking reliable cooling solutions. Its commitment to performance and efficiency makes it a standout model in the Carrier air conditioning lineup.